- 20 -
3. Setting
3.4 Setting Menu 3:
Display Settings (Setting Maximum Scale)
This section shows how to set maximum scale of current, voltage, active power and power factor in the bar graph.
In the operation mode, press
and
simultaneously for 2 seconds or more, and the following operation
becomes available.
SET
Set the maximum scale of Active power.
If you have not set active power to “Display pattern”,
this display will be skipped.
(1)Maximum scale value
(2) single deflection / double deflection
If you have not set active power to “Display pattern”,
this display will be skipped
.
③
Active power
maximum scale
Note
:
The maximum scale value becomes the value in the table on page 46.
single deflection
double deflection
+
-
SET
DISPLAY
±0 STEP (100%
:
Rating)
~
~
-18 STEP (About 20%)
+3 STEP (About 120%)
Set the voltage maximum scale.
If you have not set voltage to “Display pattern”, this display will be skipped.
Maximum scale value
②
Voltage maximum
scale
Note
:
The maximum scale value becomes the value in the table on page 46.
± 0 STEP (100%
:
Standard maximum scale value
)
~
~
-18 STEP (About 20%)
+10 STEP (About 250%)
+
-
Set the current maximum scale.
If you have not set current to “Display pattern”, this display will be skipped.
(
1
)
Maximum scale value
(
2
)
Special current maximum scale
This display is displayed when you set the "SP" in 3.1.
①
Current maximum
scale
Note
:
The maximum scale value becomes the value in the table on page 46.
± 0 STEP (100%
:
Rating)
~
~
-
10 STEP (About 40%)
+
3 STEP (About 120%)
+
-
Primary Current
(
1.4.1Primary Current Setting value
)
SP.(Special Setting)
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
Set the setting menu number to "3".
(as shown in the right figure)
Setting menu
RESET