background image

En-1

1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY

•  Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.

•  Be sure to observe the warnings and cautions specified here as they include important items related to safety.

•  After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.

•  Equipment complying with IEC/EN 61000-3-12.

1-2. SPECIFICATIONS

Model

Power supply *1

Wire specifications *2

Pipe length and height difference *3, *4, *5, *6, *7, *8

Outdoor Noise level

Rated 

Voltage

Fre-

quency

Breaker 

capacity

Power 

supply

Indoor/outdoor 

connecting wire

Max. pipe 

length per 

indoor unit / for 

multi-system

Max. height 

difference *9

Max. no. of bends 

per indoor unit / 

for multi system

Refrigerant 

adjust-

ment A

Cooling

Heating

MXZ-6D122VA

230 V

50 Hz

32 A

3-core 

4.0 mm

2

4-core 

1.0 / 1.5 mm

2

25 m / 80 m

15 m

25 / 80

20 g/m *10 55 dB (A)

57 dB (A)

MXZ-4E83VAHZ

30 A

25 m / 70 m

25 / 70

20 g/m *11 53 dB (A)

*1  Connect to the power switch which has a gap of 3 mm or more when open 

to interrupt the source power phase. (When the power switch is shut off, it 

must interrupt all phases.)

*2  Use wires in conformity with design 60245 IEC 57. Use the indoor/outdoor 

connecting wire in conformity with the wire specifications specified in the 

installation manual of the indoor unit.

*3  Never use pipes with thickness less than specified. The pressure resistance 

will be insufficient.

*4  Use a copper pipe or a copper-alloy seamless pipe.

*5  Be careful not to crush or bend the pipe during pipe bending.

*6  Refrigerant pipe bending radius must be 100 mm or more.

*7  Insulation material : Heat resisting foam plastic 0.045 specific gravity

*8  Be sure to use the insulation of specified thickness. Excessive thickness 

may cause incorrect installation of the indoor unit and insufficient thickness 

may cause dew drippage.

*9  If the outdoor unit is installed higher than the indoor unit, max. height 

difference is reduced to 10 m.

*10 If pipe length exceeds 30 m, additional refrigerant (R410A) charge is re-

quired. (No additional charge is required for pipe length less than 30 m.)

  Additional refrigerant = A × (pipe length (m) - 30)

*11 If pipe length exceeds 25 m, additional refrigerant (R410A) charge is re-

quired. (No additional charge is required for pipe length less than 25 m.) 

Additional refrigerant = A × (pipe length (m) - 25)

Required Tools for Installation

Phillips screwdriver

Level

Scale

Utility knife or scissors

Torque wrench

Wrench (or spanner)

4 mm hexagonal wrench

Flare tool for R410A

Gauge manifold for R410A

Vacuum pump for R410A

Charge hose for R410A

Pipe cutter with reamer

 ENGLISH

CONTENTS

1. BEFORE INSTALLATION ............................................................1

2. OUTDOOR UNIT INSTALLATION ...............................................4

3. FLARING WORK AND PIPE CONNECTION ...............................5

4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN ......... 5

5. PUMPING DOWN ........................................................................7

 

CAUTION

(Could lead to serious injury in particular environments when operated incorrectly.)

n

  Do not install the unit by yourself (user).

  Incomplete installation could cause fire or electric shock, injury due to the unit 

falling, or leakage of water. Consult the dealer from whom you purchased 

the unit or a qualified installer.

n

  Perform the installation securely referring to the installation manual.

  Incomplete installation could cause fire, electric shock, injury due to the 

unit falling, or leakage of water.

n

 When installing the unit, use appropriate protective equipment and 

tools for safety.

  Failure to do so could cause injury.

n

 Install the unit securely in a place which can bear the weight of the 

unit.

  If the installation location cannot bear the weight of the unit, the unit could 

fall causing injury.

Electrical work should be performed by a qualified, experienced electri-

cian, according to the installation manual. Be sure to use an exclusive 

circuit. Do not connect other electrical appliances to the circuit.

  If  the  capacity  of  the  power  circuit  is  insufficient  or  there  is  incomplete 

electrical work, it could result in a fire or an electric shock.

Do not damage the wires by applying excessive pressure with parts 

or screws.

  Damaged wires could cause fire or electric shock.

Be sure to cut off the main power in case of setting up the indoor P.C. 

board or wiring works.

  Failure to do so could cause electric shock.

n

  Use  the  specified  wires  to  connect  the  indoor  and  outdoor  units 

securely and attach the wires firmly to the terminal block connecting 

sections so the stress of the wires is not applied to the sections. Do 

not extend the wires, or use intermediate connection.

  Incomplete connecting and securing could cause fire.

Do not install the unit in a place where inflammable gas may leak.

  If gas leaks and accumulates in the area around the unit, it could cause an 

explosion.

n

  Do not use intermediate connection of the power cord or the extension 

cord and do not connect many devices to one AC outlet.

  It could cause a fire or an electric shock due to defective contact, defective 

insulation, exceeding the permissible current, etc.

Be sure to use the parts provided or specified parts for the installation 

work.

  The use of defective parts could cause an injury or leakage of water due 

to a fire, an electric shock, the unit falling, etc.

When plugging the power supply plug into the outlet, make sure that 

there is no dust, clogging, or loose parts in both the outlet and the 

plug. Make sure that the power supply plug is pushed completely into 

the outlet. 

  If there is dust, clogging, or loose parts on the power supply plug or the 

outlet, it could cause electric shock or fire. If loose parts are found on the 

power supply plug, replace it.

Attach the electrical cover to the indoor unit and the service panel 

to the outdoor unit securely.

  If the electrical cover of the indoor unit and/or the service panel of the 

outdoor unit are not attached securely, it could result in a fire or an electric 

shock due to dust, water, etc.

When installing, relocating, or servicing the unit, make sure that no 

substance other than the specified refrigerant (R410A) enters the 

refrigerant circuit.

  Any presence of foreign substance such as air can cause abnormal pres-

sure rise and may result in explosion or injury. The use of any refrigerant 

other than that specified for the system will cause mechanical failure, 

system malfunction, or unit breakdown. In the worst case, this could lead 

to a serious impediment to securing product safety.

Do not discharge the refrigerant into the atmosphere. If refrigerant 

leaks during installation, ventilate the room.

  If refrigerant comes in contact with a fire, harmful gas could be gener-

ated. Refrigerant leakage may cause suffocation. Provide ventilation in 

accordance with EN378-1.

Check that the refrigerant gas does not leak after installation has 

been completed.

  If refrigerant gas leaks indoors, and comes into contact with the flame of a 

fan heater, space heater, stove, etc., harmful substances will be generated.

Use appropriate tools and piping materials for installation. 

  The pressure of R410A is 1.6 times more than R22. Not using appropriate 

tools or materials and incomplete installation could cause the pipes to 

burst or injury. 

When pumping down the refrigerant, stop the compressor before 

disconnecting the refrigerant pipes.

  If the refrigerant pipes are disconnected while the compressor is running 

and the stop valve is open, air could be drawn in and the pressure in the 

refrigeration cycle could become abnormally high. This could cause the 

pipes to burst or injury. 

When installing the unit, securely connect the refrigerant pipes 

before starting the compressor.

  If the compressor is started before the refrigerant pipes are connected 

and when the stop valve is open, air could be drawn in and the pressure 

in the refrigeration cycle could become abnormally high. This could cause 

the pipes to burst or injury.

Fasten a flare nut with a torque wrench as specified in this manual.

  If fastened too tight, a flare nut may break after a long period and cause 

refrigerant leakage.

The unit shall be installed in accordance with national wiring regula-

tions.

n

  Earth the unit correctly.

  Do not connect the earth to a gas pipe, water pipe, lightning rod or tel-

ephone earth. Defective earthing could cause electric shock.

n

  Be sure to install an earth leakage breaker.

  Failure to install an earth leakage breaker may result in electric shock or fire.

n

  Perform the drainage/piping work securely according to the installation 

manual.

  If there is defect in the drainage/piping work, water could drop from the unit, 

soaking and damaging household goods.

n

  Do not touch the air inlet or the aluminum fins of the outdoor unit.

  This could cause injury. 

n

  Do not install the outdoor unit where small animals may live.

  If small animals enter and touch the electric parts inside the unit, it could 

cause a malfunction, smoke emission, or fire. Also, advise user to keep 

the area around the unit clean. 

 

WARNING

(Could lead to death, serious injury, etc.)

1.  BEFORE INSTALLATION

BH79A198H01_en.indd   1

6/2/2015   5:48:27 PM

Содержание MXZ-4E83VAHZ

Страница 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Страница 2: ...ng sections so the stress of the wires is not applied to the sections Do not extend the wires or use intermediate connection Incomplete connecting and securing could cause fire n Do not install the unit in a place where inflammable gas may leak If gas leaks and accumulates in the area around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extensio...

Страница 3: ...ind it is recommended to install a baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring sewage waste water Where there is high frequency or wireless equipme...

Страница 4: ...iping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insula tion vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for new refri...

Страница 5: ...ot to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 ...

Страница 6: ...ith Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor ...

Страница 7: ...o lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if this function is activated Changing the setti...

Страница 8: ...tronic control P C board damage make sure to perform static elimination before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Problem correct...

Страница 9: ... plaque du produit Opmerking het serienummer staat op het naamplaatje van het product Nota El número de serie se encuentra en la placa que contiene el nombre del producto Nota il numero di serie si trova sulla targhetta del prodotto Σημείωση Ο σειριακός του αριθμός βρίσκεται στην πινακίδα ονόματος του προϊόντος Nota o número de série encontra se na placa que contém o nome do produto Bemærk Serienu...

Отзывы: