- 41 -
5.Operation
5.1 Basic Operation
Active Energy Display
■
Disp
lay format
The following table shows the display format of active energy based on the total load.
※
1. For the direct voltage setting, the direct voltage is used for calculation instead of
the VT primary voltage.
※
2. For 3-phase 4-wire or 1-phase 3-wire, the VT primary voltage and direct voltage
are calculated using the line to phase voltage.
Total load [kW]
Display type
Digital Display
Digital Display
Less than 10
888888
kWh
(Unit can be changed from
Wh/kWh/MWh.)
10 or higher and less than 100
100 or higher and less than 1000
1000 or higher and less than 10000
MWh
(Unit can be changed from
Wh/kWh/MWh.)
10000 or higher and less than 100000
100000 or higher
How to change the unit of Wh
When and are pressed simultaneously for 2 seconds, the unit of Wh will be changed. This will enable to check
the upper digits or lower digits of counts.
Note: When the setting value of the VT primary voltage and the CT primary current are large, the lower digits less than a measurement range
display "0".
Wh zero reset
When , , and are pressed simultaneously for 2 seconds, the measured values of Wh and will be
reset.
When the password protection setting is enabled, Wh are reset after you enter the password.
Also, you can clear all Wh values by communication function. (In this case, the password is not necessary.)
(Note 1: This is effective only in the instantaneous value display.)
Each measurement item display during power transmission
The following table shows the symbol display (±) for each measurement value according to the power reception /power sending status.
Note
.
Normal mode
:
“IEC mode” in the Setting Menu 8 is OFF
IEC mode
:
“IEC mode” in the Setting Menu 8 is ON
(Refer to page 28 about “IEC mode” in the Setting Menu 8.)
Quadrant
Measured items
Imported Lag
Imported Lead
Exported Lag
Exported Lead
A, A
N, V, Hz
Unsigned
W
Unsigned
”
-
”sign
PF
Normal mode
Unsigned
display
※
“-”
sign
display
※
“-”
sign
display
※
Unsigned
display
※
IEC mode
Unsigned
display
※
“-”
sign
display
※
Unsigned
display
※
“-”
sign
display
※
※
Turns on when displayed on the bar graph.
Total load power[kW] =
α
x (VT primary voltage) x (CT primary current)
1000
PHASE
SET
RESET
Example of change: Case of active energy (imported) = 012,345,678,901,234.567Wh
Press and simultaneously for 2 seconds
+
-
Unit
:
Mega
Unit
:
non
Unit
:
non
Unit
:
kilo
α
:
1 1-phase 2-wire
2 1-phase 3-wire
3 3-phase 3-wire
3 3-phase 4-wire
The metering status blinks while the active
energy is being counted.
When active energy is not counted, turns OFF.
Active energy
measurement
value
Metering
status
+
-
+
W
+
W
-
W
+
var
-
var
Exported lag
Imported lead
Exported lead
Imported lag
√