4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.5 Performance Specifications
50
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
4.5
Performance Specifications
The main unit performance specifications are explained below.
Item
Performance
Operation control system
Stored program repetitive operation system with interruption function
Input/output control system
Batch processing system (when END instruction is executed)
Input/output refresh instruction and pulse catch function are provided.
Programming language
Relay symbol step-ladder system (SFC notation possible)
Program memory
Max. memory capacity/type
32000-step/EEPROM memory
Max. allowable write: 20,000 times
Memory cassette (Option)
32000-step/EEPROM memory (with loader function)
Max. allowable write: 10,000 times
Writing function during
running
Provided (Program can be modified while the PLC is running.)
→
For the writing function during running, refer to Subsection 5.2.5.
Keyword function
With keyword/Customer keyword function
Real-time clock
Clock function
*1
Built-in
1980 to 2079 (with correction for leap year)
2- or 4-digit year, accuracy within 45 seconds/month at 25 C
Kinds of
instructions
Basic instructions
Sequence instructions: 29
Step-ladder instructions: 2
Applied instructions
125 kinds
Processing
speed
Basic instructions
Standard mode
*3
: 0.21 s/instruction
Extension mode
*3
: 0.42 s/instruction
Applied instructions
Standard mode
*3
: 0.5 s to several hundred s/instruction
Extension mode
*3
: 1.2 s to several hundred s/instruction
Number of input/
output points
(1)Extension-combined
number of input points
128 points or less
(3)Total points
(1) + (2) (3) total number of points is
128 or less.
(2)Extension-combined
number of output points
128 points or less
(4)Remote I/O number of
points (CC-Link, AnyWireASLINK)
128 points or less
The total number of remote I/O points in CC-Link and
AnyWireASLINK must be 128 points or less.
(3) + (4) total number of
points
256 points or less
Input/output
relay
Input relay
X000 to X177
The device numbers are octal.
Output relay
Y000 to Y177
Auxiliary relay
For general
M0 to M383
384 points
-
EEPROM keep
M384 to M1535
1152 points
-
For general
*2
M1536 to M7679
6144 points
-
For special
M8000 to M8511
512 points
-
State
For initial state
(EEPROM keep)
S0 to S9
10 points
-
EEPROM keep
S10 to S999
990 points
-
For general
*2
S1000 to S4095
3096 points
-
Timer (on-delay
timer)
100ms
T0 to T191
192 points
0.1 to 3,276.7 sec
100ms
(for subroutine/interruption
subroutine)
T192 to T199
8 points
0.1 to 3,276.7 sec
10ms
T200 to T245
46 points
0.01 to 327.67 sec
1ms accumulating type
(EEPROM keep)
T246 to T249
4 points
0.001 to 32.767 sec
100ms accumulating type
(EEPROM keep)
T250 to T255
6 points
0.1 to 3,276.7 sec
1ms
T256 to T319
64 points
0.01 to 327.67 sec
Variable analog potentiometers
Available as analog timers
VR1 : D8030
VR2 : D8031
Counter
16 bits up
(For general)
C0 to C15
16 points
Counting from 0 to 32,767