11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
TROUBLESHOOTING
11
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To
make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service
work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
Lead wiring
Connector housing
<Incorrect>
<Correct>
10-1. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 11-6-1.)
Jumper wire
Defrost fi nish temperature (
°C
)
MUZ-EF25VE -
E1
MUZ-EF25VE -
E2
,
E3
,
E4
,
E5
,
ER3
,
ER4
,
ER5
,
ET3
,
ET4
,
ET5
MUZ-EF25VEH
MUZ-EF35VE
MUZ-EF35VEH
MUZ-EF42VE
MUZ-EF50VE
JS
Soldered
(Initial setting)
5°C
8°C
10°C
10°C
5°C
9°C
None (Cut)
8°C
15°C
13°C
15°C
10°C
18°C
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature.
The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermis-
tor is 20°C or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 11-6.1.)
NOTE:
When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
OBH590G
Содержание MUZ-EF25VE
Страница 11: ...11 MUZ EF25VE E5 ER5 ET5 MUZ EF35VE E5 ER5 ET5 MUZ EF25VEH E1 MUZ EF35VEH E1 OBH590G ...
Страница 12: ...12 MUZ EF25VEH E4 MUZ EF35VEH E4 MUZ EF25VEH E2 E3 ER2 ER3 ET2 ET3 MUZ EF35VEH E2 E3 ER2 ER3 ET2 ET3 OBH590G ...
Страница 13: ...13 MUZ EF42VE E1 MUZ EF50VE E1 MUZ EF42VE E2 E3 E4 ER3 ER4 ET3 ET4 MUZ EF50VE E2 ER2 ET2 OBH590G ...
Страница 14: ...14 MUZ EF42VE E5 ER5 ET5 MUZ EF50VE E3 ER3 ET3 OBH590G ...
Страница 57: ...57 OBH590G ...