Installation 4. Wiring Diagram
Note for Input
Note
1. The voltage input terminals for 3-phase 3-wire are different from those for others.
2. If the polarity for VT and CT are wrong, the measurement cannot be executed correctly.
3. Do not connect wires to the NC terminals.
4. In the case of low voltage, there is no need for grounding of the secondary sides of VT and CT.
5. Always earth the terminal to the protective earth conductor. Earth the terminal with less than
100 ohm of earth resistance. Otherwise there will be a false operation.
Note for MODBUS
®
RTU
Note
1. Use the shielded twisted pair cable. (Recommended cables: Refer to page 66.)
2. To the units at both ends of the MODBUS
®
RTU link, the 120-ohm resistance has to be
attached. This instrument can perform a 120-ohm termination by short-circuiting the terminal of
T/R- and Ter.
3. The earthing has to be connected to earth by a thick wire of low impedance.
4. Keep the distance between MODBUS
®
RTU link to power lines.
5. Connect to earth the SLD terminal at one end.