- 19 -
3. Setting
3.3 Setting Menu 2:
Communication Settings (Setting the MODBUS
®
RTU communication)
In the operation mode, press
+
simultaneously for 2 seconds or more, and the following operation
becomes available.
SET
RESET
Set the MODBUS
®
RTU parity.
③
MODBUS
®
RTU
parity
non
odd
even
(
EVEn
)
Set the MODBUS
®
RTU baud rate.
②
MODBUS
®
RTU
baud rates
2400bps
4800bps
9600bps
19.2kbps
38.4kbps
Set the MODBUS
®
RTU address number.
Selectable addresses: 1 to 255
①
MODBUS
®
RTU
address
Set the MODBUS
®
RTU stop bit.
④
MODBUS
®
RTU
stop bit
Stop bit 1
Stop bit 2
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
According to the setting flow diagram (page 14), save the changed
contents, or continue to the other setting menu.
Setting Menu
SET
Set the setting menu number to “2”.
(as shown in the right figure)
Setting Menu