background image

164

APPX
Appendix 3  I/O Module

FX5-C32EYT/D

FX5-C32EYT/D-TS

FX5-C32ET/D

FX5-C32ET/DS-TS

FX5-C32EYT/DSS

FX5-C32EYT/DSS-TS

FX5-C32ET/DSS

FX5-C32ET/DSS-TS

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM1

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM1

Notch

Smaller 
numbers

Larger 
numbers

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17

COM0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM1

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17

COM1

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Input

X0
X1
X2
X3
X4
X5
X6
X7

COM

X0
X1
X2
X3
X4
X5
X6
X7

COM

Notch

Input

X0
X1
X2
X3
X4
X5
X6
X7

S/S

X10
X11
X12
X13
X14
X15
X16
X17

S/S

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17

COM0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V1

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V1

Notch

Smaller 
numbers

Larger 
numbers

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17
+V0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V1

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17
+V1

Input

X0
X1
X2
X3
X4
X5
X6
X7

COM0

X0
X1
X2
X3
X4
X5
X6
X7

COM0

Notch

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Input

X0
X1
X2
X3
X4
X5
X6
X7

S/S

X10
X11
X12
X13
X14
X15
X16
X17

S/S

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17
+V0

Содержание MELSEC iQ-F Series

Страница 1: ...MELSEC iQ F FX5UJ User s Manual Hardware ...

Страница 2: ......

Страница 3: ...tion in such a case Note that the output current of the 24 V DC service power supply varies depending on the model and the absence presence of extension modules If an overload occurs the voltage automatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machine operation in such a case Note that when an error...

Страница 4: ...the following conditions to reduce the risk of explosion This device is open type and is to be installed in an enclosed area under suitable environment which requires a tool or key to open Warning Explosion Hazard Substitution of any component may impair suitability for Class Division 2 Warning Explosion Hazard Do not disconnect equipment while the circuit is live or unless the area is known to be...

Страница 5: ...pleted make sure to remove the sheet to provide adequate ventilation Failure to do so may cause fire equipment failures or malfunctions Install the product on a flat surface If the mounting surface is rough undue force will be applied to the PC board thereby causing nonconformities Install the product securely using a DIN rail or mounting screws Connect the expansion board and expansion adapter se...

Страница 6: ...ly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the ends of stranded wi...

Страница 7: ... PLC due to the effects of noise Do not bundle the power line control line and communication cables together with or lay them close to the main circuit high voltage line load line or power line As a guideline lay the power line control line and communication cables at least 100 mm away from the main circuit high voltage line load line or power line Ground the shield of the shield wire or shielded ...

Страница 8: ...CAUTION Construct an interlock circuit in the program so that the whole system always operates on the safe side before executing the control for data change of the PLC in operation Read the manual thoroughly and ensure complete safety before executing other controls for program change parameter change forcible output and operation status change of the PLC in operation Otherwise the machine may be ...

Страница 9: ... verrouillage pour éviter d endommager l équipement aux niveaux supérieur et inférieur de limites de positionnement Notez que lorsque le module CPU détecte une erreur telle qu une erreur de minuteur de surveillance pendant l auto diagnostic toutes les sorties sont désactivées En outre lorsqu une erreur qui ne peut pas être détectée par le module CPU se produit dans un bloc de contrôle E S la comma...

Страница 10: ...tion de chacune des stations en cas de problème de communication voir les manuels correspondants pour le réseau Une sortie erronée ou un dysfonctionnement peut être à l origine d un accident Prendre les mesures appropriées pour maintenir la sécurité sur le système du contrôleur programmable en cas d accès non autorisé d un dispositif externe via le réseau Pour maintenir la sécurité en cas d accès ...

Страница 11: ... modules d extension Si une panne de courant de longue durée ou une chute de tension anormale se produit le contrôleur programmable s arrête et la sortie est désactivée Lorsque l alimentation est rétablie elle redémarre automatiquement lorsque le commutateur RUN STOP RESET est sur le côté RUN AVERTISSEMENT Assurez vous de couper toutes les phases de l alimentation externe avant d essayer l install...

Страница 12: ...ension et l adaptateur d extension de manière sécurisée à leurs connecteurs désignés Les connexions lâches peuvent provoquer des dysfonctionnements Assurez vous de fixer la carte d extension avec des vis de taraudage Pour le couple de serrage respecter les spécifications du manuel Si les vis sont serrées à l extérieur de la plage de couple spécifiée de mauvaises connexions peuvent provoquer des dy...

Страница 13: ...ent aux précautions suivantes Faute de quoi il y a risque d électrocution de panne d équipement de court circuit de rupture de fil de dysfonctionnements ou de dommages au produit La taille de l extrémité du câble lors de la mise au rebut doit suivre les dimensions décrites dans le manuel Le couple de serrage doit suivre les spécifications du manuel Tordre les extrémités des fils échoués et s assur...

Страница 14: ...t les câbles de communication ou ni les placer près du circuit principal la ligne à haute tension la ligne de charge ou la ligne d alimentation À titre indicatif posez la ligne d alimentation la ligne de commande et les câbles de communication au moins à 100 mm du circuit principal de la ligne à haute tension de la ligne de charge ou de la ligne d alimentation Effectuer la mise à la terre du blind...

Страница 15: ... de connecteur Ne pas utiliser de produit chimique pour le nettoyage Si le contact avec le contrôleur logique programmable dans le boîtier de commutation est possible lors de l entretien etc toujours éliminer l électricité statique pour éviter son influence En raison de risques de brûlures veuillez ne pas toucher la surface de l appareil à mains nues lorsqu il fonctionne dans un environnement dont...

Страница 16: ...ôleur programmable et contrôlez l absence de dégâts des pièces de montage etc Lorsque les fumigants contenant des matières halogènes comme le fluor le chlore le brome et l iode sont utilisés pour désinfecter et protéger les emballages en bois des insectes ils provoquent des dysfonctionnements lors de l entrée dans nos produits Prenez les précautions nécessaires pour vous assurer que les matériaux ...

Страница 17: ...cur if the product fails install appropriate backup or failsafe functions in the system Note If in doubt at any stage during the installation of the product always consult a professional electrical engineer who is qualified and trained in the local and national standards If in doubt about the operation or use please consult the nearest Mitsubishi Electric representative Since the examples indicate...

Страница 18: ...Specifications 33 2 7 Communication Specifications 35 Built in Ethernet communication 35 Built in USB communication 35 2 8 External Dimensions 36 CPU module 36 2 9 Terminal Layout 37 CHAPTER 3 PRODUCT LIST 39 3 1 Overall Configuration 39 3 2 CPU Module 40 3 3 Extension Module 41 I O module 41 Intelligent function module 44 Extension power supply module 45 Connector conversion module 45 3 4 Expansi...

Страница 19: ...enclosure 62 Layout in enclosure 63 5 2 Examination for Installation Method in Enclosure 64 5 3 Procedures for Installing on and Detaching from DIN Rail 65 Preparation for installation 65 Installation of CPU module 66 Installation of extension module extension cable type 66 Installation of terminal modules 67 Removal of CPU module 67 5 4 Procedures for Installing Directly with M4 Screws 68 Hole pi...

Страница 20: ... modules 110 6 7 Examples of Wiring for Various Uses 114 Positioning function 114 Communication function 114 High speed counter 115 Interruption 119 Digital switch 120 Input matrix 122 Seven segment with latch 123 CHAPTER 7 OPERATION ADJUSTMENT 125 7 1 Preparation for Operation 125 Preliminary inspection 125 Procedure until operation 126 Connection with a personal computer 127 7 2 Operation and Te...

Страница 21: ...ertification of UL cUL standards 142 Compliance with EC directive CE Marking 142 Appendix 3 I O Module 146 Product configuration 146 Product list 146 Specifications 148 External dimensions and component names 155 Terminal layout 162 Appendix 4 Connector Conversion Module 165 External dimensions and component names 165 Specifications 165 Appendix 5 SD Memory Card 166 Part names 166 Specifications 1...

Страница 22: ...ion MELSEC iQ F FX5 User s Manual PROFIBUS SH 081910ENG Describes the functions of the PROFIBUS DP master module MELSEC iQ F FX5 User s Manual Ethernet Communication JY997D56201 Describes the Ethernet communication function of the CPU module built in and the Ethernet module MELSEC iQ F FX5 ENET User s Manual SH 082026ENG Describes the functions of the Ethernet module MELSEC iQ F FX5 ENET IP User s...

Страница 23: ...nnector type Generic term for Input modules extension connector type Output modules extension connector type and Input output modules extension connector type I O module Generic term for Input modules Output modules Input output modules Powered input output modules and High speed pulse input output modules Input module Generic term for Input modules extension cable type and Input modules extension...

Страница 24: ... NZ1MEM 8GBSD and NZ1MEM 16GBSD SD memory cards Abbreviation of Secure Digital Memory Card Device that stores data using flash memory Peripheral device Generic term for engineering tools and GOTs GOT Generic term for Mitsubishi Electric Graphic Operation Terminal GOT1000 and GOT2000 series Software packages Engineering tool The product name of the software package for the MELSEC programmable contr...

Страница 25: ...LED Indicates whether the CPU module is powered or not Lit Powered Off Not powered or hardware error Page 132 Checking with LEDs ERR LED Indicates the error status of the CPU module Page 132 Checking with LEDs Lit Error or hardware error Flashing Factory default setting error hardware error or resetting Off Operating normally P RUN LED Indicates the program running status Lit Operating normally Fl...

Страница 26: ...ccess to the SD memory card when the card is to be removed 4 Built in USB communication connector Connector for connection with engineering tool 5 SD memory card slot Slot for inserting an SD memory card 6 Terminal names The signal names for power supply input and output terminals are shown shows a function grounding terminal 7 Expansion board connector Connector for connecting an expansion board ...

Страница 27: ...on adapter to the expansion adapter connector under the cover 2 Genuine product certification label Genuine product certification label to prevent counterfeiting 3 Nameplate The product model name Manufacturer s serial number power supply specifications and MAC address are shown 4 DIN rail mounting groove The module can be installed on DIN46277 rail 35 mm wide No Name Description 1 CPU module fixi...

Страница 28: ...the machinery within premises Category applies to equipment for which electrical power is supplied from fixed facilities The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V 9 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used Pollution level 2 is when only non conductive pollution occurs Temporary...

Страница 29: ...sistance Remarks Between power supply terminal AC power supply and ground terminal 1 5 kV AC for one minute 10 MΩ or higher by 500 V DC insulation resistance tester Between 24 V DC service power supply connected to input terminal 24 V DC and ground terminal 500 V AC for one minute Between output terminal relay and ground terminal 1 5 kV AC for one minute Between output terminal transistor and grou...

Страница 30: ...0 ms by editing the user program Power fuse 250 V 3 15 A Time lag fuse Rush current FX5UJ 24M 25 A max 5 ms or less 100 V AC 50 A max 5 ms or less 200 V AC FX5UJ 40M FX5UJ 60M 30 A max 5 ms or less 100 V AC 50 A max 5 ms or less 200 V AC Power consumption 1 FX5UJ 24M 30W FX5UJ 40M 32W FX5UJ 60M 35W 24 V DC service power supply capacity 2 FX5UJ 24M 400 mA Supply capacity when 24 V DC service power ...

Страница 31: ...lses of a response frequency of 50 to 100 kHz refer to Page 94 In the case of capturing high speed pulses X2 X5 X6 X7 10kHz Pulse waveform Waveform T1 pulse width T2 rise fall time X0 X1 X3 X4 5 μs or more 2 5 μs or less X2 X5 X6 X7 50 μs or more 25 μs or less Input response time H W filter delay X0 X1 X3 X4 ON 5 μs or less OFF 5 μs or less X2 X5 X6 X7 ON 30 μs or less OFF 50 μs or less X10 to X17...

Страница 32: ... using external power supply Item Specifications 24V N L 100 to 240 V AC Fuse X S S 0V Source input wiring 24V N L 100 to 240 V AC Fuse X S S 0V Sink input wiring Input impedance Input impedance Input impedance Input impedance 24V N L 100 to 240 V AC Fuse X S S 0V Source input wiring 24V N L 100 to 240 V AC Fuse X S S 0V Sink input wiring ...

Страница 33: ...liant item Max load 2 A point The total load current per common terminal should be the following value 3 output points common terminal 6 A or less 4 output points common terminal 8 A or less For details on the common refer to Page 37 Interpretation of terminal block layout Min load 5 V DC 2 mA reference values Open circuit leakage current Response time OFF ON Approx 10 ms ON OFF Approx 10 ms Outpu...

Страница 34: ...l 0 8 A or less For details on the common refer to Page 37 Interpretation of terminal block layout Open circuit leakage current 0 1 mA or less 30 V DC Voltage drop when ON Y0 to Y2 1 0 V or less Y3 and subsequent 1 5 V or less Response time Y0 to Y2 2 5 μs or less 10 mA or more 5 24 V DC Y3 and subsequent 0 2 ms or less 200 mA or more 24 V DC Output circuit insulation Photo coupler insulation Indi...

Страница 35: ...nterrupt 1 to 60000 ms can be set in 1 ms increments Timer performance specifications 100 ms 10 ms 1 ms No of program executions 32 No of FB files 16 Up to 15 for user Operation specifications Execution type Standby type initial execution type scan execution type event execution type Interrupt type Internal timer interrupt input interruption high speed comparison match interrupt interrupt by modul...

Страница 36: ... SW 16 1024 points No of system device points Special relay SM 10 10000 points Special register SD 10 12000 points Module access device Intelligent function module device 10 Depends on the intelligent function module No of index register points Index register Z 10 20 points Long index register LZ 10 2 points No of file register points File register R 10 32768 points Extended file register ER 10 32...

Страница 37: ... etc 6 A straight cable can be used If a personal computer or GOT and CPU module are directly connected a cross cable can be used Built in USB communication Item Specifications Data transmission speed 100 10 Mbps Communication mode Full duplex FDX Half duplex HDX 1 Interface RJ45 connector Transmission method Base band Maximum segment length The distance between hub and node 100 m Cascade connecti...

Страница 38: ... Mass weight FX5UJ 24M 95 mm 76 mm Approx 0 55 kg FX5UJ 40M 130 mm 111 mm Approx 0 65 kg FX5UJ 60M 175 mm 156 mm Approx 0 80 kg Exterior color Main body Munsell 0 6B7 6 0 2 Accessories Dust proof protection sheet Manual supplied with product W1 15 82 mounting hole pitch 90 W 83 8 2 φ4 5 mounting holes Unit mm ...

Страница 39: ...ected to common COM One common terminal covers 3 or 4 output points The output number Y connected to common is the range inside the thick separation line For transistor output source type the COM terminal is the V terminal 8 1 Pin 1 2 3 4 5 6 7 8 Signal name TXD TXD RXD Not used Not used RXD Not used Not used 3 S S 1 2 X0 N L 4 5 6 7 X10 11 12 13 14 15 FX5UJ 24MR ES Y3 Y0 2 1 COM1 COM0 0V 24V 4 5 ...

Страница 40: ...COM1 6 5 Y10 COM2 12 11 Y14 COM3 16 15 17 17 7 13 FX5UJ 40MR ES FX5UJ 40MT ES FX5UJ 60MT ESS 3 S S 1 2 X0 N L 4 5 6 7 X10 11 12 13 14 15 16 17 X20 21 31 23 27 25 X30 26 22 24 32 33 34 35 36 X40 41 37 42 43 Y0 2 1 3 COM0 0V 24V COM1 Y4 5 Y6 COM2 Y10 12 11 COM3 Y14 16 15 7 13 22 Y20 COM4 21 17 23 COM5 Y24 26 25 27 Y0 2 1 3 V0 0V 24V V1 Y4 5 6 V2 Y10 12 11 V3 Y14 16 15 7 13 22 Y20 V4 21 17 23 V5 Y24 ...

Страница 41: ...4MR ES FX5UJ 24MT ES FX5UJ 24MT ESS FX5UJ 40MR ES FX5UJ 40MT ES FX5UJ 40MT ESS FX5UJ 60MR ES FX5UJ 60MT ES FX5UJ 60MT ESS Input output Expansion boards Analog FX5 4AD FX5 4DA FX5 8AD FX5 4LC Simple motion FX5 40SSC S FX5 80SSC S FX5 ENET FX5 ENET IP FX5 CCLIEF FX5 CCL MS FX5 ASL M FX5 DP M FX5 20PG P FX5 20PG D Positioning Intelligent function module Remote I O FX5 CNV IF Connector conversion modu...

Страница 42: ...nts 24 V DC service power supply FX5UJ 24MR ES 24 points 32 points 1 14 points 16 points 1 10 points 16 points 1 24 V DC sink source Relay Screw terminal block 400 mA 460 mA 2 FX5UJ 24MT ES Transistor sink FX5UJ 24MT ESS Transistor source FX5UJ 40MR ES 40 points 24 points 16 points 24 V DC sink source Relay Screw terminal block 400mA 500 mA 2 FX5UJ 40MT ES Transistor sink FX5UJ 40MT ESS Transistor...

Страница 43: ...ransistor source output YT D TS Transistor sink output YT DSS TS Transistor source output YR D TS Relay output Input output module R ES 24 V DC sink source input relay output T ES 24 V DC sink source input transistor sink output T ESS 24 V DC sink source input transistor source output T D 24 V DC sink input transistor sink output T DSS TS 24 V DC sink source input transistor source output T DS TS ...

Страница 44: ...el No of input output points Input type Output type Input output connection type Current consumption Total No of points No of input points No of output points 5 V DC power supply 24 V DC power supply FX5 C16EX D 16 points 16 points 24 V DC sink Connector 100 mA 65 mA 0 mA 1 FX5 C16EX DS 24 V DC sink source FX5 C32EX D 32 points 32 points 24 V DC sink Connector 120 mA 130 mA 0 mA 1 FX5 C32EX DS 24 ...

Страница 45: ...20 mA 200 mA FX5 C32EYT DSS Transistor source FX5 C32EYT D TS Transistor sink Spring clamp terminal block FX5 C32EYT DSS TS Transistor source Model No of input output points Input type Output type Input output connection type Current consumption Total No of points No of input points No of output points 5 V DC power supply 24 V DC power supply FX5 16ER ES 16 points 8 points 8 points 24 V DC sink so...

Страница 46: ...ut output points Current consumption 5 V DC power supply 24 V DC power supply External 24 V DC power supply FX5 4AD 4 ch voltage input current input 8 points 100 mA 40 mA FX5 4DA 4 ch voltage output current output 8 points 100 mA 150 mA FX5 8AD 8 ch voltage input current input thermocouple input resistance thermometer input 8 points 40 mA 100 mA FX5 4LC 4 ch temperature control thermocouple resist...

Страница 47: ...module extension connector type with FX5UJ systems Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply External 24 V DC power supply FX5 ENET Ethernet communication 8 points 110 mA FX5 ENET IP Ethernet communication compatible with EtherNet IP 8 points 110 mA FX5 CCLIEF Intelligent device station for CC Link IE Field network 8 points 10 mA...

Страница 48: ...on destination is a module of extension cable type except for FX5 1PSU 5V or extension power supply module always use the connector conversion adapter FX5 CNV BC Connector conversion adapter Adapter for connecting extended extension cable and module of extension cable type except for FX5 1PSU 5V or extension power supply module Model Function No of occupied input output points Current consumption ...

Страница 49: ... power supply FX 16E TB Directly connected to the I O connector of a PLC 112 mA FX 32E TB 112 mA 16 points FX 16EX A1 TB 100 V AC input type 48 mA FX 16EYR TB Relay output type 80 mA FX 16EYT TB Transistor output type sink output 112 mA FX 16EYS TB Triac output type 112 mA FX 16E TB UL Directly connected to the I O connector of a PLC 112 mA FX 32E TB UL 112 mA 16 points FX 16EYR ES TB UL Relay out...

Страница 50: ...nsion power supply module Range of devices powered by CPU module Y0 to Y17 Y20 to Y37 FX5 16EYR ES Configuration of whole system Expansion board and expansion adapters X30 to X47 FX5 16EX ES Analog module Extension power supply module Intelligent module I O module FX5 CNV IF Connector conversion module Extension module X50 to X67 Y40 to Y57 FX5 32ER ES FX5 C16EX D Extension module X70 to X107 FX5 ...

Страница 51: ...he Number of Input Output Points Current consumption Power of extension devices is supplied from the CPU module powered input output module or extension power supply module The number of extension devices that can be connected must be determined from the capacity of the power supply For details on the current consumption refer to Page 56 Limitation on Current Consumption 1 Power is supplied to inp...

Страница 52: ...ion destination is a module of extension cable type except for FX5 1PSU 5V or extension power supply module Model Limitations FX5 ENET Only one module may be connected per system FX5 ENET IP Only one module may be connected per system FX5 CCLIEF Only one module may be connected per system FX5 CCL MS One module can be connected to the system for each station type Master station 1 Intelligent device...

Страница 53: ...number of connections between the communication board and the communication adapter is exceeded all serial communication in use stops Type Limitations Communication adapter Up to 2 modules can be connected When connecting the expansion board to the CPU module only 1 module can be connected Analog adapter Up to 2 modules can be connected Expansion board FX5 232ADP FX5 485ADP Communication adapter U...

Страница 54: ...ent because external power supply of the extension module is supplied from the 24 V DC service power of the CPU module etc the extension module cannot be connected When connecting FX5 EX ES to the above figures 1 and 2 and the 24 V DC service power supply is used for the input circuit of FX5 EX ES they do not consume the 24 V DC service power supply Type Limitations Extension module Up to 8 module...

Страница 55: ...dule a total of 256 points or less including the number of input output points of extension devices and number of remote I O points can be controlled The total number of I O points and remote I O points must not exceed 256 points 1 Number of input output points including input output occupied points Up to 256 points CPU module I O module Expansion board Expansion adapter CC Link master AnyWireASLI...

Страница 56: ...s For details on the number of input output points by model refer to the following Page 40 CPU Module Page 41 I O module Number of occupied input output points of intelligent function modules Count the number of occupied input output points of intelligent function modules The number of occupied input output points per module is 8 For details on the number of occupied input output points by model r...

Страница 57: ...emote device station and the intelligent device station is 8 regardless of the number of remote I O points For details refer to the following manual MELSEC iQ F FX5 User s Manual CC Link AnyWireASLINK remote I O The number of input output points set by using the engineering tool parameters is assigned to the remote I O to be used with AnyWireASLINK For details refer to the following manual MELSEC ...

Страница 58: ... 1 Value when 24 V DC service power supply is used for input circuits The power supply capacity differs when external power supply is used for input circuit 2 Check the extension modules which requires current consumption calculation Page 41 I O module Page 44 Intelligent function module Type Model Type Model Power supply capacity 24 V DC service power supply CPU module FX5UJ 40MT ES 400 mA 1 Type...

Страница 59: ... output module 1 Value when 24 V DC service power supply is used for input circuits The power supply capacity differs when external power supply is used for input circuit 2 Check the current consumption of the extension module Page 41 I O module Page 44 Intelligent function module Power supply type Total current consumption 24 V DC power supply 200 mA Type Model Power supply capacity 5 V DC power ...

Страница 60: ... result is a negative value the current consumption exceeds the power supply capacity of the CPU module Reconfigure the system adding powered input output module Power supply type Total current consumption 5 V DC power supply 400 mA 24 V DC power supply 210 mA Ex 0 mA Ex Total of current consumed by extension module Current consumption mA 400 mA Powered input output module Capacity of 5 V DC power...

Страница 61: ...extension module Page 41 I O module Page 44 Intelligent function module 1 24 V DC power supply is supplied from the CPU module or powered input output module Type Model Power supply capacity 5 V DC power supply 24 V DC service power supply Extension power supply module FX5 1PSU 5V 1200 mA 300 mA Type Model Power supply capacity 5 V DC power supply 24 V DC service power supply Input module FX5 16EX...

Страница 62: ... the system adding powered input output module or extension power supply modules Power supply type Total current consumption 5 V DC power supply 400 mA 24 V DC power supply 125 mA Power supply from CPU module or powered input output module CPU module Powered input output module Intelligent module Extension power supply module When the CPU module or powered input output module supplies the 24 V DC ...

Страница 63: ... device are assigned The last digit of the assigned numbers must begin with 0 Module number of extension modules The CPU module automatically assigns numbers 1 to 8 to intelligent function modules as module numbers in order of distance from the CPU module Intelligent function modules connected to the CPU module Module numbers are assigned to intelligent function modules in order of distance from t...

Страница 64: ...in the following figure Spaces in enclosure Extension devices can be connected on the left and right sides of the CPU module of the PLC Keep a space of at least 50 mm between the module main body and other devices and structure Also separate the PLC from high voltage lines high voltage devices and power devices when possible Failure to do so may cause fire equipment failures or malfunctions If you...

Страница 65: ...owered input output module Extended extension cable Another equipment Another equipment A A A A A A A A FX5 20PG P FX5 30EC FX5 65EC FX5UJ CPU module FX5 16EX ES FX5 16EYT ES FX5 16EYT ES FX5 16EYT ES FX5 232ADP 50mm FX5 CNV BC FX5 4AD Extension module A 50 mm A A FX5UJ CPU module Intelligent function module For product dimensions or manual for various products refer to App 3 I O Module Expansion ...

Страница 66: ...For details on the procedures for installing on and detaching from DIN rail refer to Page 65 Procedures for Installing on and Detaching from DIN Rail Example of installation 1 FX5 CNV BC can only be installed directly Installing directly The PLC can be installed directly in the enclosure with M4 screws For mounting hole pitch refer to Page 68 Hole pitches for direct mounting Example of installatio...

Страница 67: ...d on a DIN46277 rail 35 mm wide Preparation for installation Connecting extension devices Some extension devices must be mounted on the CPU module before the module is installed in the enclosure Connect expansion adapters to the CPU module before mounting the PLC in the enclosure Mount extension modules extension cable type and terminal module in the enclosure after mounting the CPU module in the ...

Страница 68: ...o the DIN rail 3 Lock the DIN rail mounting hooks C in the following figure while pressing the PLC against the DIN rail Installation of extension module extension cable type 1 Push out the DIN rail mounting hook A in the right figure of the extension module 2 Fit the upper edge of the DIN rail mounting groove B in the right figure onto the DIN rail 3 Push the product against the DIN rail 4 Lock th...

Страница 69: ...s For the mounting procedure of the terminal block refer to Page 79 Removal and installation of removable terminal block 2 Disconnect the extension cables and the connecting cables When removing the extension cable pull the pullout tab of the extension cable straight up 3 Insert the tip of a flathead screwdriver into the hole of the DIN rail mounting hook B in the right figure This step also appli...

Страница 70: ...ing The product mounting hole pitches are shown below For pitch that varies depending on the product refer to the table CPU module Expansion adapter Dimensions Model name Mounting hole pitch W Unit mm FX5UJ 24MR ES FX5UJ 24MT ES FX5UJ 24MT ESS 76 FX5UJ 40MR ES FX5UJ 40MT ES FX5UJ 40MT ESS 111 FX5UJ 60MR ES FX5UJ 60MT ES FX5UJ 60MT ESS 156 Dimensions Model name Mounting hole pitch W Unit mm FX5 232...

Страница 71: ...gap between products is 2 mm Dimensions Model name Mounting hole pitch W Unit mm FX5 8EX ES FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS FX5 16ER ES FX5 16ET ES FX5 16ET ESS Refer to the figure shown to the left FX5 32ER ES FX5 32ET ES FX5 32ET ESS 140 Dimensions Model name Mounting hole pitch W Unit mm FX5 1PSU 5V 34 C 20 20 80 90 W D 5 5 80 90 16 W 80 ...

Страница 72: ...to the external dimensions diagram 2 Fit the CPU module A in the right figure to holes and secure it with M4 screws B in the right figure 1 Make mounting holes on the mounting surface according to the external dimensions diagram 2 Push in the DIN rail mounting hook A in the right figure of the extension module extension cable type If the DIN rail mounting hook is not pushed in the screw hole is co...

Страница 73: ...tion explains how to connect the expansion board to the CPU module 1 Remove the expansion board connector cover from the front face of the CPU module 2 Connect the expansion board to the expansion board connector A in the right figure 3 Fix the expansion board C in the right figure with provided M3 tapping screws B in the right figure to the CPU module Tightening torque 0 3 to 0 6N m Connection me...

Страница 74: ...odule B in the right figure 3 Connect the expansion adapter to the CPU module as shown in the right figure 4 Slide the hook for coupling the expansion adapter of the CPU module B in the right figure to fix the expansion adapter C in the right figure 1 Remove the extension connector cover A in the right figure on the right side of the surface of the CPU module or powered input output module 2 Conne...

Страница 75: ...ht figure of the existing module left side A in the right figure 2 Connect the extension cable C in the right figure of the module to be connected right side to the existing module left side A in the right figure 3 Fit the top cover B in the right figure 4 Pull out the pullout tab D in the right figure of the extension cable on the right side of the cover 1 Separate the case of FX5 CNV BC into two...

Страница 76: ...on connector type 1 Slide the hook for coupling the extension module A in the right figure of the existing module left side 2 Remove the subsequent extension connector cover B in the right figure 3 Connect an extension module as shown in the right figure 4 Slide the hook for coupling the extension module A in the right figure of the existing module to fix the extension module C in the right figure...

Страница 77: ...ly Remove the resin cover only when crossover wiring to a subsequent module is performed FX5 C EX DS TS and FX5 C32ET DS do not have power connectors and the power is supplied from using input connectors or input terminal blocks Thus removing the resin cover is not required Precautions To perform crossover wiring supply the power from the preceding module to the subsequent module The power cannot ...

Страница 78: ...ion of the arrow Precautions If the power cable is removed by force the cable may break Connection of I O cables I O connectors Cable connection to I O connectors I O connectors conform to MIL C 83503 For I O cables refer to Page 77 Preparation of I O connectors and prepare them I O modules extension connector type Push here with fingers a Example FX5 C32EX D Notch Input X Input X Example FX5 C32E...

Страница 79: ...of the terminal module and I O connectors For the connection with the terminal module refer to Page 78 WIRING Flat cables with tube On both ends 20 pin connectors are attached FX 16E 300CAB 3 m FX 16E 500CAB 5 m FX 16E 150CAB R 1 5 m Round multicore cables On both ends 20 pin connectors are attached FX 16E 300CAB R 3 m FX 16E 500CAB R 5 m Model and configuration of I O connectors Suitable wiring U...

Страница 80: ...e grounded wire to the terminal Page 85 Grounding 4 Wire the input X terminal Select sink or source in the following wiring For sink input connect 24V S S terminal For source input connect 0V S S terminal Connect sensors and switches to the terminals Page 90 Input Wiring 5 Wire the output Y terminal Connect the load to terminals Page 99 Output Wiring 6 Wire the Ethernet communication connectors ME...

Страница 81: ...e that there is no gap between the terminal block and mount position 6 2 Cable Connecting Procedure The cable connecting procedure is explained below Screw terminal block Wire the screw terminal block in accordance with the following specifications For information concerning screw terminal blocks for intelligent function modules refer to User s manual for each intelligent function module Terminal ...

Страница 82: ...nce with LVD directive M3 5 terminal screw When a single wire is connected to a single terminal When two wires are connected to a single terminal Terminal manufacturer Type No Applicable cable Certification Pressure bonding tool JST Mfg Co Ltd FV1 25 B3A AWG22 to 16 UL Listed YA 1 JST Mfg Co Ltd FV2 MS3 AWG16 to 14 Terminal manufacturer Type No Applicable cable Certification Pressure bonding tool ...

Страница 83: ...e used Depending on the thickness of a wiring sheath used it may be difficult to insert the sheath into an insulation sleeve Refer to the external dimensions as a reference to select wires Reference No of wire per terminal Wire size Tightening torque Single wire Strand wire Ferrule with insulation sleeve Expansion board communication adapter One wire 0 3 to 0 5 mm2 AWG22 to 20 0 3 to 0 5 mm2 AWG22...

Страница 84: ...table shows wire ferrules and tools you can remove this part compatible with the terminal block Use of items that are not listed in the following table may result in wire ferrule getting stuck to the terminals Before use carefully confirm that the wire ferrule can be removed Reference product For tightening terminals use a small commercially available screwdriver with a straight tip The recommende...

Страница 85: ...ove of the lever push up the flathead screwdriver rotate the lever to the release position and the terminal block can be removed from the module easily After inserting the terminal block check that the lever is at the lock position Precautions When installing the terminal block check that the lever is in the release position If installation is performed while the lever is in the lock position it m...

Страница 86: ...bar solderless terminal while pushing the open close button with a flathead screwdriver having a tip width of 2 0 to 2 5 mm After fully inserting the cable or bar solderless terminal remove the screwdriver Reference Precautions Pull the cable or bar solderless terminal slightly to check that the cable is securely clamped When wiring with the thick electric wire make sure to prevent the conductive ...

Страница 87: ...cation adapters Use a grounding wire with thickness of AWG 14 2 mm2 or thicker Bring the grounding point close to the PLC as much as possible so that the ground cable can be shortened PLC PLC PLC Other equipment Other equipment Other equipment Independent grounding Best condition Shared grounding Good condition Common grounding Not allowed PLC Intelligent module Independent grounding class D groun...

Страница 88: ...he CPU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time 4 Do not connect the 24V terminals 24 V DC service power supply of the CPU module and the powered input output module with each other Connect the 0V terminal AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5UJ 40MT ES FX5 8EX...

Страница 89: ...urning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time 4 Do not connect the 24V terminals 24 V DC service power supply of the CPU module and the powered input output module with each other Connect the 0V terminal AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5UJ 40MT ES FX5 8EX ES S S Class D grou...

Страница 90: ...PU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time X S S AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5UJ 40MT ES FX5 8EX ES S S Class D grounding grounding resistance 100 or less DC AC 1 2 Breaker 3 FX5 20PG P L N 1 3 FX5 1PSU 5V FX5 8AD FX5 8EX ES FX5 8EYT ES Wiring precauti...

Страница 91: ... CPU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5UJ 40MT ES FX5 8EX ES S S Class D grounding grounding resistance 100 or less DC AC 1 2 Breaker 3 FX5 20PG P L N S S 1 3 FX5 1PSU 5V FX5 8AD FX5 8EX ES FX5 8EYT ES Wiring precauti...

Страница 92: ...ype to sink or source input wire the S S terminal to the 0V or 24V terminal Sink input Connect the 24V terminal and S S terminal Page 95 Sink input Source input Connect the 0V terminal and S S terminal Page 96 Source input All inputs X of the CPU module can be set to either sink input or source input by selection Sink input common Source input common Sink input means a DC input signal with current...

Страница 93: ...nal and the circuit is closed the input X turns on At this time the LED corresponding to the DISP switch lights up FX5 C16EX D does not have the DISP switch In the sink input the input X is turned on by connecting 24 V DC with the COM terminal or S S terminal and connecting a no voltage contact or NPN open collector transistor output between the input terminal and 24 V DC to close the circuit At t...

Страница 94: ...ent malfunctions caused by chattering of the input contact and noise from the input line Input has a response delay switching from ON to OFF and OFF to ON shown in the following table Item Specifications Input response time H W filter delay CPU module X0 X1 X3 X4 ON 5 μs or less OFF 5 μs or less X2 X5 X6 X7 ON 30 μs or less OFF 50 μs or less X10 to X17 ON 50 μs or less OFF 150 μs or less Input mod...

Страница 95: ...sistance is less than the above parallel resistance Rp kΩ connect a bleeder resistance Rb kΩ obtained by the following formula as shown in the following figure Item Specifications Voltage drop CPU module X0 X1 X3 X4 3 9 V X2 X5 X6 X7 4 1 V X10 and subsequent 2 4 V Input module Input output modules Powered input output module Item Specifications Parallel resistance Rp kΩ CPU module X0 X1 X3 X4 14 X...

Страница 96: ...e wiring length should be 5 m or less Use shielded twisted pair cables for connecting cables Ground the shield of each shielded cable only on the CPU module side Connect a 1 5 kΩ 1 W or more bleeder resistance to the input terminal so that the sum of the load current of the open collector transistor output on the mating device and the input current of the CPU module is 20 mA or more The above ment...

Страница 97: ...dule The 24 V DC service power supply or external power supply can be used for all inputs X of the CPU module However you need to select either one for each CPU module or I O module Both power supplies cannot be used together in the same module X0 S S 0V 24V FX5UJ 40MT ES N L X1 X0 S S X1 FX5 16EX ES 5V 0V 24V Input terminal X0 S S X1 FX5 16EX ES 5V 0V 24V 5V 0V 24V Fuse 24 V DC Class D grounding ...

Страница 98: ...4 V DC service power supply or external power supply can be used for all inputs X of the CPU module However you need to select either one for each CPU module or I O module Both power supplies cannot be used together in the same module X0 S S 0V 24V FX5UJ 40MT ESS N L X1 X0 S S X1 FX5 16EX ES 5V 0V 24V Input terminal X0 S S X1 FX5 16EX ES 5V 0V 24V 5V 0V 24V Fuse 1 2 Three wire sensor Three wire se...

Страница 99: ...the one of the connected connector 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM Input number of PLC 3 wire sensor NPN Vacant terminal 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers COM0...

Страница 100: ...6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM0 1 3 wire sensor PNP Input number of PLC Vacant terminal 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 to 3 0 to 3 4 to 7 4 to 7 24 V DC 10 15 Fuse Fuse PLC input No Photocoupler power supply 100 V to 120 V AC ...

Страница 101: ...roximate life of a relay based on the results of an operation life test Test condition 1 sec ON 1 sec OFF The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut down Please refer to the following measures regarding the inductive load Page 101 Contact protection circuit for inductive loads Some types of inductive loads generate ru...

Страница 102: ...t comply with CE UL cUL standards for loads Insulation of circuit The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and contact The common terminal blocks are separated from one another Display of operation When power is applied to the output relay coil the LED is lit and the output contact is turned on Response time The response time of t...

Страница 103: ...for commutation must comply with the following specifications AC circuit Connect a surge absorber CR composite parts like surge killer spark killer etc parallel to the load Select a surge absorber with voltage rating that is suitable for the output used Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external inte...

Страница 104: ...e extension cable type and powered input output module the transistor output type is a 3 point or 4 point common output type Sink output common Source output common Output to make load current flow into the output Y terminal is called sink output Output to make load current flow out of the output Y terminal is called source output Sink output Source output Connect each COM number terminal to the m...

Страница 105: ...r off differs depending on the output terminal used For specifications of each module refer to the following For output specifications of the CPU module refer to Page 31 Output Specifications For output specifications of the I O modules refer to Page 152 Output specifications For output specifications of the terminal modules refer to Page 170 Output specifications The transistor OFF time is longer...

Страница 106: ...ger than the load current Contact protection circuit for inductive loads When an inductive load is connected connect a diode for commutation in parallel with the load as necessary The diode for commutation must comply with the following specifications Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external interl...

Страница 107: ...rrent Current of 0 3 A can flow per one output point However current of four output points should be 0 8 A average of 0 2 A per one point to suppress temperature rise When a load with a high rush current is frequently turned on or off the mean square current should be 0 2 A or less Open circuit leakage current C R absorbers are connected in parallel at the triac output terminal for turning off the...

Страница 108: ...w In phase PLC output contacts 1 should be used in an in phase manner C R absorbers are connected in parallel at the triac output circuit for turning off the triac When a minute current load of 0 4 VA or less 100 V AC or 1 6 VA or less 200 V AC is connected a surge absorber must be connected in parallel with the load Select a surge absorber with the rated voltage that is suitable for the output us...

Страница 109: ... breakdown due to load short circuiting 2 represents vacant terminals Y0 COM0 Y7 Y0 COM1 Y7 AC power supply 100 to 240 V PL Power ON MC MC MC MC Load Load Fuse 1 Fuse 1 Fuse 1 Fuse 1 Fuse 1 Breaker Y0 COM0 Y14 COM3 Y4 COM1 2 Emergency stop Power supply for loads connected to PLC output terminals As for emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field DC power supply CPU ...

Страница 110: ...e to load short circuiting 2 represents vacant terminals Y0 COM0 Y7 Y0 COM1 Y7 Load PL Power ON MC MC MC MC DC power supply Load Fuse 1 Fuse 1 Load Load Fuse 1 Fuse 1 AC power supply 100 to 240 V Breaker Y0 COM0 Y14 COM3 Y4 COM1 2 Emergency stop Power supply for loads connected to PLC output terminals As for emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field CPU module Tra...

Страница 111: ...to load short circuiting 2 represents vacant terminals Y0 V0 Y7 Y0 V1 Y7 PL Power ON Emergency stop MC MC MC MC DC power supply Load Load Fuse Fuse AC power supply 100 to 240 V Breaker Load Load Fuse 1 Fuse 1 Y0 V0 Y14 V3 Y4 V1 2 Power supply for loads connected to PLC output terminals As for emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field CPU module Transistor output s...

Страница 112: ... this number with the one of the connected connector 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 COM0 24 V DC MC1 MC2 COM COM COM COM COM COM COM COM 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse Fuse Fuse 1 Output number of PLC 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 V0 24 V DC MC1 MC2 COM COM COM COM COM COM COM COM ...

Страница 113: ...output contacts FX 16EYT TB Connectable models FX5 C EYT D FX5 C32ET D For external wiring precautions refer to Page 101 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse 0 to 7 Smaller numbers 0 to 7 Larger numbers PLC output No Relay power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 C...

Страница 114: ...5 C32ET DSS For external wiring precautions refer to Page 101 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output No Photocoup...

Страница 115: ...cautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorbers are connected to each output Fuse Fuse Fuse Load Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorbers are conne...

Страница 116: ...amples of programming instructions are given based on the allocation of the input output numbers for wiring For the instructions refer to MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks Positioning function For wiring examples for the positioning function refer to MELSEC iQ F FX5 User s Manual Positioning Control CPU module built in High speed pulse input output ...

Страница 117: ...ollowing figures as references for wiring The settings of the high speed counters are set by using the parameter settings of the engineering tool For details refer to MELSEC iQ F FX5 User s Manual Application Example of wiring 1 The grounding resistance should be 100 Ω or less CH to be used Pulse input mode External preset input External enable input Operation mode CH1 CPU module 1 phase 1 input S...

Страница 118: ...case of sink wiring S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 24 V DC 0V X0 Aphase B phase Z phase NPN open collector transistor output rotary encoder FX5UJ 40MT ES 1 5 k In the case of source wiring S S L N 24V 0V 24V Rotary encoder 24 V DC 0V X0 Aphase B phase Z phase FX5UJ 40MT ESS Class D grounding 1 Fuse PNP open collector transistor output rotary encoder ...

Страница 119: ...ation Example of wiring 1 The grounding resistance should be 100 Ω or less CH to be used Pulse input mode External preset input External enable input Operation mode CH4 CPU module 2 phase 2 input Invalid Invalid Normal mode 1 5 k 24 V DC In the case of sink wiring FX5UJ 40MT ES S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 0V X3 X4 Aphase B phase Z phase NPN open collector transistor ...

Страница 120: ...e of sink wiring FX5UJ 40MT ES S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 24 V DC 0V X3 X4 Aphase B phase Z phase NPN open collector transistor output rotary encoder 1 5 k In the case of source wiring FX5UJ 40MT ESS S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 24 V DC 0V X3 X4 Aphase B phase Z phase PNP open collector transistor output rotary encoder ...

Страница 121: ... measurement function refer to MELSEC iQ F FX5 User s Manual Application Example of wiring When 24 V DC service power supply is used When 24 V DC external power supply is used 1 The grounding resistance should be 100 Ω or less 1 5 k In the case of sink wiring S S L N 24V Class D grounding 1 Fuse FX5UJ 40MT ES 0V X0 3 wire type 1 5 k In the case of source wiring FX5UJ 40MT ESS S S L N 24V Class D g...

Страница 122: ...example is the wiring for the input output of the FX5UJ 40MT ES Source wiring The example is the wiring for the input output of the FX5UJ 40MT ESS DSW SM400 X10 Y10 D100 K1 X10 X11 X12 X13 X15 X14 X16 X17 COM2 Y10 Y11 Y12 Y13 Sink input FX5UJ 40MT ES 1 2 4 8 103 102 101 100 103 102 101 100 0 1A 50V diode is necessary Digital switch of BCD Transistor output sink 0V 24V S S X10 X11 X12 X13 X15 X14 X...

Страница 123: ...nual Instructions Standard Functions Function Blocks Example of program Example of wiring Sink wiring The example is the wiring for the input output of the FX5UJ 40MT ES Source wiring The example is the wiring for the input output of the FX5UJ 40MT ESS BIN SM400 K2X10 D102 X10 X11 X12 X13 X15 X14 X16 X17 1 2 4 8 1 2 4 8 101 100 FX5UJ 40MT ES Sink input 0V 24V S S X10 X11 X12 X13 X15 X14 X16 X17 1 ...

Страница 124: ... X12 X13 X14 X15 X16 X17 Y10 Y11 Y12 Y13 M30 M31 M32 M33 M34 M35 M36 M37 M40 M41 M42 M43 M44 M45 M46 M47 M50 M51 M52 M53 M54 M55 M56 M57 0 1A 50V diode is necessary Transistor output sink X11 X13 X15 X17 X12 X14 X16 X11 X13 X15 X17 X12 X14 X16 Sink input FX5UJ 40MT ES To use X0 to X17 of the input connect a pull up resistor 3 3 k 0 5 W 0V 24V S S X10 V2 X11 X12 X13 X14 X15 X16 X17 Y10 Y11 Y12 Y13 ...

Страница 125: ...e wiring for the input output of the FX5UJ 40MT ESS 1 Use a 7 segment display with a latch and a built in BCD decoder SEGL SM400 D100 Y10 K1 103 102 101 100 1 2 4 8 103 102 101 100 1 2 4 Y10 Y11 Y12 Y13 Y14 COM3 Y15 Y16 Y17 8 Transistor output sink 1 COM2 FX5UJ 40MT ES Signal Internal circuit Seven Segment with Latch Y COM1 PLC 7 segment display to be used for sink wiring in the case of transistor...

Страница 126: ...nput output of the FX5UJ 40MT ESS BCD SM400 D100 K2Y10 Y10 Y11 Y12 Y13 Y14 COM3 Y15 Y16 Y17 1 2 4 8 1 2 4 8 8 4 2 1 8 4 2 1 Signal Internal circuit Seven Segment with Latch Y COM1 PLC 7 segment display to be used for sink wiring in the case of transistor output COM2 FX5UJ 40MT ES Transistor output sink Fuse FX5UJ 40MT ESS Transistor output source Signal Internal circuit Seven Segment with Latch Y ...

Страница 127: ...resistance test of the PLC should be measured in accordance with the following procedure 1 Remove all input output wires and power supply wires from the PLC 2 Connect a crossing wire to each of the PLC terminals power supply terminal input terminals and output terminals except the ground terminal For the dielectric withstand voltage test of each terminal refer to the generic specifications for the...

Страница 128: ...t in memory using the engineering tool GX Works3 Operating Manual 4 Parameter setting Set the parameters needed for startup GX Works3 Operating Manual System parameters CPU parameters Unit parameters 5 Programming Create a program using the engineering tool MELSEC iQ F FX5 User s Manual Application 6 Write the parameters and the program Write the parameters and the program set with the engineering...

Страница 129: ...e specified Click the CPU Module Direct Coupled Setting button on the Specify Connection Destination Connection window to display the CPU Module Direct Coupled Setting window Select the adapter on the window Connection via HUB GX Works3 settings No Item Selection item Internal setting Input value 1 PC side I F Ethernet Board 2 PLC side I F PLC Module Ethernet Port Direct Connection Other Station S...

Страница 130: ...LED turns on in response to the RUN instruction Page 129 Running Stopping and Resetting If any error is detected the ERR LED flashes or lights up Monitoring and debugging The ON OFF status of PLC s devices current values or set values can be monitored or changed by using engineering tools For details refer to GX Works3 Operating Manual No Item Selection item Internal setting Input value 1 PC side ...

Страница 131: ...status of the CPU module can be changed externally with the RUN STOP RESET switch set to the RUN position The operation status of the CPU module can be set to the PAUSE status Remote operation can be performed by either of the following methods Using contacts MELSEC iQ F FX5 User s Manual Application Using engineering tools GX Works3 Operating Manual Using external devices using SLMP MELSEC iQ F F...

Страница 132: ... terminals Check the proximity between crimp terminals and correct the clearance Looseness of connectors Connect cable connectors securely 3 LED status Check that the LED status is normal Page 132 Checking with LEDs User s manuals for each module Item Inspection item Description 1 Ambient environment Operating ambient temperature The temperature in the panel should be 0 to 55 Operating ambient hum...

Страница 133: ...8 MAINTENANCE AND INSPECTION 8 2 Periodic Inspection 131 8 MEMO ...

Страница 134: ...he action to be taken can be displayed Page 135 Module diagnostics 6 If the cause could not be specified by Module diagnostics check the error history from the event history of the engineering tool to identify the cause Page 136 Event history 7 Check the cause of the error and take corrective actions 9 2 Checking with LEDs Check the module status with LEDs as a means to perform the primary diagnos...

Страница 135: ...nd avoid the maximum value SD524 SD525 of the scan time exceeding the the scan time monitoring time setting value set by the parameter Check that the input used for input interruption or pulse catch is not being abnormally turned on and off in one scan Check that the frequency of the pulse input to the high speed counter is within the specified range Add some WDT instructions to the program and re...

Страница 136: ...tion displays the module configuration and detailed information and error status of each module For the error module identified the module diagnostics can be executed from this window Diagnostics System Monitor Function Description System monitor Displays the module configuration and detailed information and error status of each module Page 134 System monitor Module diagnostics This function diagn...

Страница 137: ... Information required for troubleshooting such as the current error details and cause of the error and action to be taken are displayed The incorrect parameter setting and program error location can also be identified by selecting the error and clicking the Error Jump button On the Module Information List tab the LED status and the switch status of the target module can be checked Diagnostics Syst...

Страница 138: ...tion collected before the CPU module is powered off or reset can also be displayed the error cause can be identified based on the errors The displayed information can also be saved in CSV file format Diagnostics System Monitor Event History button Use the event history function to identify the cause of failure that occurred in facilities or devices For details on this function and collected inform...

Страница 139: ...e the occurrence of the error Continuable errors can be canceled by either of the following methods Using engineering tools Using special relay SM Page 138 Canceling Errors Error status Program execution status Description Required action Major error Stop The module is unable to continue its operation due to a hardware issue Perform troubleshooting If the error still persists consult your local Mi...

Страница 140: ...es and buffer memory using the engineering tool is explained below Online Read from PLC 1 Click the Device Memory check box 2 Click Detail 3 Input character strings in Device Data Name and select the devices to back up 4 Select the Buffer Memory Intelligent Module No and input module number 5 Click OK and then click Execute to read the data from the PLC 9 6 Canceling Errors Only continuable errors...

Страница 141: ...rnal wiring properly Stop the PLC and check that the output turns off When the output turns off The output may be turned off unintentionally in the program Review user program Duplicate coils or RST instructions When the output does not turn off There may be a hardware fault Consult your local Mitsubishi Electric representative Item to check Action Disconnect the external wiring and connect the S ...

Страница 142: ...ation refer to MELSEC iQ F FX5 User s Manual Application Boot operation Boot operation cannot be performed from the SD memory card If the boot operation cannot be performed even after the items shown above are checked there may be a hardware issue Consult your local Mitsubishi Electric representative Item to check Action Check if a password is not registered When a password has been registered aut...

Страница 143: ...e module front surface The year and month of production of the product can be checked from the manufacturer s serial number LOT on the front at the bottom of the CPU module 9 1 X 0 0 0 Control number Year Example 2019 Last two digits of year 1 Month Example October 1 to 9 January to September X October Y November Z December Right side Example nameplate manufacturer s serial number 19X0001 Actual p...

Страница 144: ...ber 1st 2014 FX5 8EX ES FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS FX5 32ER ES FX5 32ET ES FX5 32ET ESS FX5 232ADP FX5 485ADP FX5 232 BD FX5 485 BD FX5 422 BD GOT FX5 1PSU 5V from January 1st 2015 FX5 C32EX D FX5 C32EYT D FX5 C32ET D FX5 C32EX DS FX5 C32EYT DSS FX5 C32ET DSS FX5 4AD ADP FX5 4DA ADP from October 1st 2015 FX5 C16EX D FX5 C16EYT D FX5 C16...

Страница 145: ...models PLCs manufactured in March 2018 are compliant with LVD directive successively from October 1st 2014 FX5 8EYR ES FX5 16EYR ES FX5 32ER ES FX5 32ET ES FX5 32ET ESS FX5 1PSU 5V from October 1st 2016 FX5 16ER ES from January 1st 2019 FX5 C16EYR D TS from October 1st 2019 FX5UJ 24MR ES FX5UJ 24MT ES FX5UJ 24MT ESS FX5UJ 40MR ES FX5UJ 40MT ES FX5UJ 40MT ESS FX5UJ 60MR ES FX5UJ 60MT ES FX5UJ 60MT ...

Страница 146: ...precautions Use EN60947 1 or EN60947 3 standards Place the cutoff device so that it can be operated easily Specify that the cutoff device is for this equipment 1 For the time of compliance with the LVD directive EN61010 2 201 2013 refer to Page 143 Requirement for compliance with LVD directive Caution for when analog products are used It is recommended to perform the following when precision of me...

Страница 147: ... the shielded twisted pair cable as shown below and ground as much of the exposed shield as possible to both sides of the cable Connect a ferrite core to both ends of the cable Ferrite core used in tests by Mitsubishi ZCAT2035 0930A manufactured by TDK Co The control cabinet must be conductive Ground the control cabinet with the thickest possible grounding cable To ensure that there is electric co...

Страница 148: ...ring system Type No of points Common wiring system Input extension sink input type FX5 C16EX D 24 V DC 16 Connector FX5 C32EX D 24 V DC 32 Connector Input extension sink and source input type FX5 C16EX DS 24 V DC 16 Connector FX5 C32EX DS 24 V DC 32 Connector FX5 C32EX DS TS 24 V DC 32 Spring clamp terminal block Model Input Output Input output connection type Type No of points Common wiring syste...

Страница 149: ...r 32 Spring clamp terminal block Output extension relay output type FX5 C16EYR D TS Relay 16 Spring clamp terminal block Model Input Output Input output connection type Type No of points Common wiring system Type No of points Common wiring system Input output extension sink and source input relay output type FX5 16ER ES 24 V DC 8 Relay 8 Screw terminal block Input output extension sink and source ...

Страница 150: ...terminal block Input output extension sink and source input sink output type AC power supply DC input type FX5 32ET ES 24 V DC 16 Transistor 16 Screw terminal block Input output extension sink and source input source output type AC power supply DC input type FX5 32ET ESS 24 V DC 16 Transistor 16 Screw terminal block Item Specifications Voltage rating 24 V DC supplied from 24 V DC service power sup...

Страница 151: ...consumption 5 V DC FX5 16E E 100 mA FX5 C32ET 120 mA Current consumption 24 V DC FX5 16E E 125 mA 85 mA 1 FX5 C32ET 165 mA 100 mA 1 Item Specifications Voltage rating 100 to 240 V AC Voltage fluctuation range 15 10 Rated frequency 50 60 Hz Allowable instantaneous power failure time Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less Power fuse 250 V 3 15 A t...

Страница 152: ...minal block M3 screws FX5 C EX D S FX5 C32ET D SS Connector FX5 C32EX DS TS FX5 C32ET DS S TS Spring clamp terminal block Input type FX5 EX ES FX5 32E FX5 16ER ES FX5 C EX DS TS FX5 C32ET DS Sink source FX5 C EX D FX5 C32ET D Sink Input signal voltage 24 V DC 20 15 Input signal current 4 0 mA 24 V DC Input impedance 5 6 kΩ Input sensitivity current ON 3 0 mA or more OFF 1 5 mA or less Input respon...

Страница 153: ...ations Source input wiring 0V 24V S S X S S Sink input wiring CPU module 0V 24V S S X S S CPU module Input module Input module Powered input output module Powered input output module 24V N L 100 to 240 V AC Fuse X S S 0V Source input wiring 24V N L 100 to 240 V AC Fuse X S S 0V Sink input wiring Input module Input module Source input wiring 0V 24V S S X S S Sink input wiring CPU module 0V 24V S S ...

Страница 154: ...he module does not comply with CE UL cUL standards Output circuit insulation Mechanical insulation Indication of output operation LED is lit when output is on Max load FX5 8EYR ES FX5 16EYR ES FX5 16ER ES FX5 32ER ES 2 A point The total load current of resistance loads per common terminal should be the following value 4 output points common terminal 8 A or less 8 output points common terminal 8 A ...

Страница 155: ... 16ET ES FX5 32ET ES 0 5 A point The total load current of resistance loads per common terminal should be the following value 4 output points common terminal 0 8 A or less 8 output points common terminal 1 6 A or less FX5 C EYT D TS FX5 C32ET D S TS 0 1 A point The total load current of resistance loads per common terminal should be the following value 8 output points common terminal 0 8 A or less...

Страница 156: ...T ESS FX5 16ET ESS FX5 32ET ESS 0 5 A point The total load current of resistance loads per common terminal should be the following value 4 output points common terminal 0 8 A or less 8 output points common terminal 1 6 A or less FX5 C EYT DSS TS FX5 C32ET DSS TS 0 1 A point The total load current of resistance loads per common terminal should be the following value 8 output points common terminal ...

Страница 157: ...is on 2 POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable used to connect the extension module 5 I O terminal Terminals for input or output For details on the terminal layout refer to Page 162 Terminal layout 6 Extension connector Connec...

Страница 158: ... output modules is powered or not Lit Powered Off Not powered or hardware error 3 I O display LED Lit when input or output is on 4 I O connectors Connector for connecting input signal cables or output signal cables For details on the terminal layout refer to Page 162 Terminal layout 5 DISP switch Switches the display of smaller and larger numbers of the input display LED or output display LED Smal...

Страница 159: ...ted to extend modules 2 PWR POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 I O display LED Lit when input or output is on 4 I O terminal Terminals for input or output For details on the terminal layout refer to Page 162 Terminal layout 5 Extension connector Connector for connecting the extension connector of an extensi...

Страница 160: ...output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable used to connect the extension module 5 Terminal Terminals for input and output For details on the terminal layout refer to Page 162 Terminal layout 6 Extension connector Connector for connecting the extension cable of an extension mo...

Страница 161: ...rdware error 3 I O display LED Lit when input or output is on 4 Input connector Connector for connecting input signal cables For details on the terminal layout refer to Page 162 Terminal layout 5 Output connector Connector for connecting output signal cables For details on the terminal layout refer to Page 162 Terminal layout 6 DISP switch Switches input output of the I O display LED Input IN Outp...

Страница 162: ... powered or not Lit Powered Off Not powered or hardware error 3 Input display LED Lit when input is on 4 Input terminal Terminals for input For details on the terminal layout refer to Page 162 Terminal layout 5 Output terminal Terminals for output For details on the terminal layout refer to Page 162 Terminal layout 6 Output display LED Lit when output is on 7 Extension connector Connector for conn...

Страница 163: ...isplay LED Lit when output is on 6 Extension connector cover for next module Cover for protecting the extension connector cover for next module 7 Extension connector for preceding module Connector for connecting the supplied extension cable that connects to the preceding module the CPU module side 8 Terminal block mounting screws Gradually loosen the left and right screws alternatingly to remove t...

Страница 164: ...T ESS X 0 S S 1 2 3 X 4 5 6 7 Y 0 1 2 3 Y 4 5 6 7 C O M 0 C O M 1 Y 0 V 0 1 2 3 Y 4 5 6 7 V 1 X 0 C O M S S 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 X 0 S S 1 2 3 4 5 7 6 X 0 1 2 3 4 5 6 7 Lower numbers Higher number Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Lower numbers Higher number C O M 0 C O M 1 Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Lower numbers Higher number V 0 V 1 X 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 S S ...

Страница 165: ...X6 X7 COM Input X0 X1 X2 X3 X4 X5 X6 X7 COM X0 X1 X2 X3 X4 Notch X5 X6 X7 COM Smaller numbers Larger numbers Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Notch Output 1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Output 1 Y10 ...

Страница 166: ... X6 X7 COM X0 X1 X2 X3 X4 X5 X6 X7 COM Notch Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 COM0 Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V1 Notch Smaller numbers Larger numbers Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Y10 Y11 Y12 Y13 Y14...

Страница 167: ...e CPU module Page 26 Generic Specifications External color weight accessories Model W mm FX5 CNV IF 14 6 No Name Description 1 Extension connector for preceding module Connector for connecting the supplied extension cable that connects to the preceding module the CPU module side 2 Extension connector for next module Connector for connecting the extension connector of an extension module extension ...

Страница 168: ...oving the SD memory card while the card is being accessed may corrupt the data in the SD memory card Always turn off or reset the CPU module or remove the SD memory card after disabling access to the SD memory card With SM606 SD memory card forced disable instruction and SM607 SD memory card forced disable status flag the SD memory card can be disabled and its usage status can be checked It is rec...

Страница 169: ...F turn ON SM606 instruction of forcibly stop using SD memory card so that the SD memory card cannot be used 1 Insert the SD memory card 1 straight into the SD memory card slot Make sure that the notch of the card is directed downward After mounting check that the card is mounted completely If the card is mounted incompletely malfunctions may occur because of poor contact 2 The CARD LED 2 blinks un...

Страница 170: ...6 100 V AC input type FX5 C EX D FX5 C32ET D 24 V DC 48 mA FX 16EYR TB 16 Relay output type FX5 C EYT D FX5 C32ET D 24 V DC 80 mA FX 16EYT TB 16 Transistor output type sink 24 V DC 112 mA FX 16EYS TB 16 Triac output type Sink and source common input source output transistor output FX 16E TB UL 16 input points or 16 output points Directly connected to I O terminals of a PLC FX5 C EX DS FX5 C EYT DS...

Страница 171: ...t sensitivity ON 3 8 mA 80 V AC or more OFF 1 7 mA 30 V AC or less Input response time 1 30 ms or less Input signal format Input sensor form Voltage contact Input circuit insulation Photo coupler insulation Indication of input operation No input LED However the 24 V power LED display exists Power consumption 1 2 W 48 mA 24 V DC Input output configuration circuit Unsupported applications High speed...

Страница 172: ...lation Mechanical insulation Indication of output operation LED is lit when the power is supplied to relay coils Power consumption 1 92 W 80 mA 24 V DC Input output configuration circuit FX 16EYR TB FX 16EYR ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O fu...

Страница 173: ...r insulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYT TB FX 16EYT ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOE...

Страница 174: ...of output element 1 5 V Output circuit insulation Photo coupler insulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop o...

Страница 175: ...ion Indication of output operation LED is lit when the power is supplied to photo thyristors Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYS TB FX 16EYS ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOEN instr...

Страница 176: ...or connecting input signal cables or output signal cables for CN2 FX 32E TB and FX 32E TB UL only 3 POWER LED Indicates the conduction status FX 16EX A1 TB only Lit Powered Off Not powered or hardware error 4 Operation display LED Turns on when the output is on FX 16EYR TB FX 16EYR ES TB UL FX 16EYT TB FX 16EYT ES TB UL FX 16EYT ESS TB UL FX 16EYS TB and FX 16EYS ES TB UL only 5 Terminal block for...

Страница 177: ...5 6 7 COM COM Smaller numbers Larger numbers CN1 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN2 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN1 CN2 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM2 0 1 2 3 COM3 COM3 4 5 6 7 COM4 COM4 Smaller numbers Larger numbers 24 24 POWER 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM...

Страница 178: ...9 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 3 2 1 0 COM 7 6 5 4 3 2 1 0 CN1 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 5 4 3 2 1 0 0 COM 7 6 5 4 3 2 0 1 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB FX 32E TB 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers 5 4 1 C...

Страница 179: ... 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 0 COM0 7 6 5 4 3 2 0 1 1 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 COM0 7 6 5 4 3 2 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB UL FX 32E TB UL 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers CN2...

Страница 180: ... COM4 COM4 4 to 7 20 COM 6 7 5 4 3 2 1 0 COM 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 CN1 Photocoupler Photocoupler Photocoupler Photocoupler 0 to 3 0 to 3 4 to 7 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 0 to 7 Smaller numbers 0 to 7 Larger numbers 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 1...

Страница 181: ... COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 4 5 6 7 1 1 3 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 0 to 7 Smaller nu...

Страница 182: ...V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo coupler Photo coupler 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3...

Страница 183: ... 5 6 7 3 3 k 3 3 k U U U U U Surge absorbers are connected to each output 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 ...

Страница 184: ...onnector 24 Extension connector cover 23 G Genuine product certification label 25 I Input display LED 23 Installing directly 64 68 Installing on DIN rail 64 M Memory capacity 33 N Nameplate 25 Number of input output points 49 54 O Output display LED 23 P P RUN LED 23 Peripheral device connecting connector cover 23 PWR LED 23 R RUN STOP RESET switch 24 129 S SD memory card disable switch 24 SD memo...

Страница 185: ...I 183 MEMO ...

Страница 186: ...dified parts Section 2 3 6 5 Appendix 6 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual ...

Страница 187: ...tions in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies and applications in which a special quality assurance system is required such as for railway companies or public service purposes shall be excluded from the programmable controller applications In addition applications in which human life or property that could ...

Страница 188: ...LINK are either registered trademarks or trademarks of Anywire Corporation Phillips is a registered trademark of Phillips Screw Company The company names system names and product names mentioned in this manual are either registered trademarks or trademarks of their respective companies In some cases trademark symbols such as or are not specified in this manual ...

Страница 189: ......

Страница 190: ...APAN Specifications are subject to change without notice When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permission Manual number SH NA 082206ENG B Model FX5UJ U HW E Model code 09R578 ...

Отзывы: