background image

En-7

4-6. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi-

nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.

Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not 

a malfunction.

Procedure

Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the 

power supply.

•  Correction completes in 10 to 20 minutes. When the correction is completed, its result 

is shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch 

(SW871) again.

•  When the correction completed without error, do not press the piping/wiring correction 

switch (SW871) again.

When  the  result  was  “cannot  be  corrected”,  press  the  piping/wiring  correction  switch 

(SW871) again to cancel this function. Then, confirm the wiring and piping combination in 

a conventional manner by operating the indoor units one by one.

•  The operation is done while the power is supplied. Make sure not to contact parts other 

than the switch, including the P.C. board. This may cause electric shock or burn by hot 

parts and live parts around the switch. Contacting the live parts may cause P.C. board 

damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimination 

before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED1 

(Red)

LED2 

(Yellow)

LED3 

(Green)

Lighted

Lighted

Once

Result of piping/wiring correction function

LED1 

(Red)

LED2 

(Yellow)

LED3 

(Green)

Result

Lighted Not lighted Lighted

Completed

(Problem corrected or 

normal)

Once

Once

Once

Not completed 

(Detection failed)

Other indications

Refer to “SAFETY PRE-

CAUTIONS WHEN LED 

BLINKS” located behind 

the service panel.

4-7. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Turn off the breaker.

2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

3) Fully close the stop valve on the liquid pipe side of the outdoor unit.

4) Turn on the breaker.

5) Start the emergency COOL operation on all the indoor units.

6) When the pressure gauge shows 0 – 0.05 MPa [Gauge] (approx. 0 – 0.5 kgf/cm

2

), fully close the stop valve on the gas pipe side of the outdoor unit and 

stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)

  *  If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0 – 0.05 MPa [Gauge] (approx. 0 – 0.5 kgf/cm

2

), or 

the protection function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device 

to collect all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have 

been relocated.

7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.

The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

 

WARNING

5.  PUMPING DOWN

BH79A198H01_en.indd   7

6/2/2015   5:48:29 PM

Содержание MXZ-4E83VAHZ

Страница 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Страница 2: ...ng sections so the stress of the wires is not applied to the sections Do not extend the wires or use intermediate connection Incomplete connecting and securing could cause fire n Do not install the unit in a place where inflammable gas may leak If gas leaks and accumulates in the area around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extensio...

Страница 3: ...ind it is recommended to install a baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring sewage waste water Where there is high frequency or wireless equipme...

Страница 4: ...iping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insula tion vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for new refri...

Страница 5: ...ot to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 ...

Страница 6: ...ith Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor ...

Страница 7: ...o lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if this function is activated Changing the setti...

Страница 8: ...tronic control P C board damage make sure to perform static elimination before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Problem correct...

Страница 9: ... plaque du produit Opmerking het serienummer staat op het naamplaatje van het product Nota El número de serie se encuentra en la placa que contiene el nombre del producto Nota il numero di serie si trova sulla targhetta del prodotto Σημείωση Ο σειριακός του αριθμός βρίσκεται στην πινακίδα ονόματος του προϊόντος Nota o número de série encontra se na placa que contém o nome do produto Bemærk Serienu...

Отзывы: