7. Installation
7.4. Wiring Diagram
For Input
Note
1. The voltage input terminals of 3-phase 3-wire system are different from those of other
systems.
2. If the VT and CT polarities are incorrect, measurement will not be correctly executed.
3. Do not wire the NC terminal.
4. For low voltage, it is not necessary to ground the VT and CT secondary sides.
5. Be sure to ground the earth terminal ( ) to use. The ground resistance is 100 ohm or less.
Improper ground may cause a malfunction.
For MODBUS RTU
Note
1. Use a shielded twisted pair cable for transmission signal line.
*For recommended cables, refer to
8.3 MODBUS RTU Communication Specifications
2. Install 120-Ohm terminating resistors between terminals
‘T/R+’ and ‘T/R-’ for devices at
both ends of MODBUS RTU communication line.
3. Use wires as thick as possible to ground for low impedance.
4. The transmission signal lines of MODBUS RTU communication must not be placed close
to or bound together with high voltage lines.
5. Perform one point grounding for the SLD terminal.