12. OPTIONS AND AUXILIARY EQUIPMENT
12.2.4 Relays
The following relays should be used with the interfaces:
Interface
Selection example
Relay used for digital input signals (interface DI-1)
To prevent defective contacts , use a relay for small signal
(twin contacts).
(Ex.) Omron : type G2A , MY
Relay used for digital output signals (interface DO-1)
Small relay with 12VDC or 24VDC of 40mA or less
(Ex.) Omron : type MY
12.2.5 Surge absorbers
A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.
Insulate the wiring as shown in the diagram.
Maximum rating
Permissible circuit
voltage
Surge
immunity
Energy
immunity
Rated
power
Maximum
limit voltage
Static
capacity
(reference
value)
Varistor voltage
rating (range) V1mA
AC[Vma]
DC[V]
[A]
[J]
[W]
[A]
[V]
[pF]
[V]
140
180
(Note)
500/time
5
0.4
25
360
300
220
(198 to 242)
Note. 1 time 8 20 s
13.5 (0.53)
16
.5
(0
.6
5)
Vinyl tube
Crimping terminal
for M4 screw
30.0 (
1.1
8
)
or
mo
re
3.
0
(0
.1
2)
or le
ss
0.8 (0.03)
4.7 1.0 (0.19 0.04)
(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon Chemi-con)
Outline drawing [mm] ( [in] ) (ERZ-C10DK221)
12.2.6 Noise reduction techniques
Noises are classified into external noises which enter MELSERVO-J2M to cause it to malfunction and
those radiated by MELSERVO-J2M to cause peripheral devices to malfunction. Since MELSERVO-J2M
is an electronic device which handles small signals, the following general noise reduction techniques are
required.
Also, the drive unit can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral devices malfunction due to noises produced by the drive unit, noise suppression measures
must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques
(a) General reduction techniques
Avoid laying power lines (input cables) and signal cables side by side or do not bundle them
together. Separate power lines from signal cables.
Use shielded, twisted pair cables for connection with the encoder and for control signal
transmission, and connect the shield to the SD terminal.
Ground the base unit, servo motor, etc. together at one point (refer to Section 3.8).
Содержание MELSERVO-J2M series
Страница 26: ...www dadehpardazan ir 88594014 15 1 10 1 FUNCTIONS AND CONFIGURATION MEMO ...
Страница 36: ...www dadehpardazan ir 88594014 15 2 10 2 INSTALLATION AND START UP MEMO ...
Страница 64: ...www dadehpardazan ir 88594014 15 3 28 3 SIGNALS AND WIRING MEMO ...
Страница 74: ...www dadehpardazan ir 88594014 15 4 10 4 OPERATION AND DISPLAY MEMO ...
Страница 112: ...www dadehpardazan ir 88594014 15 6 12 6 GENERAL GAIN ADJUSTMENT MEMO ...
Страница 122: ...www dadehpardazan ir 88594014 15 7 10 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 124: ...www dadehpardazan ir 88594014 15 8 2 8 INSPECTION MEMO ...
Страница 186: ...www dadehpardazan ir 88594014 15 12 36 12 OPTIONS AND AUXILIARY EQUIPMENT MEMO ...
Страница 190: ...www dadehpardazan ir 88594014 15 13 4 13 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...