21
3. How to Set up
3.2
Setting Menu 1: Basic Setup (Settings for Phase Wire System, Display Pattern,
VT/Direct Voltage, and CT Primary Current)
Set the settings for CT.
You will set the primary and secondary current of CT.
<Secondary current setting>
Note: CT is Current Transformer.
<Primary current setting>
The factory default setting: 5.0 A
④
CT current
・
From the upper digit, set the blinking digit with or .
・
By pressing , move the setting digit, blinking one, to a
lower digit.
・
By pressing , move the setting digit, blinking one, to
an upper digit.
・
The setting ranges from 1.0 A
to 30000.0 A.
The setting unit is A.
*If you set out of range, the error message (E05) will appear.
If the error message appears, press and then review the
settings to set it again.
・
By pressing at the lowest digit, shift to the next setting
item.
1 A
5 A
+
-
DISPLAY
SET
SET
SET
Continued form the previous page.
(2) For measurement with VT
<Secondary voltage setting>
(a) When set to 3-phase 4-wire system (Phase voltage)
63.5 V 100 V 110 V 115 V 120 V
(b) When set to 3-phase 3-wire (2CT, 3CT) /1-phase 2-wire (Line voltage)
<Primary voltage setting>
The factory default settings:
・
For 3-phase 4-wire system
⇒
200 V (Phase voltage)
・
For 3-phse 3-wire/1-phase 2-wire system
⇒
10000 V
(Line voltage)
・
From the upper digit, set the blinking digit with or .
・
By pressing , move the setting digit, blinking one, to a lower digit.
・
By pressing , move the setting digit, blinking one, to an upper digit.
・
The setting ranges from
60 V to 750000 V.
The setting unit is V.
*If you set out of range, the error message (E05) will appear.
If the error message appears, press and then review the settings to
set it again.
・
By pressing at the lowest digit, shift to the next setting item.
100 V 110 V 220 V
+
-
SET
DISPLAY
SET
SET
SET
DISPLAY
SET
DISPLAY