6 Examination of System Configuration
6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
75
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
1
Introduc
tion
2
Features an
d
Part Nam
es
3
Produc
t
Introducti
on
4
Specifi
cations
5
Ve
rsi
on and
Peri
pheral
De
vice
s
6
Sy
stem
Confi
gurati
on
7
Input/Output
N
os.,
Unit N
os.
8
Ins
tallati
on
9
Preparati
on
and
Power Suppl
y
Wi
rin
g
10
Input W
iring
6.3.3
Maximum number of input/output points when AnyWireASLINK master is used
1. Calculation of maximum number of input/output points
The maximum number of available input/output points is as follows when AnyWireASLINK master block is
used.
*1.
With regard to remote I/O of the AnyWireASLINK, input/output points set by the rotary switch of the
AnyWireASLINK master are assigned.
When using together with the CC-Link master, make sure that the total number of remote I/O points in
CC-Link and AnyWireASLINK master is 128 or less. For details, refer to FX
3U
-128ASL-M User's
Manual.
2. Procedures for calculating number of input/output points based on example of system
configuration
For the main unit, input/output extension units/blocks and AnyWireASLINK, the number of input/output points
and the total number of points are restricted.
*2.
When using 27 remote I/O points (8 points 3 + 2 1 point) shown above, assign 32 or more
input/output points using the rotary switch of the AnyWireASLINK master.
+
+
Maximum number of
input/output points
256 points
Maximum number
of points
controllable on
system
Number of input/
output points
Total number of
input/output points
(A) : Number of input/output points of main unit
(B) : Number of input/output points of input/output
powered extension units
(C) : Number of input/output points of input/output
extension blocks
(D) : Number of remote I/O points of FX2N-64CL-M
(E) : Number of input/output points occupied by special function blocks
(F) : Number of remote I/O points assigned to AnyWireASLINK master
(A)(B)(C)(D)
Number of input/output
occupied points
(E) units
AnyWireASLINK remote I/O
(F) stations
For details, refer to Subsection 6.3.1.
8
points
Number of points occupied
by special function blocks
128
points
*1
Remote I/O assigned to
AnyWireASLINK master
-
-
Special
function block
-
-
Input
extension
block
X000 to X027
Y000 to Y017
Main unit
X030 to X047
Y020 to Y037
Input/output
powered
extension unit
X050 to X067
-
Input
extension
block
8 points
8 points
16/16=32
points
24/16=40
points
16/0=16
points
8/0=8 points
X070 to X077
-
FX
3U
-128ASL-M
256 points
AnyWireASLINK system
Slave
(1 point)
Slave
(2 point)
Slave
(8 point)
Slave
(8 point)
Slave
(8 point)
Number of
remaining
points
0 points
128
224
Number of
remaining points
Number of input/output points (excluding remote I/O points on AnyWireASLINK)
+ Number of input/output occupied points
Up to 128 points
Number of input/output points occupied by
special function blocks (16 points)
Number of AnyWireASLINK
input/output points
Up to 128 points
256 points or less in total
112
96
Number of remote I/O
points (32 points)
*2
Number of input/output points (96 points)