3. Setting
34
3.14. Examples of Simple Settings
The following shows a simple setting example.
■
Setting Example
Model:
ME96SSEA-MB
Phase wire system : 3-phase 4-wire
Measuring element :
A, V, W, PF
Input Voltage :220/380V
CT primary current : 200A
CT Secondary current:5A
frequency
:50Hz
MODBUS
®
RTU
:
address
1,
baud rates
19.2kbps,
parity
even,
stop bit
1
■
Setting Procedure
Items of which setting value need to be changed are indicated by .
Operation mode
Set the setting menu number to "1" and then press S E T .
Setting menu
The factory default setting is "3-phase 4-wire," so just press SET.
Phase wire system
Setting is "P01," so just press SET.
Display pattern
The factory default setting is "No VT," so just press SET.
VT/direct voltage
selection
The factory default setting is "220/380V," so just press .
Direct voltage
The factory default setting is "5A," so just press SET.
CT secondary
current
Set to "200A" and then press SET.
CT primary
curren
t
The factory default setting is "50Hz," so just press SET.
frequency
The factory default setting is "0 second," so just press SET
.
Time constant for
current demand
Set the setting menu number to "2" and then press SET .
Setting menu
SET
Note: For more details about setting contents, refer to pages 16 to 19.
SET
SET
SET
SET
SET
SET
SET
SET
SET
Press
+
simultaneously for 2seconds
RESET
SET