6 WIRING
6.6 Output Wiring
109
6
■
Source output type
*1 The output circuit of the PLC does not have a built-in fuse.
Provide a fuse suitable for each load to prevent melting of the wires on the circuit board caused by output device breakdown due to load
short-circuiting.
*2 "
⋅
" represents vacant terminals.
Y0
+V0
Y7
Y0
+V1
Y7
PL
Power ON
Emergency
stop
MC
MC
MC
MC
DC power supply
Load
Load
Fuse
Fuse
AC power supply (100 to 240 V)
Breaker
Load
Load
Fuse
*1
Fuse
*1
Y0
+V0
Y14
+V3
Y4
+V1
*2
Power supply for loads connected to
PLC output terminals
As for emergency stop operation, see "DESIGN
PRECAUTIONS" at "Safety Precautions" field.
CPU module
Transistor output (source)
Output module
Transistor output (source)