9 TROUBLESHOOTING
9.7 Troubleshooting for Each Symptom
139
9
9.7
Troubleshooting for Each Symptom
When the CPU module does not operate properly, check the appropriate item from the following and perform troubleshooting.
I/O operation (CPU module, I/O module)
Output does not turn on
Output does not turn off
Input does not turn on
Input does not turn off
Item to check
Action
Check for errors with external wiring.
Connect the external wiring properly.
Stop the PLC, and forcibly turn on or off the inoperable output with a
peripheral device or the engineering tool.
■
When the output operates
The output may be turned off unintentionally in the program. Review user
program (Duplicate coils or RST instructions).
■
When the output does not operate
Check the configuration of the connected devices and the connection of the
extension cables.
If the configuration of the external wiring and connected devices and the
connection of the extension cables are acceptable, there may be a hardware
issue. Consult your local Mitsubishi Electric representative.
Item to check
Action
Check for errors with external wiring.
Connect the external wiring properly.
Stop the PLC and check that the output turns off.
■
When the output turns off
The output may be turned off unintentionally in the program. Review user
program (Duplicate coils or RST instructions).
■
When the output does not turn off
There may be a hardware fault. Consult your local Mitsubishi Electric
representative.
Item to check
Action
Disconnect the external wiring and connect the [S/S] terminal and the [0V]
terminal or the [24V] terminal.
Short-circuit the [0V] terminal or [24V] terminal not connected to the [S/S]
terminal and the input terminal, and check the LED or a peripheral device to
check that the input turns on.
■
When the input turns on
Check that the input device does not have a built-in diode or parallel
resistance. If so, refer to
Page 93 Precautions for connecting input
■
When the input does not turn on
Measure the voltage between the [0V] terminal or [24] V terminal not
connected to the [S/S] terminal and the input terminal with a tester to check
that the voltage is 24 V DC.
Check the configuration of the external wiring and connected devices and the
connection of the extension cables.
Item to check
Action
Check that there is no leakage current from input devices.
If the leakage current is 1.5 mA or more, connect a bleeder resistance.
(
Содержание MELSEC iQ-F Series
Страница 1: ...MELSEC iQ F FX5UJ User s Manual Hardware ...
Страница 2: ......
Страница 133: ...8 MAINTENANCE AND INSPECTION 8 2 Periodic Inspection 131 8 MEMO ...
Страница 185: ...I 183 MEMO ...
Страница 189: ......