4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air conditioner 

for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerat-

ing cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 

liquid refrigerant. Adding gas refrigerant may change the composition of the refriger-

ant in the system and affect normal operation of the air conditioner. Also, charge 

the liquid refrigerant slowly, otherwise the compressor will be locked.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

COOL/DRY

HEAT

•  Description of the function:

  With this function, once the operation mode is locked to either COOL/DRY mode 

or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “3” of SW1 on the outdoor controller board to ON to enable this function.

3) To lock the operation mode in COOL/DRY mode, set the “4” of SW1 on the 

outdoor controller board to OFF. To lock the operation in HEAT mode, set the 

same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:

  With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 

However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Union

Stop valve

Liquid 

pipe

Indoor 

unit

Stop valve with 

service port

Gas 

pipe

Refrigerant gas 

cylinder  

operating valve

(for R410A)

Gauge manifold 

valve (for R410A)

Charge hose 

(for R410A)

Refrigerant gas cylinder for R410A with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

Union

Union
Union

4-5. CHANGING THE AMPERE LIMIT

•  Description of the function:

  With this function, the amount of current that flows in the outdoor unit can be 

changed.

Note:

Use this function only when the amount of current exceeds the allowed value.

[How to change the ampere limit]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Make the setting referring to the table below.

3) Turn on the main power for the air conditioner.

SW2

MXZ-6D122VA

MXZ-4E83VAHZ

ON

1   2   3   4   5   6

20A

21A

ON

1   2   3   4   5   6

Factory setting 

Full

Factory setting 

Full

SW1

ON

1   2   3   4   5   6

SW1

ON

1   2   3   4   5   6

SW1

ON

1   2   3   4   5   6

Lower the operating noise

[How to lower the operating noise]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “5” of SW1 on the outdoor controller board to ON to enable this function.

3) Turn on the main power for the air conditioner.

LED

SW1

SW871

SW2

Model

Indoor unit

MXZ-6D122VA

A

 - 

F

MXZ-4E83VAHZ

A

 - 

D

BH79A198H01_en.indd   6

6/2/2015   5:48:29 PM

Содержание MXZ-4E83VAHZ

Страница 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Страница 2: ...ng sections so the stress of the wires is not applied to the sections Do not extend the wires or use intermediate connection Incomplete connecting and securing could cause fire n Do not install the unit in a place where inflammable gas may leak If gas leaks and accumulates in the area around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extensio...

Страница 3: ...ind it is recommended to install a baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring sewage waste water Where there is high frequency or wireless equipme...

Страница 4: ...iping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insula tion vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for new refri...

Страница 5: ...ot to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 ...

Страница 6: ...ith Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor ...

Страница 7: ...o lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if this function is activated Changing the setti...

Страница 8: ...tronic control P C board damage make sure to perform static elimination before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Problem correct...

Страница 9: ... plaque du produit Opmerking het serienummer staat op het naamplaatje van het product Nota El número de serie se encuentra en la placa que contiene el nombre del producto Nota il numero di serie si trova sulla targhetta del prodotto Σημείωση Ο σειριακός του αριθμός βρίσκεται στην πινακίδα ονόματος του προϊόντος Nota o número de série encontra se na placa que contém o nome do produto Bemærk Serienu...

Отзывы: