17 Extension Power Supply Unit
17.2 Specifications
288
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
17.2
Specifications
17.2.1 Generic Specifications
The generic specifications are the same as those for the main unit.
→
For the generic specifications, refer to Section 4.1.
17.2.2 Performance Specifications
*1. The output current depends on the ambient temperature as shown in the derating curve below.
17.2.3 External Dimensions
Items
Specifications
Supply voltage
100-240V AC
Voltage fluctuation range
-15%, +10%
Rated frequency
50/60Hz
Allowable instantaneous power failure time
The allowable momentary power failure time depends on the power supply used.
•
100V AC power supply system:
The operation is continued to the momentary power failure for 10 or less ms.
•
200V AC power supply system:
The operation is continued to the momentary power failure for 100 or less ms.
Rush current
30A max. 5ms or less/100V AC, 65A max. 5ms or less/200V AC
Power consumption
20W Max.
Output current
(Internal for supply)
24V DC
300mA
*1
5V DC
1000mA
*1
800
1000
Ambient temperature [°C]
55
40
300
200
5V DC
Output current [mA]
24V DC
0
Derating curve
2- 4.5 mounting holes
55(2.17")
87(3.43")
80(3.15")
(mounting hole pitch)
90(3.55")
4(0.16")
Unit:mm (inches)
9(0.36")