9. TROUBLESHOOTING
9.2 Remedies for alarms
CAUTION
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
If an absolute position erase (A.25) occurred, always make home position setting
again. Otherwise, misoperation may occur.
As soon as an alarm occurs, make the Servo off status and interrupt the main
circuit power.
POINT
When any of the following alarms has occurred, always remove its cause
and allow about 30 minutes for cooling before resuming operation. If
operation is resumed by switching control circuit power off, then on to reset
the alarm, each unit and servo motor may become faulty. To protect the
main circuit elements, any of these servo alarms cannot be deactivated from
the servo system controller until the specified time elapses after its
occurrence. Judging the load changing condition until the alarm occurs, the
servo amplifier calculates this specified time automatically.
Regenerative error (A.30)
Overload 2 (A.51)
Overload 1 (A.50)
Multi axis overload (A.53)
The alarm can be deactivated by switching power off, then on or by the
error reset command CPU reset from the servo system controller. For
details, refer to Section 9.1.
When an alarm occurs, the dynamic brake is operated to stop the servomotor. At this time, the display
indicates the alarm No. The servo motor comes to a stop. Remove the cause of the alarm in accordance
with this section. The optional MR Configurator (servo configuration software) may be used to refer to the
cause.
@ in the Indication field denotes the slot number of the base unit and # the axis number of the drive unit.
Display
IFU
DRU
Name
Definition
Cause
Action
1. Power supply voltage is low.
2. There was an instantaneous control
circuit power failure of 30ms or
longer.
3. Shortage of power supply capacity
caused the power supply voltage to
drop at start, etc.
4. Power was restored after the bus
voltage had dropped to 200VDC.
(Main circuit power switched on
within 5s after it had switched off.)
Review the power supply.
5. Faulty parts in the base unit.
Checking method
Alarm (A.10) occurs if interface
unit is changed.
Change the base unit.
6. Faulty parts in interface unit.
Checking method
Alarm (A.10) occurs if base unit
is changed.
Change the interface unit.
FA.10
Undervoltage
Power supply voltage
fell to or below 160VAC.
7. CNP3 or CNP1B connector
unplugged.
Connect properly.
FA.12
Memory error 1 RAM, memory fault
FA.13
Clock error
Printed board fault.
FA.14
Watchdog
CPU/parts fault
Faulty parts in the interface unit.
Checking method
Alarm (any of A.11 and 13)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
Change the interface unit.
FA.15
Memory error 2 EEP-ROM fault
C hecking m ethod
Alarm (A.15) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
Change the interface unit.
Содержание MELSERVO-J2M series
Страница 26: ...www dadehpardazan ir 88594014 15 1 10 1 FUNCTIONS AND CONFIGURATION MEMO ...
Страница 36: ...www dadehpardazan ir 88594014 15 2 10 2 INSTALLATION AND START UP MEMO ...
Страница 64: ...www dadehpardazan ir 88594014 15 3 28 3 SIGNALS AND WIRING MEMO ...
Страница 74: ...www dadehpardazan ir 88594014 15 4 10 4 OPERATION AND DISPLAY MEMO ...
Страница 112: ...www dadehpardazan ir 88594014 15 6 12 6 GENERAL GAIN ADJUSTMENT MEMO ...
Страница 122: ...www dadehpardazan ir 88594014 15 7 10 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 124: ...www dadehpardazan ir 88594014 15 8 2 8 INSPECTION MEMO ...
Страница 186: ...www dadehpardazan ir 88594014 15 12 36 12 OPTIONS AND AUXILIARY EQUIPMENT MEMO ...
Страница 190: ...www dadehpardazan ir 88594014 15 13 4 13 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...