10 USING A FULLY CLOSED LOOP SYSTEM
10.5 Basic functions
■
Position deviation error detection
Set [Pr. PE03.0 Fully closed loop control error - Detection function selection] to "2" (position deviation error detection) to
enable the position deviation error detection.
When the difference between the servo motor-side feedback position (2) and the load-side feedback position (4) is equal to or
more than the value of [Pr. PE07 Fully closed loop control - Position deviation error detection level] (1 kpulse to 20000
kpulses), [AL. 042.8 Servo control error based on position deviation] occurs, and the servo motor stops.
If the difference is equal to or more than the value of [Pr. PE07] at the command stop, [AL. 042.A Fully closed loop control
error based on position deviation during command stop] occurs.
When [Pr. PE03.1 Position deviation error - Detection method selection] is set to "1" (Detection only at stop), only [AL. 042.A]
is detected.
The initial value for [Pr. PE07] is 100 kpulses.
The setting unit for [Pr. PE07] can be changed with [Pr. PE10.1 Fully closed loop control - Position deviation error detection
level - Unit selection].
Change the setting value as necessary.
■
Detecting multiple deviation errors
Multiple deviation errors can be detected when [Pr. PE03.0 Fully closed loop control error - Detection function selection] is set
as follows. Refer to the following for the error detection method.
Page 181 Speed deviation error detection
Page 182 Position deviation error detection
• [Pr. PE03.0 Fully closed loop control error - Detection function selection]
Fully closed loop control error - Reset selection
Select the reset condition of fully closed loop control errors.
■
[Pr. PE03.3 Fully closed loop control error - Reset selection]
0: Reset disabled (reset by cycling the power or software reset)
1: Reset enabled
Servo parameter
Description
PE03.0
Fully closed loop control error - Detection function selection
2: Position deviation error detection
PE03.1
Position deviation error - Detection method selection
0: Continuous detection
1: Detection only at stop (An error is detected if the command is "0".)
2: Detection only at stop 2 (An error is detected during servo-off or if the command is "0" while in servo-on state.)
Servo parameter
Description
PE10.1
Fully closed loop control - Position deviation error detection level - Unit selection
0: 1 [kpulse] unit
1: 1 [pulse] unit
Setting value
Speed deviation error detection
Position deviation error detection
1
2
3