APPENDIX 3 EMC INSTALLATION GUIDELINES
6. Parts for EMC Measures
129
6. Parts for EMC Measures
6.1 Shield Clamp Fitting
The ground can be directly connected to the grounding plate to increase the effect.
Install the grounding plate near the outlet (within 10cm) of each panel, and press against the grounding
plate with the clamp fitting. If the cables are thin, several can be bundled and clamped together.
To provide sufficient frame grounding, install the grounding plate directly on the cabinet or connect with
a grounding wire.
If the grounding plate and clamp fitting set (AERSBA-
SET) is required, please contact Mitsubishi.
40
Peel the cable sheath
at the clamp section
Cable
Clamp f it ting
(F it ting A, B)
Grounding plate
Shield sheath
Cable
•
Outline drawing
MAX L
10
11
35
6
22
17.5
30
+0
.3
0
24
35
A
C
24
0 -0
.2
6
3
7
B
±
0.
3
2-
φ
5 hole
Note 1)
M4 s crew
Installation hole
Note 1)
Screw hole for wiring to cabinet's grounding plate.
Note 2)
The grounding plate thickness is 1.6mm.
A
B
C
Enclosed
fitting
L
AERSBAN-DSET
100
86
30
Two A clamp fittings
A clamp fitting
70
AERSBAN-ESET
70
56
—
One B clamp fitting
B clamp fitting
45
Unit: mm
Clamp section drawing
Grounding plate
Clamp fitting