5 SYSTEM CONFIGURATION
5.2 Power Supply to the AnyWireASLINK System
Description of condition 1
■
Constants related to the non-isolation slave module (Ihin, Iho)
In the non-isolation slave module, the current required for the internal control circuit and the connected load is supplied with
transmission cables (DP, DN).
• The 24VL and 0VL terminals of a slave module are used to supply the power to the connected load.
• For the current consumption of a non-isolation slave module, refer to the manual for the slave module used.
■
Ihin(A): Current consumption of the non-isolation input slave module/I/O combined slave module
= Current consumption of the non-isolation input slave module/I/O combined slave Current consumption of connected load (three-wire sensor)
Number of points
■
Iho(A): Current consumption of the non-isolation output slave module
= Current consumption of the non-isolation output slave Current consumption of connected load
Number of points
(1) 24 V DC external power supply
(2) Non-isolation slave module
(3) Internal control circuit
(4) Power supply generation
(5) Connected load