22
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft.
Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-A09NA
MUZ-A12NA
65 40
3/8 1/4
MUZ-A15NA
MUY-A15NA
MUZ-A17NA
MUY-A17NA
1/2 1/4
MUZ-A24NA
MUY-A24NA
MUZ-GA24NA
MUY-GA24NA
100 50 5/8 1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
65
MUZ-A09NA
MUZ-A09NA -
U1
MUZ-A12NA
2 lb. 5 oz.
0
1.62
4.86
8.10
11.34
12.96
MUZ-A09NA -
1
MUZ-A09NA -
U2
2 lb.
MUZ-A15NA
MUY-A15NA
MUZ-A17NA
MUY-A17NA
2 lb. 7 oz.
Calculation: X oz. = 1.62/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
70
80
90
100
MUZ-A24NA
MUY-A24NA
MUZ-GA24NA
MUY-GA24NA
4
lb.
0
1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Содержание Mr.Slim MUZ-A17NA
Страница 12: ...12 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA 5 WIRING DIAGRAM ...
Страница 13: ...13 MUY A15NA MUY A17NA ...
Страница 14: ...14 MUZ A24NA MUZ A24NA U1 ...
Страница 15: ...15 MUZ A24NA 1 MUZ A24NA U2 ...
Страница 16: ...16 MUY A24NA ...
Страница 17: ...17 MUY A24NA 1 ...
Страница 18: ...18 MUZ GA24NA ...
Страница 19: ...19 MUY GA24NA ...
Страница 74: ...74 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 OUTDOOR UNIT ELECTRICAL PARTS 2 3 5 6 7 ...
Страница 80: ...80 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 OUTDOOR UNIT ELECTRICAL PARTS 2 3 5 6 7 ...