52
5. Operation
Usage Depending on the Application (Alarm, Operating Time, Password, etc.)
The following shows how to use the instrument depending on the application.
5.2.1. Upper/Lower Limit Alarm Display and Action
When the set upper/lower limit alarm value is exceeded, the display starts to blink.
*For details on how to set the upper/lower limit alarm, refer to
■
Action in case of alarm
Alarm generating:
When the set alarm value is exceeded, the display blinks.
*Note
Alarm cancellation: When an alarm is cancelled, the display turns to the normal mode.
Note: When you set the alarm delay time, an alarm will generate if the set upper/lower limit alarm value is exceeded and
this situation continues for the alarm delay time.
Alarm reset
method
Measured value
>
Upper limit alarm value
Measured value
<
Lower limit alarm value
Measured value
<
Upper limit alarm value
Measured value
>
Lower limit alarm value
Automatic
(Auto)
Screen
and or blink
Normal display
Manual
(HoLd)
Screen
and or
blink
(Alarm generating)
and or
light up
(Alarm retention)
Normal display
(Alarm cancellation)
Note1: If measuring elements of alarm generating are displayed on the screen, the digital value, unit (A, V, W, PF, Hz, %,
DM, and THD), and phase (1, 2, 3, and N) will be displayed according to the alarm status as the following table.
Alarm status
Digital value
Unit
Phase
Alarm generating
Blink*
Blink
Blink*
Alarm retention
Light up
Blink
Blink*
Alarm cancellation
Light up
Light up
Light up
Note2: When the backlight blinking is set to
‘on’ in case of alarm, the backlight blinks at generating alarm.
Note3: On the Max/Min value screen, the present value, which is displayed at the middle line of digital display,
and or blink.
■
Monitored phase of upper/lower limit alarm item
The phase for monitoring the upper/lower limit alarm varies depending on the measuring item.
For details, refer to the following table.
Upper/Lower limit alarm item
Monitored phase
3-phase
4-wire
3-phase 3-wire
(3CT, 2CT)
1-phase 3-wire
(1N2)
1-phase 3-wire
(1N3)
A upper limit, DA upper limit
1, 2, 3
1, 2, 3
1, N, 2
1, N, 3
A lower limit, DA lower limit
1, 2, 3
1, 2, 3
1, 2
1, 3
A
N
upper limit, DA
N
upper limit
N
―
―
―
A
N
lower limit, DA
N
lower limit
N
―
―
―
V (L-L) upper limit Note1
12, 23, 31
12, 23, 31
1N, 2N, 12
1N, 3N, 31
V (L-L) lower limit Note1
12, 23, 31
12, 23, 31
1N, 2N, 12
1N, 3N, 31
V (L-N) upper limit
1N, 2N, 3N
―
―
―
V (L-N) lower limit
1N, 2N, 3N
―
―
―
W upper limit, var upper limit, PF upper limit
Total
Total
Total
Total
W lower limit, var lower limit, PF lower limit
Total
Total
Total
Total
Hz upper limit
1N
12
1N
1N
Hz lower limit
1N
12
1N
1N
HI total upper limit
1, 2, 3
1, 2, 3 *Note2
1, 2
1, 3
HI
N
total upper limit
N
―
―
―
THD
V
upper limit
1N, 2N, 3N
12, 23
1N, 2N
1N, 3N
Note1: For 12-phase or 31-phase of 1-phase 3-wire system, alarm monitoring is executed based on twice the set
upper/lower limit alarm value.
Note2: Harmonic current 2-phase is measured for 3-phase 3-wire system (3CT) only.
*When the phase of no alarm is
displayed on the screen, it does not
blink.
RESET
Содержание ME96SSEB-MB
Страница 64: ...63 7 Installation Dimensions ME96SSEB MB mm ...