3. Outdoor unit failure mode table
The left
lamp of
OPERATION
INDICATOR
lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit
failure mode
recall function
OFF None
(Normal)
—
—
—
—
—
1-time fl ash
2.5 seconds
OFF
Indoor/outdoor
communication, receiving
error
—
Any signals from the inverter P.C.
board cannot be received normally for
3 minutes.
•Refer to 11-5. How
to check miswiring and
serial signal error.
○
○
Indoor/outdoor
communication, receiving
error
—
Although the inverter P.C. board sends
signal "0", signal "1" has been received
30 consecutive times.
•Refer to 11-5. How
to check miswiring and
serial signal error.
2-time fl ash
2.5 seconds
OFF
Outdoor power system
—
Overcurrent protection cut-out
operates 3 consecutive times within
1 minute after the compressor gets
started.
• Reconnect
connectors.
• Refer to 11-5. "How
to check inverter/
compressor".
• Check the stop valve.
○
○
3-time fl ash
2.5 seconds
OFF
Discharge temperature
thermistor
1-time fl ash every
2.5 seconds
Thermistor shorts or opens during
compressor running.
• Refer to 11-5.
"Check of outdoor
thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
○
○
Defrost thermistor
Fin temperature thermistor
3-time fl ash
2.5 seconds OFF
P.C. board temperature
thermistor
4-time fl ash
2.5 seconds OFF
Ambient temperature
thermistor
2-time fl ash
2.5 seconds OFF
Outdoor heat exchanger
temperature thermistor
—
4-time fl ash
2.5 seconds
OFF
Overcurrent 11-time
fl ash
2.5 seconds OFF
Large current fl ows into intelligent
power module.
• Reconnect
compressor connector.
• Refer to 11-5. "How
to check inverter/
compressor".
• Check the stop valve.
—
○
Compressor synchronous
abnormality (Compressor
start-up failure protection)
12-time fl ash
2.5 seconds OFF
Waveform of compressor current is
distorted.
• Reconnect
compressor connector.
• Refer to 11-5. "How
to check inverter/
compressor".
—
○
5-time fl ash
2.5 seconds
OFF
Discharge temperature
—
Temperature of discharge temperature
thermistor exceeds 116°C, compressor
stops.
Compressor can restart if discharge
temperature thermistor reads 100°C or
less 3 minutes later.
• Check the refrigerant
circuit and the
refrigerant amount.
• Refer to 11-5. "Check
of LEV".
—
○
6-time fl ash
2.5 seconds
OFF
High pressure
—
Temperature indoor coil thermistor
exceeds 70°C in HEAT mode.
Temperature defrost thermistor
exceeds 70°C in COOL mode.
• Check the refrigerant
circuit and the
refrigerant amount.
• Check the stop valve.
—
○
7-time fl ash
2.5 seconds
OFF
Fin temperature/ P.C. board
temperature
7-time fl ash
2.5 seconds OFF
Temperature of fi n temperature
thermistor on the inverter P.C. board
exceeds 75 ~ 86°C, or temperature of
P.C. board temperature thermistor on
the inverter P.C. board exceeds 72 ~
85°C.
• Check the around
outdoor unit.
• Check the outdoor unit
air passage.
• Refer to 11-5. "Check
of outdoor fan motor".
—
○
8-time fl ash
2.5 seconds
OFF
Outdoor fan motor
—
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor
fan start-up.
• Refer to 11-5. "Check
of outdoor fan motor".
Refer to 11-5. "Check
of inverter P.C. board".
—
○
9-time fl ash
2.5 seconds
OFF
Nonvolatile memory data
5-time fl ash
2.5 seconds OFF
Nonvolatile memory data cannot be
read properly.
• Replace the inverter
P.C. board.
○
○
Power module
6-time fl ash
2.5 seconds OFF
The interface short circuit occurs in the
output of the intelligent power module
(IC700).
The compressor winding shorts circuit.
• Refer to 11-5. "How
to check inverter/
compressor".
NOTE:
Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
OBH590G
Содержание MUZ-EF25VE
Страница 11: ...11 MUZ EF25VE E5 ER5 ET5 MUZ EF35VE E5 ER5 ET5 MUZ EF25VEH E1 MUZ EF35VEH E1 OBH590G ...
Страница 12: ...12 MUZ EF25VEH E4 MUZ EF35VEH E4 MUZ EF25VEH E2 E3 ER2 ER3 ET2 ET3 MUZ EF35VEH E2 E3 ER2 ER3 ET2 ET3 OBH590G ...
Страница 13: ...13 MUZ EF42VE E1 MUZ EF50VE E1 MUZ EF42VE E2 E3 E4 ER3 ER4 ET3 ET4 MUZ EF50VE E2 ER2 ET2 OBH590G ...
Страница 14: ...14 MUZ EF42VE E5 ER5 ET5 MUZ EF50VE E3 ER3 ET3 OBH590G ...
Страница 57: ...57 OBH590G ...