![Mitsubishi Electric Mr.Slim MUZ-A17NA Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-muz-a17na/mr-slim-muz-a17na_service-manual_1810119048.webp)
48
●
Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance be-
tween the compressor terminals.
<<Measurement point>>
At 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>>
Refer to 10-4.
0 [
Ω
] ················Abnormal (short)
Infinite [
Ω
] ·······Abnormal (open)
NOTE:
1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 68°F (20°C).
Refer to "3. SPECIFICATION".
Measure the resistance between the lead wires at 3 points.
B Check of open phase
MUZ-A09/12/15/17 MUY-A15/17
MUZ-A09/12/15/17 MUY-A15/17
MUZ-A09/12/15/17 MUY-A15/17
ohmmeter indication
••••••Normal
(infinite)
••••••Abnormal
(0~dozens of
Ω
)
X1
X1
Ω
Ω
D Check of compressor
C Check of intelligent power module
MUZ-A09/12/15/17 MUY-A15/17
E Check of compressor winding
●
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if
the inverter is normal by measuring the balance of voltage between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION
switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-7.)
<<Measurement point>>
at 3 points
BLK (U) - WHT (V)
BLK (U) - RED (W)
WHT(V) - RED (W)
NOTE
: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of inverter P.C. board
fl
ashes 9 times. (Refer to 10-6.1.)
●
Measure the resistance between the terminals on the intelligent power module.
<<Measurement point>>
At 6 points
BLK-WHT, WHT-BLK
BLK-RED, RED-BLK
WHT-RED, RED-WHT
<<Judgement>>
In
fi
nite [
Ω
]············Normal
0 - dozens of········Abnormal (short)
Refer to 10-5. “Check of compressor
operation time”.
Does the compressor operate continuously?
OK.
No
Yes
Refer to 10-5. “Check of compressor
winding”.
Is the compressor normal?
Replace the compressor.
No
Yes
Is the compressor operation
time more than 10 seconds?
Check the refrigerant circuit.
Yes
Replace the compressor.
No
LED
Inverter P.C. board
(Parts side)
9-time flash
2.5-second OFF
Flashing
Содержание Mr.Slim MUZ-A17NA
Страница 12: ...12 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA 5 WIRING DIAGRAM ...
Страница 13: ...13 MUY A15NA MUY A17NA ...
Страница 14: ...14 MUZ A24NA MUZ A24NA U1 ...
Страница 15: ...15 MUZ A24NA 1 MUZ A24NA U2 ...
Страница 16: ...16 MUY A24NA ...
Страница 17: ...17 MUY A24NA 1 ...
Страница 18: ...18 MUZ GA24NA ...
Страница 19: ...19 MUY GA24NA ...
Страница 74: ...74 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 OUTDOOR UNIT ELECTRICAL PARTS 2 3 5 6 7 ...
Страница 80: ...80 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 OUTDOOR UNIT ELECTRICAL PARTS 2 3 5 6 7 ...