3. How to Set up
3.6
Setting Menu 5:
Alarm Settings (Settings for Upper/Lower Limit Alarm and Motor
Starting Current Mask Function)
SET
DISPLAY
According to
complete the settings or shift to other setting menu.
Setting Menu
SET
DISPLAY
For motor current monitoring, this setting enables to prevent unnecessary
maximum value update and alarm generating caused by motor starting
current.
・
When this setting is not necessary
⇒
Select "oFF" and then press
to
move to the next setting item.
・
When this setting is necessary
⇒
Select "on" and then press
to move to
(1) below.
(1) Motor starting current threshold
Set the threshold to detect motor starting current.
Setting range
Setting step
*Note
3 to 5 to 120 (%)
1%
*Note: This is the percentage of the CT primary current
setting.
(2) Motor starting current delay time
During the delay time after motor starting current is
detected, neither a maximum value update nor an
alarm is generated.
⑧
Motor starting
current delay time
oFF on
1 s
3 s
5 s
10 s
15 s
20 s
30 s
45 s
4 min
5 min
SET
SET
SET
DISPLAY
1 min
1.5 min
2 min
3 min
It is possible to blink the backlight in case of alarm.
⑦
Backlight blinking
for alarm
o
FF
on
(Not blink)
(Blink)
Note: When
①
Upper/Lower limit alarm item 1 and
③
Upper/Lower limit
alarm item 2 to 4 are all set to
“non”, this setting is skipped.