152
APPX
Appendix 3 I/O Module
Output specifications
There is the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient temperature. For details,
refer to
Page 32 Input/Output Derating Curve.
■
Relay output
*1 When two common terminals are connected outside the I/O module, resistance load is 8 A or less.
Item
Specifications
No. of output points
FX5-8EYR/ES
8 points
FX5-16EYR/ES
16 points
FX5-16ER/ES
8 points
FX5-32ER/ES
16 points
FX5-C16EYR/D-TS
16 points
Connection type
FX5-8EYR/ES
FX5-16EYR/ES
FX5-16ER/ES
FX5-32ER/ES
Screw terminal block (M3 screws)
FX5-C16EYR/D-TS
Spring clamp terminal block
Output type
Relay
External power supply
30 V DC or less
240 V AC or less
(250 V AC or less when the module does not comply with CE UL, cUL standards)
Output circuit insulation
Mechanical insulation
Indication of output operation
LED is lit when output is on
Max. load
FX5-8EYR/ES
FX5-16EYR/ES
FX5-16ER/ES
FX5-32ER/ES
2 A/point
The total load current of resistance loads per common terminal should be the following value.
• 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
FX5-C16EYR/D-TS
2 A/point
The total load current of resistance loads per common terminal should be the following value.
• 8 output points/common terminal: 4 A or less
Open circuit leakage current
Min. load
5 V DC, 2 mA (reference values)
Response time
OFF
→
ON
Approx. 10 ms
ON
→
OFF
Approx. 10 ms
Output circuit configuration
FX5-8EYR/ES
FX5-16EYR/ES
FX5-16ER/ES
FX5-32ER/ES
FX5-C16EYR/D-TS
Load
Fuse
Fuse
Y
COM0
Y
COM1
AC power
supply
DC power
supply
Load
Fuse
Fuse
Y
COM0
COM0
Y
COM1
COM1
AC power
supply
DC power
supply
Содержание MELSEC iQ-F Series
Страница 1: ...MELSEC iQ F FX5UJ User s Manual Hardware ...
Страница 2: ......
Страница 133: ...8 MAINTENANCE AND INSPECTION 8 2 Periodic Inspection 131 8 MEMO ...
Страница 185: ...I 183 MEMO ...
Страница 189: ......