3. How to Set up
Setting Menu 3: Display Settings (Settings for Display of Active/Reactive Energy and
Harmonic Measurement)
This section describes how to set the special measurement of active/reactive energy and harmonic display.
In the operating mode, press the and buttons simultaneously for 2 seconds or more to enter the
following operation.
SET
DISPLAY
①
Active/Reactive
Energy
measurement
Set the display combination of active energy and reactive energy
(imported/exported, lag/lead) and the measurement method of reactive
energy.
Combination
(Settings)
Active energy
(Wh)
Reactive energy
(varh)
Reactive
energy
measurement
method
Imported Exported
Imported
Exported
lag lead lag lead
Ⅰ
○
○
2 quadrant
measurement
Ⅱ
○
○
○
Ⅲ
○
○
○
○
4 quadrant
measurement
Ⅳ
○
○
○
○
○
○
Note: For details on how to measure reactive energy, refer to
Combination
Ⅰ
,
Ⅱ
⇒
They are suitable for measuring systems without a
private power generator or measuring reactive
power of capacitor load where power factor is
around zero generally.
Combination
Ⅲ
,
Ⅳ
⇒
They are suitable for measuring systems with a
private power generator.
<Display exapmles>
When
‘Wh’ or ‘varh’ is selected in the display pattern of P00, it is displayed.
Combination
Ⅰ
Combination
Ⅱ
Combination
Ⅲ
Combination
Ⅳ
varh (lag)
Exported
Imported
varh (lead)
Select 3 in the setting menu.
*Refer to the right figure.
Setting Menu
Set
t
he harmonic display.
When you set to
“on (Display)”, harmonic measured values are displayed on
the additional screen of display pattern.
②
Harmonics
oFF
on
(Not display)
(Display)
SET
RESET
SET
DISPLAY
According to
complete the settings or shift to other setting menu.
Setting Menu
SET