3 SIGNALS AND WIRING
3.2 Example I/O signal connections
49
3
MR-J5D1-_G_
Sink I/O interface
*1 To prevent an electric shock, connect the protective earth (PE) terminal (the terminal marked with the symbol) of the drive unit to the
protective earth (PE) of the cabinet.
*2 Connect the diode in the correct direction. If it is connected reversely, the drive unit may malfunction and not output signals, disabling
protective circuits such as EM2 (Forced stop 2).
*3 If the controller does not have the forced stop function, install a forced stop 2 switch (normally closed contact).
*4 When starting operation, turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end), and LSN (Reverse rotation stroke end)
(normally closed contact). If FLS (Upper stroke limit) and RLS (Lower stroke limit) are used via a controller, wiring LSP and LSN is
unnecessary. In that case, set [Pr. PD41].
*5 Use SW1DNC-MRC2-_.
*6 Supply 24 V DC ± 10 % to interfaces from outside. The total current capacity of these power supplies is 300 mA maximum.
The amperage will not exceed 300 mA when all I/O signals are used. Reducing the number of I/O points decreases the current capacity.
For the amperage required for interfaces, refer to the following.
Page 77 Digital input interface DI-1
Although the diagram shows the input signal and the output signal each using a separate 24 V DC power supply for illustrative purposes,
the system can be configured to use a single 24 V DC power supply.
*7 If no alarm is occurring, ALM (Malfunction) is on (normally closed contact).
*8 In the initial setting, INP (In-position) is assigned to this pin. The device of the pin can be changed with [Pr. PD08].
*9 The devices of these pins can be changed with servo parameters ([Pr. PD07] to [Pr. PD09]).
*10 The devices of these pins can be changed with servo parameters ([Pr. PD03] to [Pr. PD05]).
*11 To prevent an unexpected restart of the drive unit, configure a circuit that turns off EM2 when the main circuit power supply is turned off.
*12 If not using the STO function, attach the short-circuit connector that came with the drive unit.
*13 This device can be changed to TPR3 (touch probe 3) by servo parameter settings. To set the device to TPR3, the wiring must be the
same as TPR1 and TPR2.
13
EM2
12
29
28
LSP
DOG
LSN
CN3
CN3
15
MBR
32
INP
16
ALM
23
7
LA
22
LAR
6
LB
21
LBR
5
LZ
LZR
24
LG
18
MO1
19
LG
2
MO2
DOCOM
14
CN5
LG
*2
TPR1
11
27
TPR2
DICOM
8
CN1A
CN1B
RA1
RA2
RA5
CN8
CN40A
CN40B
*1
MR Configurator2
*5
+
3
MR-J3USBCBL3M
Main circuit
power supply
*11
Forced stop 2
*3*4
Forward rotation stroke end
Electromagnetic brake interlock
Reverse rotation stroke end
In-position
*8
Proximity dog
*13
Malfunction
*7
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
Encoder Z-phase pulse
(differential line driver)
Control common
Analog monitor 1
Analog monitor 2
Short-circuit connector
*12
Personal computer
Network
Network
Touch probe1
Touch probe2
± 10 V DC
± 10 V DC
*10
*9*13
*13
Protection coordination
cable
Protection coordination
cable
Converter unit or
drive unit
(supplied with the drive unit)
Drive unit
24 V DC
*6
24 V DC
*6
10 m or less
2 m or less
10 m or less
USB cable
Содержание MR-J5D
Страница 1: ...MR J5D User s Manual Hardware MR J5D_ _G_ MR J5D_ _G_ _N1 Mitsubishi Electric AC Servo System ...
Страница 2: ......
Страница 189: ...10 USING A FULLY CLOSED LOOP SYSTEM 10 7 Absolute position detection system 187 10 MEMO ...
Страница 193: ......