13
8.1.P
ower suppl
y
8.1.1.
Indoor unit power supplied fr
om outdoor unit
The follo
wing connection patterns are a
vailab
le.
The outdoor unit pow
er supply patterns v
ary on models
.
1:1 System
[Fig. 8-1-1] (P
.5)
A
Outdoor unit power supply
B
Earth leakage break
er
C
Wiring circuit break
er or isolating switch
D
Outdoor unit
E
Indoor unit/outdoor unit connecting cords
F
Wired remote controller
G
Indoor unit
H
Indoor controller board
J
Radio frequency interface f
or RF thermostat
*
Affix a label A that is included with the manuals near each wir
ing diagram f
or the
indoor and outdoor units.
Field electrical wir
ing
*1.The
10 m [32 ft] wire is attached in the wired remote controller accessor
y . Max.
500 m [1640 ft]
*2.The figures are NOT always against the ground.
S3 terminal has 24
V DC against S2 terminal.
Howe
ver betw
een S3 and S1, these terminals
are not electrically insulataed by the tr
ansfor
mer or other device
.
Notes:
1.
Wiring size m
ust comply with the applicab
le local and national code.
2.Power supply cords and indoor unit/outdoor unit connecting cords
shall not be lighter than polychloroprene sheathed flexible cord.
(Design 245 IEC57)
3.Install an ear
th longer than other cab
les.
Caution:
Do not use anything other than the correct capacity breaker and fuse
. Using fuse
,
wire or copper wire with too larg
e capacity may cause a risk of malfunction or fire
.
8.2.Indoor wire connection
Work
procedure
1.Remo
ve 2 scre
ws to detach the electric component co
ver
.
2.Route each cab
le through the wiring intake into the electr
ic component box.
(Pro-
cure power cab
le and in-out connecting cable locally and use
wired remote control
cable supplied with the unit.)
3.Securely connect the po
wer cab
le and the in-out connecting cable and the
wired
remote control cable to the ter
minal bloc
ks.
4.F
or radio frequency interf
ace
Connect the electric wires securely to the CN105 (RED) of indoor controller board.
Connect the electric wires securely to the corresponding ter
minals.
5.Secure the cab
les with clamps inside the electric component bo
x.
6.Attach the electr
ic component cov
er as it was
.
•
Fix pow
er supply cable and indoor/outdoor cab
le to control box b
y using buff
er
bushing f
or tensile force
. (PG connection or the lik
e.)
W
arning:
•
Attach the electrical par
t cover securel
y. If it is attac
hed incorrectly,
it could
result in a fire, electric shoc
k due to dust, water
, etc.
•
Use the specified indoor/outdoor unit connecting wire to connect the indoor
and outdoor units and fix the wire to the terminal bloc
k securely so that no
stress is applied to the connecting section of the terminal bloc
k. Incomplete
connection or fixing of the wire could result in a fire.
[Fig. 8-2-1] (P
.6)
A
Screw holding co
ver (1pc)
B
Cover
[Fig. 8-2-2] (P
.6)
C
T er
minal box
D
Knockout hole
E
Remove
8.
Electrical work
[Fig. 8-2-3] (P
.6)
F
Use PG bushing to k
eep the weight of the cab
le and exter
nal force from being applied to the
power supply ter
minal connector. Use a cab
le tie to secure the cable
.
G
Pow
er source wiring
H
Use ordinary b
ushing
I
T ransmission wiring
J
Conduit
K
Side frame
L
Knockout hole (f
or power source wiring)
M
Washer (accessor
y)
[Fig. 8-2-4] (P
.6)
N
T er
minal bloc
k for po
wer source and indoor transmission
O
T er
minal bloc
k for wired remote controller
P
Indoor controller board
Q
Radio frequency interface is installed on Indoor controller board
R
CN105 (RED/5P)
S
Wiring f
or radio frequency interf
ace
•
Perf
orm wir
ing as shown in the diag
ram to the lo
wer left. (Procure the cab
le locally.)
Make sure to use cab
les of the correct polarity only .
[Fig. 8-3] (P
.6)
A
Indoor terminal b
lock
B
Earth wire (g
reen/yello
w)
C
Indoor/outdoor unit connecting wire 3-core 1.5 mm
2
[AWG 16] or more
D
Outdoor terminal b
lock
1
Connecting cable
Cable 3-core 1.5 mm
2
[AWG 16], in conf
ormity with Design 245 IEC 57.
2
Indoor terminal b
lock
3
Outdoor terminal b
lock
4
Alwa
ys install an earth wire (1-core 1.5 mm
2
[AWG 16]) longer than other cab
les
5
Wired remote controller cable
Wire No
×
size (mm
2
) : Cab
le 2C
×
0.3
This wire accessory of remote controller
(wire length : 10 m [32 ft], non-polar
. Max.
500 m [1640 ft])
6
Wired remote controller
•
Connect the terminal b
locks as sho
wn in the diagram belo
w.
Caution:
•
Use care not to make mis-wiring.
•
Firmly tighten the terminal scre
ws to prevent them fr
om loosening.
•
After tightening, pull the wires lightl
y to confirm that they do not mo
ve.
8.3.Remote contr
oller
8.3.1.
For wired remote controller
1)
Tw
o wired remote controller
s setting
If two wired remote controllers are connected, set one to
“Main” and the other to
“Sub”. F
or setting procedures, ref
er to “Function selection of remote controller”
in the
operation manual f
or the indoor unit.
8.3.2.
For IR wireless remote controller
1)
Installation area
•
Area in which the IR wireless remote controller is not exposed to direct sunshine
.
•
Area in which there is no near by heating source
.
•
Area in which the IR wireless remote controller is not exposed to cold (or hot) winds.
•
Area in which the IR wireless remote controller can be operated easily
.
•
Area in which the IR wireless remote controller is beyond the reach of children.
* The signal can tr
av
el up to approximately 7 meters [23 ft] (in a streight line) within 45
degrees to both r
ight and left of the center line of the receiver
.
2)
Setting the Model No.
[Fig. 8-4] (P
.6)
1
Insert batter
ies.
2
Press the SET button with something shar
p at the end.
Start this oper
ation from the status of IR wireless remote controller display
turned off
.
MODEL SELECT
blinks and Model No
. is lighted.
3
Press the temp
button to set the Model No
.
4
Press the SET button with something shar
p at the end.
MODEL SELECT
and Model No. are lighted f
or three seconds, then tur
ned off.
Indoor Unit Model
A
Model No.
PEAD
026
Indoor unit model
Wir
ing Wire
No
.
×
siz
e (mm
2
)
Circuit
rating
Indoor unit power supply (Heater)
Indoor unit power supply (Heater) earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Wired remote controller-Indoor unit
*1
Indoor unit (Heater) L-N
*2
Indoor unit-Outdoor unit S1-S2
*2
Indoor unit-Outdoor unit S2-S3
*2
Wired remote controller-Indoor unit
*2
PEAD
–
–
3
×
1.5 (polar)
1
×
Min. 1.5
2
×
0.3 (Non-polar)
–
230 V A
C
24 V DC
14 V DC
WT06034X01_GB.p65
10.8.31, 15:32
13