The FX-16EYT(-H)-TB is used by connecting it to the FX
2N
series output extension block (transistor).
The applications shown below are not supported.
20.8.1 Specifications
*1.
This response time does not include the response delay at the PLC.
Output Connector
Connectable models
FX
2N
-16EYT-C (sink output)
Unsupported Applications
Pulse outputs
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation
(PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction,
absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV)
instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction
Time division inputs Input matrix (MTR) instruction, digital switch (DSW) instruction
Time division output Seven segment with latch (SEGL) instruction
Item
Transistor output
FX-16EYT-TB
FX-16EYT-H-TB
Input/output
circuitry
Load voltage
5-30 V DC
Max.
load
Resistance
load
0.5A/point
The total load current of resistance loads per common
terminal should be the following value.
•
4 output points/common terminal: 0.8A or less
1A/point
The total load current of resistance loads per common
terminal should be the following value.
•
4 output points/common terminal: 3A or less
Inductive
load
12W/24V DC
The total of inductive loads per common terminal should
be the following value.
•
4 output point/common terminal: 19.2W or less/24V
DC
24W/24V DC
The total of inductive loads per common terminal should
be the following value.
•
4 output point/common terminal: 72W or less/24V
DC
Open-circuit
leakage current
0.1mA / 30V DC
Res-
ponse
time
OFF ON
*1
0.2ms or less/24V DC
0.3ms or less/24V DC
OFF ON
*1
1.5ms or less/24V DC
4ms or less/24V DC
Output element's
ON voltage
1.5V
Circuit isolation
Photo-coupler isolation
Operation
indicators
Activation of the photo-coupler will light the LED indicator lamp on panel.
Power
consumption
2.7W (112mA 24V DC)
Photo-
coupler
3.3k
LED
24V DC
7mA
5-30 V
DC
0 to 7
COMn
Fuse
CN1
Connector
side
External
wiring
24+
Photo-
coupler
LED
0 to 7
COMn
Fuse
CN1
Connector
side
3.3k
24V DC
7mA
External
wiring
5-30 V
DC
24+