- 51 -
6.Other
6.5 Measurement Characteristic
■
Metering actions in other than operation mode
Status
Measurement
Display
Several seconds just
after turning on the
auxiliary power supply
(Backlight is lit, and
LCD is not lit.)
No measurement
No display
Setting mode,
Set value confirmation
mode
Password protection
mode
Same actions
as in operation
mode
No display of
measured value
During power failure
No measurement
No display
■
Metering actions in input status
Measurement
items
Actions
Current (A)
0A when the input current is less than 0.005A
When it is over the upper limit of the possible
display range (9999), the upper limit of the
possible display range (9999) is displayed.
Voltage (V)
0V when the input voltage (line voltage) is less than11V.
For 3-phase 4-wire, 0V when the line to neutral voltage
is less than 11V or the line to line voltage is less than
19V.
For 1-phase 3-wire, 0V when the voltage between P1-P3
is less than 22V.
When it is over the upper limit of the possible
display range (9999), the upper limit of the
possible display range (9999) is displayed.
(Note 2)
Active power (W)
0W for total when the current and the voltage are 0A and
0V for all 3 phases.
0W for each phase when the current of phase n is 0A or
the voltage of phase n is 0V.
(where n = 1,2 or 3)
When it is over the upper limit of the possible
display range (9999), the upper limit of the
possible display range (9999) is displayed.
Power factor (PF)
1.0 for total when the current and the voltage are 0A and 0V for all 3 phases.
1.0 for each phase when the current of phase n is 0A or the voltage of phase n is 0V. (where n = 1,2 or 3)
Frequency (Hz)
When the voltage of phase1 is 0V, ---- is displayed.
(Note 3)
When the frequency is less than 44.5Hz or
over 99.9Hz, ---- is displayed.
Operating Time
999999 hour is displayed if it is over 999999.
Note1: Input current and input voltage means the input to the instrument. They are not to primary sides of VT, CT.
Note2: For direct measurement, it does not input upper maximum scale value.
Note3: Depending on the setting, “----“ is displayed when the voltage of phase 1 is not 0V.