338

19 Display Module (FX3G-5DM)

FX

3G

 Series Programmable Controllers

User's Manual - Hardware Edition

19.12 Memory Cassette Transfers

• Result and measures to take

- The transfer is not executed if a "PLC is running" message 

appears.
In this case, set the PLC to the STOP state, then perform the step 
3) operation described above.

- The transfer is not executed if a "Transfer failed" message 

appears.
In this case, turn the power off, check the memory cassette 
connection, then attempt the operation again from the first step.

- A "Transfer completed" message appears when the transfer is 

completed.
When this message appears, press [OK] or [ESC] to display the 
"memory cassette transfer screen".

5) Press [ESC] to display the "menu screen".

P L C i s r u n n n g

i

r

T a n s e

f

r

f a i e

l d

P L

C a s e t t

s

e

C

T r a n f

r

e

c

s

o m l

p e e

t d

P L

C a s e t t

s

e

C

Содержание FX2N-16E series

Страница 1: ...e Edition Main Unit AC Power Type FX3G MR ES FX3G MT ES FX3G MT ESS DC Power Type FX3G MR DS FX3G MT DS FX3G MT DSS Input Output Powered Extension Unit FX2N E Input Output Extension Block FX2N 8E FX2N 16E Display Module FX3G 5DM Memory Cassette FX3G EEPROM 32L ...

Страница 2: ......

Страница 3: ...during self diagnosis all outputs are turned off Also when an error that cannot be detected by the PLC CPU occurs in an input output control block output control may be disabled External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 3 Note that the output current of the 24V DC service power supply varies depending on the model and the absence presence...

Страница 4: ...t failures or malfunctions Be sure to remove the dust proof sheet from the PLC s ventilation port when installation work is completed Failure to do so may cause fire equipment failures or malfunctions Connect the extension cables peripheral device cables input output cables and battery connecting cable securely to their designated connectors Loose connections may cause malfunctions Connect the dis...

Страница 5: ...plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions Failure to do so may cause electric shock equipment failures a shor...

Страница 6: ... control panel in maintenance make sure to discharge to avoid the influence of static electricity 200 311 379 389 Reference Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device When disposing of batteries separate them from other waste according to local regulations For details of the Battery Directive in EU countries refer...

Страница 7: ...ttempting to install or use the unit And store this manual in a safe place so that you can take it out and read it whenever necessary Always forward it to the end user 2008 MITSUBISHI ELECTRIC CORPORATION Manual number JY997D31301 Manual revision N Date 1 2020 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electri...

Страница 8: ... in purposes related to human life Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or fail...

Страница 9: ...Interpretation of Model Names 34 3 1 1 Main units 35 3 1 2 Input output powered extension units 36 3 1 3 Input output extension blocks 37 3 1 4 Special function blocks 38 3 1 5 Display module 38 3 1 6 Expansion boards 38 3 1 7 Connector conversion adapter 39 3 1 8 Special adapters 39 3 1 9 Extension power supply unit 39 3 1 10 Extension cables and connector conversion adapter Battery Memory casset...

Страница 10: ... F900 Series 65 5 6 Other Peripheral Equipment Applicability 66 5 6 1 Other Peripheral Equipment Applicability 66 6 Examination of System Configuration 67 6 1 Configuration of a Whole System 67 6 1 1 Expansion board connector conversion adapter memory cassette display module configuration 68 6 2 Rules of System Configuration 70 6 3 Number of Input Output Points and Maximum Number of Input Output P...

Страница 11: ...ion 105 8 4 Procedures for Installing on and Detaching from DIN Rail 107 8 4 1 Preparation for installation 107 8 4 2 Installation of main unit 108 8 4 3 Installation of input output powered extension unit block and special function block 109 8 4 4 Removal of main unit 110 8 5 Procedures for Installing Directly with M4 Screws 111 8 5 1 Hole pitches for direct mounting 111 8 5 2 Example of mounting...

Страница 12: ...g source input AC Power Supply Type 149 10 2 5 Examples of external wiring sink input DC Power Supply Type 150 10 2 6 Examples of external wiring source input DC Power Supply Type 152 10 3 100V AC Input 153 10 3 1 Input specifications 153 10 3 2 Handling of 100V AC Input 153 10 3 3 Examples of external wiring 100V AC input 154 10 4 Input Interruption I00 to I50 155 10 4 1 Allocation of pointers to...

Страница 13: ...g precautions 185 12 3 3 Example of external wiring 186 13 Examples of Wiring for Various Uses 187 13 1 Notes about Examples of Wiring 188 13 2 Digital Switch DSW Instructions FNC72 BIN Instructions FNC19 189 13 2 1 When DSW instructions are used 189 13 2 2 When BIN instructions are used 192 13 3 Input Matrix MTR Instructions FNC 52 193 13 4 Seven Segment with Latch SEGL Instructions FNC74 BCD Ins...

Страница 14: ...fications 231 15 3 2 External dimensions 232 15 3 3 Terminal layout 233 15 4 FX2N 32ET ESS UL FX2N 48ET ESS UL FX2N 48ET DSS 234 15 4 1 Product specifications 234 15 4 2 External dimensions 235 15 4 3 Terminal layout 236 15 5 FX2N 32ER FX2N 48ER FX2N 48ER D 237 15 5 1 Product specifications 237 15 5 2 External dimensions 238 15 5 3 Terminal layout 239 15 6 FX2N 32ET FX2N 48ET FX2N 48ET D 240 15 6 ...

Страница 15: ...ct specifications 273 16 9 2 Parts identification and terminal arrangement 274 16 9 3 External dimensions 275 16 10 FX2N 8EYR FX2N 16EYR Relay Output 276 16 10 1 Product specifications 276 16 10 2 Parts identification and terminal arrangement 277 16 10 3 External dimensions 278 16 11 FX2N 8EYT FX2N 16EYT FX2N 16EYT C Transistor Output 279 16 11 1 Product specifications 279 16 11 2 Parts identifica...

Страница 16: ...AD BD 307 18 3 8 FX3G 1DA BD 307 18 3 9 FX3G 8AV BD 308 18 4 Power Supply 309 18 4 1 FX2N 20PSU 309 18 5 Connector Conversion Adapter 309 18 5 1 FX3G CNV ADP 309 18 5 2 FX2N CNV BC 310 18 6 Interface Module 310 18 6 1 FX 232AWC H 310 19 Display Module FX3G 5DM 311 19 1 Specifications 311 19 1 1 Applicable PLC 311 19 1 2 Display switch specifications 311 19 1 3 Part Names 312 19 1 4 External Dimens...

Страница 17: ...ation keys 343 19 14 6 Monitor operation on specified device monitor screen 344 19 14 7 Specified device monitor screen for monitoring 344 19 14 8 Test operation on specified device monitor screen 345 19 15 Screen saver function 346 19 15 1 System information Screen saver function 346 19 15 2 Screen saver display 346 19 15 3 Program example screen saver time setting 346 19 16 Display Screen Protec...

Страница 18: ...ple of output external wiring 377 20 9 4 External wiring precautions 378 21 Memory Cassette 379 21 1 Outline 379 21 2 Specifications 379 21 2 1 Electrical specifications 379 21 2 2 Part names and External dimensions 379 21 3 Installation 380 21 3 1 Installation when the expansion board connector conversion adapter is not used together 380 21 3 2 Installation when the expansion board connector conv...

Страница 19: ...2 Special data registers D8260 to D8279 408 Appendix A 4 Analog special adapters M8280 to M8299 and D8280 to D8299 409 Appendix A 4 1 Special auxiliary relays M8280 to M8299 409 Appendix A 4 2 Special data registers D8280 to D8299 411 Appendix B Instruction List 413 Appendix B 1 Basic Instructions 413 Appendix B 2 Step Ladder Instructions 413 Appendix B 3 Applied Instructions in Ascending Order of...

Страница 20: ...irective The following products have shown compliance through direct testing of the identified standards below and design analysis through the creation of a technical construction file to the European Directive for Electromagnetic Compatibility 2014 30 EU when used as directed by the appropriate documentation UL cUL file number E95239 Models MELSEC FX3G FX3U series manufactured FX3G MR ES FX3G MT ...

Страница 21: ...G 1DA BD FX3G 8AV BD FX3G 5DM from December 1st 2008 FX3G MR ES Where indicates 14 24 40 60 from March 1st 2009 FX3G MT ESS Where indicates 14 24 40 60 from June 1st 2009 FX3U 3A ADP from December 1st 2009 FX3G MR DS FX3G MT DS FX3G MT DSS Where indicates 14 24 40 60 from February 1st 2012 FX3U ENET ADP from September 1st 2013 FX3G 4EX BD FX3G 2EYT BD FX3G 485 BD RJ Standard Remark EN61131 2 2007 ...

Страница 22: ...ial environment EN50081 2 1993 Electromagnetic compatibility Compliance with all relevant aspects of the standard Emission Enclosure port Emission Low voltage AC mains port Emission Telecommunications network port EN50082 2 1995 Electromagnetic compatibility Generic immunity standard Industrial environment Compliance with all relevant aspects of the standard RF immunity Fast transients ESD Conduct...

Страница 23: ...emark EN61131 2 2007 Programmable controllers Equipment requirements and tests The equipment has been assessed as a component for fitting in a suitable control box which meets the requirements of EN61131 2 2007 EN61010 2 201 2013 Safety of electrical equipment for measurement control and test The equipment has been assessed as a component for fitting in a suitable control box which meets the requi...

Страница 24: ...rnal terminal For crimp terminals to be used for the wiring applied with 30 V AC or higher use the products with insulating sleeves Cutoff device such as a breaker or a circuit protector should be installed in accordance with the following precautions Use EN60947 1 or EN60947 3 standards Place the cutoff device so that it can be operated easily Specify that the cutoff device is for this equipment ...

Страница 25: ...ucts Chapter 3 Specifications This chapter contains explanations of the specifications for power supply and input output external dimensions and terminal block layout Chapter 4 Version information This chapter contains explanation for upgrading of FX3G PLCs and information for the application of programming tools Chapter 5 System configuration Procedure for determining whether or not a system conf...

Страница 26: ...DM Chapter 19 FX Series terminal blocks This chapter contains explanations of the procedures for wiring FX 16 32E TB Chapter 20 Memory cassette This chapter contains explanations of the specifications for the memory cassette and the installation procedures Chapter 21 Battery This chapter contains explanations of the procedures for replacing the battery and detecting battery voltage drop Chapter 22...

Страница 27: ...be available in or after September 2008 The manuals for FX3G Series will be available in or after September 2008 FX3G Series Main unit Special function blocks Analog Sequence instructions High speed counter Positioning instructions PID Built in functions Options Memory cassette Battery Expansion board Special adapters Analog Communication As for FX2N Series refer to individual manuals Input output...

Страница 28: ...c provided in structured projects of GX Works2 09R925 Separate volume FX CPU Structured Programming Manual Basic Applied Instruction JY997D34701 Sequence instructions provided in structured projects of GX Works2 09R926 Separate volume FX CPU Structured Programming Manual Application Functions JY997D34801 Application functions provided in structured projects of GX Works2 09R927 FX Series terminal b...

Страница 29: ... 16CCL M User s Manual Separate volume FX2N 16CCL M User s Manual JY992D87901 Details of CC Link master special function block 09R710 Supplied with product FX3U 64CCL Installation Manual JY997D29801 Procedures for handling the CC Link Intelligent device station special function block When using refer to FX3U 64CCL User s Manual Separate volume FX3U 64CCL User s Manual JY997D30401 Details of the CC...

Страница 30: ...ser s Manual JY997D14701 Procedures for handling the 4 ch Pt100 temperature sensor input special adapter When using refer to FX3S FX3G FX3GC FX3U FX3UC Series User s Manual Analog Control Edition Supplied with product FX3U 4AD PTW ADP User s Manual JY997D29101 Procedures for handling the 4 ch Pt100 temperature sensor input special adapter When using refer to FX3S FX3G FX3GC FX3U FX3UC Series User ...

Страница 31: ...s Manual Analog Control Edition Supplied with product FX2N 5A User s Manual JY997D11401 Procedures for handling the 4 ch analog input and 1 ch analog output special function block 09R616 Manuals for positioning control Common Separate volume FX3S FX3G FX3GC FX3U FX3UC Series User s Manual Positioning Control Edition JY997D16801 Details of positioning functions of FX3S FX3G FX3GC FX3U FX3UC Series ...

Страница 32: ...ations and operating procedures of the memory cassette Display module Supplied with product FX3G 5DM Installation Manual JY997D33801 Procedures for mounting and handling the display module Extension power supply unit Supplied with product FX3U 1PSU 5V Installation Manual JY997D22501 Specifications and operating procedures of the extension power supply unit Manual title Manual number Contents Model...

Страница 33: ...8ER UA1 UL FX2N 48ER DS FX2N 48ET DSS FX2N 48ER D FX2N 48ET D FX2N Series input output extension blocks Generic name for the following models FX2N 8ER ES UL FX2N 8ER FX2N Series input extension blocks Generic name for the following models FX2N 16EX ES UL FX2N 16EX FX2N 16EX C FX2N 16EXL C FX2N 8EX ES UL FX2N 8EX UA1 UL FX2N 8EX FX2N Series output extension blocks Generic name for the following mod...

Страница 34: ...32AW FX 232AWC FX 232AWC H RS 232C RS 485 converters Abbreviation of FX 485PC IF Indicators GOT1000 Series Generic name for GT16 GT15 GT14 GT11 and GT10 GOT 900 Series Generic name for GOT A900 Series and GOT F900 Series GOT A900 Series Generic name for GOT A900 Series GOT F900 Series Generic name for GOT F900 Series Manuals FX3G Hardware Edition Abbreviation of FX3G Series User s Manual Hardware ...

Страница 35: ... Connectability in this manual For peripheral devices not applicable to FX3G Series specify FX1N Series for model selection and you can program the sequence In this case use instructions and devices within the ranges common to FX3G Series and the selected model of PLC Remote debugging of program Use of programming software GX Works2 GX Developer enables you to remotely transfer programs and monito...

Страница 36: ...mmunication Edition Ethernet Supported in Ver 2 00 or later Refer to FX3U ENET ADP User s Manual CC Link Master station Compatible with CC Link Ver 2 00 and Ver 1 10 FX3U 16CCL M Master station Compatible with CC Link Ver 1 10 FX2N 16CCL M Intelligent device station FX3U 64CCL Remote device station FX2N 32CCL Refer to the manual for each product CC Link LT Master station FX2N 64CL M Remote I O sta...

Страница 37: ...evice connecting connector cover Connect the extension cables of input output powered extension unit block or special function block to the extension device connecting connectors under this cover FX3U Series extension devices and FX2N Series extension devices can be connected For details on the extension devices refer to Chapter 15 Chapter 16 Chapter 17 and Section 18 1 8 Operation status display ...

Страница 38: ...ect the expansion board display module and memory cassette to the connector 7 Battery connector Connect the optional battery to the connector 8 Battery holder This holder accommodates the optional battery 9 Optional equipment connecting screw holes2 2 places 40 points 60 points type only These holes are designed to secure the expansion board and memory cassette with screws 10 Optional equipment co...

Страница 39: ...iring 2 2 2 Sides Left side 1 2 3 Right side 1 Connector conversion adapter connecting screw holes1 2 places These holes are designed to secure the connector conversion adapter with screws 2 Nameplate The product model name manufacturer s serial number and power supply specifications are shown For details on the manufacturer s serial number refer to Subsection 5 1 1 is a mark that instructs to use...

Страница 40: ...PTW ADP FX3U 4AD PNK ADP FX3U 4AD TC ADP FX3U 232ADP MB FX3U 485ADP MB FX3U ENET ADP FX3G CNV ADP FX3G 14MR ES FX3G 24MR ES FX3G 40MR ES FX3G 60MR ES FX2N 8EX ES UL FX2N 8EX FX2N 8EX UA1 UL FX2N 16EX ES UL FX2N 16EX FX2N 16EX C FX2N 16EXL C FX2N 8ER ES UL FX2N 8ER FX2N 8EYR ES UL FX2N 8EYR S ES UL FX2N 8EYT ESS UL FX2N 8EYR FX2N 8EYT FX2N 8EYT H FX2N 16EYR ES UL FX2N 16EYT ESS UL FX2N 16EYR FX2N 1...

Страница 41: ...lay Terminal block FX3G 60MT ES 60 64 1 36 40 1 24 24V DC sink source Transistor sink Terminal block FX3G 60MT ESS 60 64 1 36 40 1 24 24V DC sink source Transistor source Terminal block DC power supply common to 24V DC sink and source input FX3G 14MR DS 14 16 1 8 6 8 1 24V DC sink source Relay Terminal block FX3G 14MT DS 14 16 1 8 6 8 1 24V DC sink source Transistor sink Terminal block FX3G 14MT D...

Страница 42: ...N 48ET 48 24 24 24V DC sink Transistor sink Terminal block AC power supply common to 100V AC sink and source input FX2N 48ER UA1 UL 48 24 24 100V AC Relay Terminal block DC power supply common to 24V DC sink and source input FX2N 48ER DS 48 24 24 24V DC sink source Relay Terminal block FX2N 48ET DSS 48 24 24 24V DC sink source Transistor source Terminal block DC power supply only for 24V DC sink i...

Страница 43: ...nector FX2N 16EXL C 16 16 5V DC Connector Output extension type FX2N 8EYR ES UL 8 8 Relay Terminal block FX2N 8EYR S ES UL 8 8 Relay Terminal block FX2N 8EYT ESS UL 8 8 Transistor source Terminal block FX2N 8EYR 8 8 Relay Terminal block FX2N 8EYT 8 8 Transistor sink Terminal block FX2N 8EYT H 8 8 Transistor sink Terminal block FX2N 16EYR ES UL 16 16 Relay Terminal block FX2N 16EYT ESS UL 16 16 Tra...

Страница 44: ...trol resistance thermometer sensor thermocouple micro voltage input FX2N 2LC 2 loops Temperature control resistance thermometer sensor thermocouple Model name Description FX3U 16CCL M Master for CC Link Compatible with Ver 2 00 and Ver 1 10 Connectable stations Remote I O station Remote device station Intelligent device station FX2N 16CCL M Master for CC Link Compatible with Ver 1 10 Connectable s...

Страница 45: ...4AD ADP 4 ch voltage current input FX3U 4DA ADP 4 ch voltage current output FX3U 3A ADP 2 2 ch voltage current input 1 ch voltage current output FX3U 4AD PT ADP 4 ch platinum resistance thermometer sensor input 50 to 250 C FX3U 4AD PTW ADP 4 ch platinum resistance thermometer sensor input 100 to 600 C FX3U 4AD PNK ADP 4 ch Pt1000 Ni1000 resistance thermometer sensor input FX3U 4AD TC ADP 4 ch ther...

Страница 46: ...or output sink FX 16EYT H TB 16 Transistor output sink Model name Function FX 16E 500CAB S 5m 16 4 Single wire Wire color red PLC side A 20 pin connector FX 16E 150CAB 1 5m 4 11 Flat cables with tube A 20 pin connector at both ends FX 16E 300CAB 3m 9 10 FX 16E 500CAB 5m 16 4 FX 16E 150CAB R 1 5m 4 11 Round multicore cables A 20 pin connector at both ends FX 16E 300CAB R 3m 9 10 FX 16E 500CAB R 5m ...

Страница 47: ... D SUB 9Pin RS 232C FX 232CAB 1 FX3G 422 BD MINI DIN 8Pin RS 422 Half pitch 14Pin FX 422CAB0 F2 232CAB 2 FX 232AW FX 232AWC FX 232AWC H FX3G CNV ADP FX 232CAB 2 Peripheral device connector USB USB Mini B connector USB D SUB 25Pin FX 422CAB0 F2 232CAB FX 232AW FX 232AWC FX 232AWC H Peripheral device connector RS 422 MINI DIN 8Pin F2 232CAB 1 Expansion board connector FX 30P MINI DIN 8Pin RS 422 FX ...

Страница 48: ... 232C cable F2 232CAB 1 3m 9 10 D SUB 9Pin D SUB 25Pin For connection between personal computer and RS 232C RS 422 converter F2 232CAB 3m 9 10 D SUB 25Pin D SUB 25Pin For connection between personal computer and RS 232C RS 422 converter F2 232CAB 2 3m 9 10 Half pitch 14 pin D SUB 25Pin For connection between personal computer and RS 232C RS 422 converter FX 232CAB 1 3m 9 10 D SUB 9Pin D SUB 9Pin F...

Страница 49: ...PU Q mode master local station when GX Works2 is used Accessing permits read write verify device batch monitoring and device test The communication path of CC Link is illustrated as follows For details refer to the manual of GX Works2 or GX Developer 1 The path when accessing from the FX3U 16CCL M 2 The path when accessing from the master QCPU Q mode station 3 The path when accessing from a local ...

Страница 50: ...ng and 25 to 75 C 13 to 167 F when stored Ambient humidity 5 to 95 RH no condensation when operating Vibration resistance 1 Frequency Hz Acceleration m s2 Half amplitude mm When installed on DIN rail 10 to 57 0 035 Sweep Count for X Y Z 10 times 80 min in each direction 57 to 150 4 9 When installed directly 10 to 57 0 075 57 to 150 9 8 Shock resistance 1 147m s2 Acceleration Action time 11ms 3 tim...

Страница 51: ...500V AC for 1min Between 24V DC service power supply connected to input terminal 24V DC and ground terminal Between input terminal 100V AC and ground terminal 1 5kV AC for 1min Only input output powered extension unit block Between output terminal relay and ground terminal Between output terminal transistor and ground terminal 500V AC for 1min Between output terminal triac and ground terminal 1 5k...

Страница 52: ...ion 6 5 4 2 2 DC Power Supply Type 1 There power consumption values are maximum values which include consumption of all expansion equipment and input current 5 or 7 mA per point Item Specifications FX3G 14M E FX3G 24M E FX3G 40M E FX3G 60M E Supply voltage 100 to 240V AC Voltage fluctuation range 15 10 Rated frequency 50 60Hz Allowable instantaneous power failure time Operation can be continued up...

Страница 53: ...terminal layout refer to Section 4 7 Item Specifications FX3G 14M FX3G 24M FX3G 40M FX3G 60M Number of input points 8 points 14 points 16 1 24 points 36 points 40 1 Input connecting type Removable terminal block M3 screw Input form sink source Input signal voltage AC power supply type 24V DC 10 DC power supply type 20 4 28 8 V DC Input impedance X000 to X007 3 3k X010 or more 4 3k Input signal cur...

Страница 54: ...mply with CE UL or cUL standards Max load Resistance load 2A point The total load current of resistance loads per common terminal should be the following value For details on the common terminal for each model refer to the Section 4 7 Terminal Layout 1 output point common terminal 2A or less 4 output points common terminal 8A or less Inductive load 80VA For the product life refer to Subsection 14 ...

Страница 55: ...l Layout 1 output point common terminal 0 5A or less 4 output points common terminal 0 8A or less Inductive load 12W 24V DC The total of inductive loads per common terminal should be the following value For details on the common terminal for each model refer to the Section 4 7 Terminal Layout 1 output point common terminal 12W or less 24V DC 4 output points common terminal 19 2W or less 24V DC Ope...

Страница 56: ...truction Extension mode 3 0 42 s instruction Applied instructions Standard mode 3 0 5 s to several hundred s instruction Extension mode 3 1 2 s to several hundred s instruction Number of input output points 1 Extension combined number of input points 128 points or less 3 Total points 1 2 3 total number of points is 128 or less 2 Extension combined number of output points 128 points or less 4 Remot...

Страница 57: ...483 648 to 2 147 483 647 32 bits up down EEPROM keep C220 to C234 15 points High speed counter 1 phase 1 count input in both directions 32 bits up down EEPROM keep C235 to C245 Counting from 2 147 483 648 to 2 147 483 647 1 phase 2 count input in both directions 32 bits up down EEPROM keep C246 to C250 2 phase 2 count input in both directions 32 bits up down EEPROM keep C251 to C255 Data register ...

Страница 58: ...Series Model name W mm inches W1 mm inches MASS weight kg lbs FX3G 14M FX3G 14MR ES 90 3 55 82 3 23 Approx 0 50 1 1lbs FX3G 14MT ES FX3G 14MT ESS FX3G 14MR DS FX3G 14MT DS FX3G 14MT DSS FX3G 24M FX3G 24MR ES 90 3 55 82 3 23 Approx 0 55 1 21lbs FX3G 24MT ES FX3G 24MT ESS FX3G 24MR DS FX3G 24MT DS FX3G 24MT DSS FX3G 40M FX3G 40MR ES 130 5 12 122 4 81 Approx 0 70 1 54lbs FX3G 40MT ES FX3G 40MT ESS FX...

Страница 59: ...the DC power supply type does not have the service power supply Do not connect with terminals For external wiring make sure to read the power supply wiring described later Refer to Chapter 9 Indication of Input terminal Both AC and DC power supply type have the same input terminals however the external input wiring differs from each other For external wiring make sure to read the input wiring desc...

Страница 60: ...V3 Y3 V4 Y5 V5 FX3G 14MT ESS 0V 24V Y1 Y4 S S X1 X2 X3 X4 X5 X6 X7 Y2 Y0 COM1 COM2 COM0 COM3 Y3 COM4 Y5 COM5 Y1 Y4 X0 Y2 Y0 V1 V2 V0 V3 Y3 V4 Y5 V5 Y1 Y4 FX3G 14MR DS FX3G 14MT DS FX3G 14MT DSS S S N L X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 Y2 Y0 COM1 COM2 COM0 COM3 Y3 Y4 Y6 Y7 Y10 Y11 COM4 FX3G 24MR ES FX3G 24MT ES 0V 24V Y1 Y5 X0 FX3G 24MT ESS Y2 Y0 V1 V2 V0 V3 Y3 Y4 Y6 Y7 Y10 Y11 V4 0V 24...

Страница 61: ...M1 COM2 COM0 Y3 COM3 Y6 Y7 COM4 Y12 Y13 COM5 Y5 Y11 X20 X21 X22 X23 X24 X25 X26 X27 Y14 Y15 Y16 Y17 Y1 Y4 Y10 X0 Y2 Y0 V1 V2 V0 Y3 V3 Y6 Y7 V4 Y12 Y13 V5 Y5 Y11 Y14 Y15 Y16 Y17 Y1 Y4 Y10 FX3G 40MR DS FX3G 40MT DS FX3G 40MT DSS X0 S S N L X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X17 Y2 Y0 COM1 COM2 COM0 0V 24V Y3 COM3 Y6 Y7 COM4 Y12 Y13 COM5 Y5 Y11 X20 X21 X22 X23 X24 X25 X26 X27 Y16 Y17 Y2...

Страница 62: ...bottom of the product Products manufactured in and after October 2008 and after Year Example 2009 Last digit of year Year Example 2010 Last two digit of year 0 1 1 0 0 0 Control number Product from January 2010 Product during December 2009 or earlier 1 Month Example Jan 1 to 9 January to September X October Y November Z December 9 Z 0 0 0 Control number 1 Month Example Dec 1 to 9 January to Septem...

Страница 63: ...wing expansion boards FX3G 2AD BD FX3G 1DA BD FX3G 8AV BD Supports connection of display module FX3G 5DM Supports of the inverter communication function Supports of the pulse width measurement function Ver 1 20 96 June 2009 Supports connection of following special adapter FX3U 3A ADP Supports the hardware error function of FX3U 4DA ADP Ver 1 30 9Z December 2009 Supports of the MODBUS communication...

Страница 64: ...ion Remarks Before Ver 1 40 GX Works2 SW DNC GXW2 E Ver 1 08J or later Before Ver 2 00 Ver 1 62Q or later Ver 2 00 Ver 1 87R or later FX3G PLC version Model name Media model name is shown below Applicable GX Works2 version Remarks Before Ver 1 40 GX Works2 SW DNC GXW2 J Ver 1 07H or later Before Ver 2 00 Ver 1 56J or later Ver 2 00 Ver 1 86Q or later The setting of the FX3U ENET ADP is supported i...

Страница 65: ...city etc The built in USB port cannot be used for programming communication 5 2 3 Program transfer speed and programming tools 1 Built in USB communication The FX3G PLC has a built in USB communication port and performs program writing program reading and monitoring at high speed 12 Mbps with a personal computer that supports USB 1 Supported programming tools GX Works2 Ver 1 08J or later GX Develo...

Страница 66: ...ng RUN program changes in the RUN mode is enabled using the following programming tools For the operating procedure of and cautions on write during RUN refer to the manual of the used programming tool Programming tools supporting write during RUN English version Programming tool Version Remarks GX Works2 1 SW DNC GXW2 E Ver 1 08J or later Writing in the instruction and device ranges during RUN is ...

Страница 67: ... device ranges during RUN is supported in FX3G PLCs earlier than Ver 1 10 Ver 8 76E or later Writing in the instruction and device ranges during RUN is supported in FX3G PLCs Ver 1 10 FX PCS WIN 2 Ver 4 00 or later Writing in the instruction and device ranges during RUN is supported in FX1N PLCs Ver 1 00 Item Caution Program memories which can be written in RUN mode Built in EEPROM and optional me...

Страница 68: ...F for executing the instruction for falling edge pulse Instructions for rising edge pulse When write during RUN is completed for a circuit including an instruction for rising edge pulse the instruction for rising edge pulse is executed if a target device of the instruction for rising edge pulse or the operation condition device is ON Target instructions for rising edge pulse LDP ANDP ORP and pulse...

Страница 69: ...ng the built in USB programming port and GX Works2 GX Developer Ver 8 72A or later For GX Developer is prior to Ver 8 72A communication using the built in USB programming port is not available 5 3 1 Installation of USB driver It is necessary to install the USB driver to execute USB communication using the built in USB programming port For the USB driver installation method and procedure refer to t...

Страница 70: ... FX3G Series Setting in GX Developer Ver 8 22Y or later 1 Select Online Transfer setup to open the Transfer setup dialog box 2 Double click Serial in PC side I F to open the PC side I F Serial setting dialog box 3 Select USB GOT Transparent mode 4 Click the OK button to finish the setting GX Developer Ver 8 21X or former GX Developer Ver8 22Y or later 1 When using transparent function by way of US...

Страница 71: ...ecuted Setting in GX Developer Ver 8 22Y or later 1 Select Online Transfer setup to open the Transfer Setup dialog box 2 Double click PLC module in PLC side I F to open the PLC side I F Detailed setting of PLC module dialog box 3 Put a check mark to the check box via GOT F900 transparent mode as shown below 4 Click the OK button to finish the setting GX Developer Ver 8 12N or earlier GX Developer ...

Страница 72: ...on driver and option OS to the version compatible with the FX3G PLC Check the applicability of other items in the GOT manual F940WGOT Not available The following restriction applies when connected Contents of restrictions Programming is enabled only in the function ranges such as instructions device ranges and program sizes available in the FX1N and FX1NC PLCs For applicable models refer to the GO...

Страница 73: ... unit is the AC power supply type Special function block FX2N input output powered extension unit 3 Extension power supply unit 4 Unit No 0 2 1 Extension devices for FX2N FX3U Series Main unit Extension devices for FX2N FX3U Series Range of devices powered from main unit Expansion board 6 FX Series terminal block Configuration of whole system 4 Determination of number of devices to be connected to...

Страница 74: ... data stored in the memory cassette 2 Can be connected in any position however only one device can be connected at one time 3 The memory cassette cannot be connected when the display module is connected to the BD2 1st position 4 Only the BD2 1st position and the BD2 2nd position can be used for connection Only one display module can be connected to the main unit 5 The display module cannot be conn...

Страница 75: ...put Wiring In the case of the main units 14 24 point type 1 Can be connected in either position only one device can be at one time 2 The memory cassette cannot be connected when the display module is connected to the BD 1st position 3 The display module cannot be connected when the memory cassette is connected to the BD 1st position Model name Available connection position BD 1st position BD 2nd p...

Страница 76: ... main unit is the AC power supply type CC Link LT 1 Number of input output points including input output occupied points Up to 128 points Main unit Input output extension unit block Special function block Expansion board Special adapter CC Link master AnyWireASLINK master CC Link LT master CC Link and AnyWireASLINK system 2 Number of remote I O points on CC Link and AnyWireASLINK Up to 128 points ...

Страница 77: ...ons Restrictions in the use of the FX3G 422 BD When connecting a device such as GOT which consumes an internal 5V DC to each of the RS 422 port built in the main unit and the FX3G 422 BD at the same time avoid continuous use of either device If both devices are used continuously their life may be shortened due to heat generation Configuration example 1 RS 422 port built in main unit GT1020LBL 5V D...

Страница 78: ...utput powered extension units blocks calculated in the above step For the remote I O point calculation method refer to the FX2N 64CL M manual 3 Count the number of input output occupied points of special function blocks The number of occupied input output points per unit is 8 The number of occupied input output points of each type of device can be obtained by the following formula or from the list...

Страница 79: ...ep must be 256 or less For details refer to the following subsection 1 FX3U 16CCL M FX2N 16CCL M CC Link master Calculate the number of remote I O points connected on the network in the following step When a CC Link master is used refer to Subsection 6 3 2 2 FX3U 128ASL M AnyWireASLINK master Calculate the number of remote I O points connected on the network in the following step When an AnyWireAS...

Страница 80: ...able on system Number of input output points Total number of input output points A Number of input output points of main unit B Number of input output points of input output powered extension units C Number of input output points of input output extension blocks D Number of remote I O points of FX2N 64CL M E Number of input output points occupied by special function blocks F Number of remote I O s...

Страница 81: ...Maximum number of input output points 256 points Maximum number of points controllable on system Number of input output points Total number of input output points A Number of input output points of main unit B Number of input output points of input output powered extension units C Number of input output points of input output extension blocks D Number of remote I O points of FX2N 64CL M E Number o...

Страница 82: ... when the extension block is connected FX0N 65EC 650mm 25 59 FX0N 30EC 300mm 11 81 Use of expansion board Number of connectable expansion boards Number of connectable special adapters of each type Communication special adapters Analog special adapters When expansion board is not used 0 2 units 2 2 units When expansion board is used 1 unit Communication expansion board 1 unit 2 units FX3G 4EX BD FX...

Страница 83: ...block including the FX2N 8ER ES UL and FX2N 8ER extended to the extension power supply unit does not exceed 32 2 When connecting the input output extension block and special function block Input output extension blocks of up to 16 points can be connected However when the extension power supply unit FX3U 1PSU 5V is used and the main unit is the nearest upstream unit to the extension power supply un...

Страница 84: ...er supply it is necessary to examine again whether extension is possible for all of extension blocks selected in the preceding subsection and extension blocks to be selected in this subsection Note that only up to two network related special function blocks can be connected including extension to the main unit 1 Confirm the priority of all extension blocks to be connected to the main unit The prio...

Страница 85: ... 8 output points are connected the current of the 24V DC service power supply becomes 150mA or less 4 Confirm the current capacity of the 24V DC service power supply from the value shown in the quick reference matrix This remaining power supply capacity current can be used as a power supply for external loads such as sensors special adapters and special function blocks by the user For the current ...

Страница 86: ... Check whether extension from the 24V DC service power supply is possible Check using the quick reference matrix whether 16 input points and 8 output points whose exten sion is judged as impossible in step 2 can be added After 16 input points and 8 output points are connected the remaining current of the 24V DC service power supply is 50mA or less Accordingly it is possible to add 16 input points ...

Страница 87: ...le due to the restriction two special function blocks only the FX3U 64CCL priority 1 and FX2N 2AD priority 1 can be connected to the main unit 3 Check whether extension from the 24V DC service power supply is possible Check using the quick reference matrix whether 8 input points and 16 output points whose exten sion is judged as impossible in step 2 can be added After 8 input points and 16 output ...

Страница 88: ...ut points to be added horizontal axis with the number of output points to be added vertical axis indicates the remaining power supply capacity 1 Select the input output extension block number of points to be connected to the main unit Check that the number of input output points can be added When connecting the FX3U 1PSU 5V extension power supply unit to a system where the nearest upstream unit to...

Страница 89: ... DC service power supply is not provided Example When adding 32 inputs to FX2N 48ER DS a maximum of 24 outputs are expandable 3 AC power supply AC input type 1 FX2N 48ER UA1 UL 24V DC service power supply is not provided Example When adding 24 inputs to FX2N 48ER UA1 UL a maximum of 32 outputs are expandable 310 260 210 160 110 60 10 16 385 335 285 235 185 135 85 35 8 460 410 360 310 260 210 160 1...

Страница 90: ... and special function units blocks are connected by external wiring it is necessary to consider whether they can be covered by the remaining power supply capacity 2 In the case of DC power supply DC input type 24V DC service power supply is not provided 3 In the case of AC power supply AC input type 24V DC service power supply is not provided 3 When the power supply capacity is insufficient connec...

Страница 91: ...pply unit to a system where the nearest upstream unit to the FX3U 1PSU 5V is input output powered extension unit also enter the current consumption and number of occupied I O points for the input extension blocks including FX2N 8ER ES UL and FX2N 8ER that are connected to the FX3U 1PSU 5V 2 A maximum of 8 special function blocks are connectable including the main unit and extension power supply un...

Страница 92: ...ity of 24V DC service power supply and the capacity can be used for external loads 2 Calculate the current consumption of the built in 5V DC power supply If the calculation results for the current consumption of the 24V DC power supply and 5V DC power supply are negative values the current consumption exceeds the capacity of the built in power supply Reconfigure the system adding input output powe...

Страница 93: ...xtension power supply unit is less than 32 2 Enter the specifications for the products to be added Enter the data on the input output extension blocks and special function units blocks to be con nected to the input output powered extension unit and calculate the current For the data on the number of input output occupied points and current consumption of each type refer to Section 6 8 Power supply...

Страница 94: ...Calculate the current consumption of the built in 5V DC power supply 2 Calculate the available current supply from the internal 24V DC power supply 3 Calculate the available input output occupied points excluding the occupied input output by special function blocks If the calculation result for the 5V DC power supply is a negative value the current consumption exceeds the power supply capacity If ...

Страница 95: ... internal 24V DC are supplied via extension cables It is necessary to calculate the current consumption Subtract the current consumption of the internal 24V DC from the 24V DC service power supply The special function units blocks connected to the AC power supply type main unit or to the 24V DC service power supply terminal of the input output powered extension unit consume the external 24V DC Inc...

Страница 96: ...R ES UL 32 16 16 690 250 FX2N 32ET ESS UL FX2N 32ER FX2N 32ES FX2N 32ET FX2N 48ER ES UL 48 24 24 460 FX2N 48ET ESS UL FX2N 48ER FX2N 48ET FX2N 48ER UA1 UL DC power supply type FX2N 48ER DS 48 24 24 690 FX2N 48ET DSS FX2N 48ER D FX2N 48ET D No Type Number of input output points Current consumed mA 5V DC Internal 24V DC Types for addition of input output FX2N 8ER ES UL 16 1 62 5 FX2N 8ER Types for a...

Страница 97: ...D and FX2N 2DA should be less than the following current values Total current consumption of blocks connected to FX2N 32E 190 mA or less Total current consumption of blocks connected to FX2N 48E 300 mA or less 4 The number of input output points set by the rotary switch is added For details refer to FX3U 128ASL M User s Manual 5 This value does not include the supply current to slave modules For d...

Страница 98: ...0 to Y027 Y070 to Y077 Y100 to Y107 2 Unused numbers Note that unused numbers which cause the difference between the number of occupied points and the number of effective points are generated when the following products are used Main units FX3G 14M FX3G 24M FX3G 60M input output extension blocks FX2N 8ER ES UL FX2N 8ER 3 Numbers for added input output unit block To an added input output powered ex...

Страница 99: ...t powered extension units blocks come with an I O number label Apply the I O number label to spaces on the enclosure see the following figure so that the input output numbers can be identified Input output powered extension unit FX2N 32ET Special function block FX2N 16CCL M Connector conversion adapter FX3G CNV ADP Special adapter FX3U 4AD ADP Input output extension block FX2N 8ER Main unit FX3G 2...

Страница 100: ...tor conversion adapter FX3G CNV ADP FX2N CNV BC Expansion boards FX3G 232 BD etc Special adapters FX3U 232ADP MB FX3U 4AD ADP etc Extension power supply unit FX3U 1PSU 5V 7 2 2 Example of assigning Unit numbers are assigned to the special function blocks in the following configuration For assignment of input output numbers refer to Section 7 1 1 Example of configuration 2 Assignment of Unit No Uni...

Страница 101: ...cations 5 Version and Peripheral Devices 6 System Configuration 7 Input Output Nos Unit Nos 8 Installation 9 Preparation and Power Supply Wiring 10 Input Wiring 7 2 3 Application of unit number labels The special function units blocks come with unit number labels Apply the unit number labels to spaces on the enclosure see the following figure so that the unit numbers can be identified No 0 No 7 No...

Страница 102: ...r 2 In the case of main unit 14 24 point type Ch1 is assigned to the communication expansion board FX3G 4EX BD FX3G 2EYT BD FX3G 8AV BD connected to the BD connector or the special communication adapter connected to the connector conversion adapter ch1 Only between the communication expansion board FX3G 4EX BD FX3G 2EYT BD FX3G 8AV BD and the special communication adapter which requires the connec...

Страница 103: ...ut Wiring 7 4 Station No Label of FX3G 485 BD The station No label is packed together with the FX3G 485 BD Place it in a position where it can be seen easily for simple reference as shown in the figure below 7 5 Station No Label of FX3G 485 BD RJ The station No label is packed together with the FX3G 485 BD RJ Place it in a position where it can be seen easily for simple reference as shown in the f...

Страница 104: ...3G 8AV BD 98 FX3G Series Programmable Controllers User s Manual Hardware Edition 7 6 Trimmer Layout Label of FX3G 8AV BD The trimmer layout label is packed together with the FX3G 8AV BD Adhere it in a position where it can be seen easily for quick reference as shown in the figure below ...

Страница 105: ...rvice power supply varies depending on the model and the absence presence of extension blocks If an overload occurs the voltage automatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 4 Note that when an error occurs in a relay triac or transistor output device the output...

Страница 106: ...cause fire equipment failures or malfunctions Be sure to remove the dust proof sheet from the PLC s ventilation port when installation work is completed Failure to do so may cause fire equipment failures or malfunctions Connect the extension cables peripheral device cables input output cables and battery connecting cable securely to their designated connectors Loose connections may cause malfuncti...

Страница 107: ...ailure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Tighten the screws using a Phillips head screwdriver No 2 shaft diameter 6mm 0 24 or less Make sure that the screwdrive...

Страница 108: ...dy and other devices and structure Install the unit as far away as possible from high voltage lines high voltage devices and power equipment Failure to do so may cause fire equipment failures or malfunctions To prevent temperature rise do not install the PLC on a floor or a ceiling or in the vertical direction Install it horizontally on a wall as shown below Arrange the extension cable in such a w...

Страница 109: ...ith extension cable 8 2 Layout in Enclosure The PLC components can be laid out in one stage or in two stages upper and lower The connecting procedures in each case are explained below 8 2 1 1 stage layout FX3G Series main unit FX 2N 16EX FX 2N 16EYT A A A A A 50mm 1 97 Other equipment Other equipment A A A A A Input output powered extension unit A Other equipment A FX3G Series main unit FX 3U 4AD ...

Страница 110: ...h product refer to the external dimensions Extension block Extension block A Special adapter A Input output powered extension units blocks Special function blocks Connector conversion adapter Input output powered extension units 1 For the dimensions of each product refer to the external dimensions Extension cable FX0N 65EC 650mm 25 59 FX0N 30EC 300mm 11 81 Extension block Extension block Extension...

Страница 111: ...d removed The PLC is installed higher by the height of the DIN rail For details on the procedures on mounting and removing the DIN rail refer to Section 8 4 2 Direct installing with screws The PLC can be installed directly in the enclosure with M4 screws For the mounting hole pitch refer to Section 8 5 8 3 2 Cautions on examining installing method Refer to Section 8 2 1 Cautions when FX3U 4LC or F...

Страница 112: ...ion devices connected with the extension cable can be installed directly in the enclosure 1 FX2N CNV BC can be installed directly in the enclosure but cannot be installed on the DIN rail FX3G Series main unit Extension cable FX0N 65EC FX0N 30EC FX2N CNV BC FX2N 16EX FX2N 16EX FX2N 16EX FX2N 64CL M 1 to 2mm 0 04 to 0 08 1 to 2mm 0 04 to 0 08 indicates an M4 screw indicates an M4 screw FX3G Series m...

Страница 113: ...nversion adapter FX3G CNV ADP on the main unit before installing the main unit to the enclosure Mount the input output powered extension units blocks and the special function blocks in the enclosure after installing the main unit in the enclosure The expansion boards memory cassette and the display module can be fitted to the main unit after it is installed The battery can be replaced while the ma...

Страница 114: ...e installing a special adapter or connector conversion adapter on the enclosure For the connection procedure refer to Subsection 8 6 3 and Subsection 8 6 4 1 Push out all DIN rail mounting hooks A in the right figure 2 Fit the upper edge of the DIN rail mounting groove B in the right figure onto the DIN rail 3 Lock the DIN rail mounting hooks C in the following figure while pressing the PLC agains...

Страница 115: ...n unit block and special function block 1 Push out the DIN rail mounting hook A in the right fig ure of the input output extension block For input output powered extension units 8 point type input output extension blocks except for the FX2N 8EYR S ES UL and special extension units blocks this operation is unnecessary 2 Fit the upper edge of the DIN rail mounting groove B in the right figure onto t...

Страница 116: ...les and the con necting cables including expansion board and special adapters 4 Insert the tip of a flathead screwdriver into the hole of the DIN rail mounting hook C in the right figure This step also applies for the DIN rail mounting hooks of the special adapters 5 Move the flathead screwdriver as shown in the right figure to draw out the DIN rail mounting hooks of all devices 6 Remove the produ...

Страница 117: ...ing The product mounting hole pitches are shown below For the pitch that varies depending on the product refer to the table 1 Main unit A Unit mm inches 2 Special adapter B Unit mm inches Model name Mounting hole pitch W A FX3G 14MR ES 82 3 23 FX3G 14MT ES FX3G 14MT ESS FX3G 14MR DS FX3G 14MT DS FX3G 14MT DSS FX3G 24MR ES FX3G 24MT ES FX3G 24MT ESS FX3G 24MR DS FX3G 24MT DS FX3G 24MT DSS FX3G 40MR...

Страница 118: ... 48ET ESS UL FX2N 48ER FX2N 48ET FX2N 48ER DS FX2N 48ET DSS FX2N 48ER D FX2N 48ET D 172 6 78 FX2N 48ER UA1 UL 210 8 27 Model name Mounting hole pitch W E FX2N 8ER ES UL FX2N 8ER FX2N 8EX ES UL FX2N 8EX FX2N 8EX UA1 UL FX2N 8EYR ES UL FX2N 8EYT ESS UL FX2N 8EYR FX2N 8EYT FX2N 8EYT H 39 1 54 F FX2N 8EYR S ES UL FX2N 16EX ES UL FX2N 16EX FX2N 16EX C FX2N 16EXL C FX2N 16EYR ES UL FX2N 16EYR FX2N 16EYT...

Страница 119: ...ch W G FX3U 128ASL M FX3U 32DP FX2N 2AD FX2N 2DA FX2N 64CL M FX2N 32CCL 39 1 54 FX3U 4AD FX3U 4DA FX2N 4AD FX2N 4DA FX2N 4AD PT FX2N 4AD TC FX2N 5A FX2N 2LC FX3U 16CCL M FX3U 64CCL FX3U 1PSU 5V 51 2 01 H FX2N 16CCL M Refer to the figure shown left I FX2N 20PSU 52 2 05 FX2N 8AD 67 2 64 J FX3U 4LC Refer to the figure shown left 4 0 16 W 80 3 15 G 90 3 55 I 98 3 86 4 0 16 4 0 16 W 105 4 14 H 75 2 96 ...

Страница 120: ... special function block 1 Make mounting holes in the mounting surface according to the external dimensions diagram 2 Push in the DIN rail mounting hook A in the right figure of the input output extension block If the DIN rail mounting hook is not pushed in the screw hole is covered and the block cannot be mounted For input output powered extension units 8 point type input output extension blocks e...

Страница 121: ...cting method varies depending on the combination of the products i e the main unit expansion board special adapters input output extension blocks and special function blocks The connecting methods are explained with the following configuration examples Example of configuration Extension cable FX0N 65EC FX0N 30EC Special adapter FX3G Series main unit FX CNV BC FX2N Series Input output powered exten...

Страница 122: ... front face of the main unit 2 Attach the provided side cover B in the right figure as shown in the right figure Caution Attachment of the side cover is not necessary when connecting the expansion board only under the top cover S of a 40 60 point type main unit FX3G 4EX BD FX3G 2EYT BD FX3G 8AV BD cannot attach in the top cover S side of a main unit 3 Connect the expansion board to the option conn...

Страница 123: ... example 1 Remove the top cover A in the right figure and peripheral device connector cover B in the right figure from the front face of the main unit Caution The peripheral device connector cover has the possibility of being damaged when removed Please remove by pressing on the attaching tab a in the figure to the right 2 Attach the provided side cover C in the right figure as shown in the right ...

Страница 124: ...igure from the front face of the main unit Caution The peripheral device connector cover has the possibility of being damaged when removed Please remove by pressing on the attaching tab a in the figure to the right 2 Connect the connector conversion adapter to the option connector C in the right figure as shown in the right figure and fix it with provided M3 tapping screws D in the right figure Ti...

Страница 125: ...wing steps 2 Connect the special adapter B in the right figure to the connector conversion adapter as shown in the right figure 3 Slide the special adapter connecting hooks A in the right figure of the connector conversion adapter to secure the special adapter B in the right figure Caution When using the FX3U ENET ADP connect it to the last adapter position leftmost position 8 6 5 Connecting metho...

Страница 126: ...ted connect the unit to be added right side and the existing unit left side with the supplied extension cable 3 Fit the top cover B in the above figure 8 6 7 Connecting method F connection of extension cable and FX2N CNV BC This subsection explains the procedures for connecting an extension cable and FX2N CNV BC to the extension cable of the powered extension unit block 1 Separate the case of FX2N...

Страница 127: ...f the extension cable supplied B in the right figure to the extension connector of the input output powered extension unit to be added 4 Fit the top cover A in the right figure 8 6 9 Connecting method H connection of extension block to input output powered extension unit This subsection explains the procedures for connecting an extension block to an input output powered extension unit 1 Remove the...

Страница 128: ...off External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 4 Note that when an error occurs in a relay triac or transistor output device the output could be held either on or off For output signals that may lead to serious accidents external circuits and mechanisms should be designed to ensure safe machinery operation in such a case To maintain the sa...

Страница 129: ...ng precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Tighten the screws using a Phillips head screwdriver No 2 shaft diameter 6mm 0 24 or less Make sure tha...

Страница 130: ...nals For a type 24V DC input type common to sink source input select sink or source input by the fol lowing connection In the case of AC power supply type For sink input connect the 24V and S S terminals For source input connect the 0V and S S terminals In the case of DC power supply type For sink input connect the and S S terminals For source input connect the and S S terminals Connect sensors an...

Страница 131: ...al block is used 1 Applicable products 2 Terminal block screw size and tightening torque The size of the terminal screws for each product is shown below For the solderless terminals refer to the following page Product type Model name Main unit All models of FX3G Series main units Input output powered extension unit All models of FX2N Series input output powered extension units Input output extensi...

Страница 132: ...VD directive EN61010 2 201 2013 of the EC directive avoid the wiring with two wires to the built in terminal and take an appropriate action such as adding an external terminal For the time of compliance with the LVD directive EN61010 2 201 2013 refer to Requirement for Compliance with LVD directive Terminal manufacturer Type No Applicable cable Certification Pressure bonding tool J S T Mfg Co Ltd ...

Страница 133: ...6 System Configuration 7 Input Output Nos Unit Nos 8 Installation 9 Preparation and Power Supply Wiring 10 Input Wiring In the case of M3 5 terminal screw When one wire is connected to one terminal When two wires are connected to one terminal 6 8mm 0 27 or less 3 7 0 15 Terminal Terminal Terminal screw Crimp terminal 6 8mm 0 27 or less 3 7 0 15 6 8mm 0 27 or less 3 7 0 15 6 0mm 0 24 or more Termin...

Страница 134: ...side A 20 pin connector FX 16E 150CAB 1 5m 4 11 Cables for connecting FX Series terminal block and input output connector For the connection with FX Series terminal block refer to the following chapter 20 Terminal Block Flat cables with tube A 20 pin connector at both ends FX 16E 300CAB 3m 9 10 FX 16E 500CAB 5m 10 4 FX 16E 150CAB R 1 5m 4 11 Round multicore cables A 20 pin connector at both ends F...

Страница 135: ...PFOX ZA 3 4 Old model name CRIMPFOX UD 6 4 Tool For tightening the terminal use a commercially available small screwdriver having a straight form that is not widened toward the end as shown right Note If the diameter of screwdriver grip is too small tightening torque will not be able to be achieved To achieve the appropriate tightening torque shown in the table above use the following screwdriver ...

Страница 136: ... plate the end of the cable 3 Tightening torque Set the tightening torque to 0 5 to 0 6 N m Do not tighten terminal screws with a torque outside the above mentioned range Failure to do so may cause equipment failures or malfunctions Caution When tightening a grounding terminal use a screwdriver suitable for the terminal screw The screwdriver which does not suit the thread groove is used tightening...

Страница 137: ...cable so that loose wires will not stick out Do not solder plate the end of the cable 3 Tightening torque Set the tightening torque to 0 4 to 0 5 N m Do not tighten terminal screws with a torque outside the above mentioned range Failure to do so may cause equipment failures or malfunctions Caution When tightening a grounding terminal use a screwdriver suitable for the terminal screw The screwdrive...

Страница 138: ... below Extension devices of PLC except expansion board and special adapter Use ground wires thicker than AWG14 2 mm2 Position the grounding point as close to the PLC as possible to decrease the length of the ground wire PLC Other equipment PLC Other equipment PLC Other equipment Shared grounding Good condition Common grounding Not allowed Independent grounding Best condition Expansion board Input ...

Страница 139: ... output terminals As for the details of emergency stop see DESIGN PRECAUTIONS at Safety Precautions field Class D grounding X0 S S 0V 24V Main unit N L X1 5V 0V 24V Input impedance X7 Fuse Y0 COM0 Y2 Input extension block S S 3 X0 COM2 AC power supply of 100 to 240V PL Power ON Emergency stop MC MC MC MC 0V 24V 1 S S 0V 24V 24V 0V Load 5V 0V 24V 1 Connect the AC power supply to the L and N termina...

Страница 140: ...When turning OFF the power confirm the safety of the system and then turn OFF the power of the PLC including special extension equipment at the same time 6 The 24V and 0V terminals are located on the output terminal side For details on the terminal layout refer to Section 4 7 7 When turning OFF the power confirm the safety of the system and then turn OFF the power of the PLC including special exte...

Страница 141: ...the 24V terminals 24V DC service power supply of the main unit and the input output extension unit with each other Connect the 0V terminal Some special extension units blocks do not have power terminals When using an external power supply turn it ON at the same time with the extension unit or earlier than the extension unit When turning OFF the power confirm the safety of the system and then turn ...

Страница 142: ...rning OFF the power confirm the safety of the system and then turn OFF the power of the PLC including special extension equipment at the same time S S L N 0V Special adapter 24 24 Class D grounding PL Power supply ON Emergency stop MC MC MC MC DC power supply Power supply for loads to be connected to PLC output terminals As for the details of emergency stop operation see DESIGN PRECAUTIONS at Safe...

Страница 143: ... have the power supply terminals When using an external power supply turn it ON at the same time with the extension power supply unit or earlier than the extension power supply unit When turning OFF the power confirm the safety of the system and then turn OFF the power of the PLC including special extension equipment at the same time 4 AC power supply of 100 to 240V S S L N 0V Special adapter 24 2...

Страница 144: ...ce input type Power supply for loads to be connected to PLC output terminals As for the details of emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field Output extension block Special function block Input extension block Special function block Input extension block Sink and source input type Sink input type Connect DC power to and terminals The same power source for the main ...

Страница 145: ... source input type Sink and source input type As for the details of emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field Connect DC power to and terminals The same power source for the main unit extension units special function unit blocks and special adapters is preferable When using the different power source from the main unit turn ON the peripheral devices power simultan...

Страница 146: ...sms should be designed to ensure safe machinery operation in such a case 4 Note that when an error occurs in a relay triac or transistor output device the output could be held either on or off For output signals that may lead to serious accidents external circuits and mechanisms should be designed to ensure safe machinery operation in such a case To maintain the safety of the programmable controll...

Страница 147: ...ailure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Tighten the screws using a Phillips head screwdriver No 2 shaft diameter 6mm 0 24 or less Make sure that the screwdrive...

Страница 148: ...en collector transistor output can be used Source input common Source input means a DC input signal with current flow into the input X terminal When a sensor with a transistor output is connected PNP open collector transistor output can be used 2 Method of switching between sink source input To switch the input type to sink or source input wire the S S terminal to the 0V or 24V or terminal In the ...

Страница 149: ...t extension blocks is determined based upon the selection of the sink or source input mode of the main unit or powered extension unit power source Cautions when selecting a model Sink source input type and sink input type only unit models are both available Select the proper type for the application Differences from FX1N PLCs in input specifications reference Sink input type only FX1N PLCs manuals...

Страница 150: ...main unit 1 of the main unit can be used as RUN input terminals by setting parameters 1 X000 to X007 in the FX3G 14M main unit and X000 to X015 in the FX3G 24M main unit For the functions of the RUN terminals refer to Subsection 14 2 1 2 Input circuit Function of input circuit The primary and secondary circuits for input are insulated with a photocoupler and the second circuit is provided with a C...

Страница 151: ...e input devices applicable to this minute current If no voltage contacts switches for large current are used contact failure may occur Example Products of OMRON 2 In the case of input device with built in series diode The voltage drop of the series diode should be approx 4V or less For example when lead switches with a series LED are used up to two switches can be connected in series Also make sur...

Страница 152: ...e leakage current I is 1 5 mA or less when the switch is off When the current is larger than 1 5mA connect a bleeder resistance Rb k determined by the following formula as shown in the following figure Rb 4Rp 15 Rp k PLC source input X 24V Rp Rb PLC sink input X 0V Rp Bleeder resistance Rb 15k or more 1 24V S S S S 0V 1 In the case of a type only for sink input connect the device to the COM termin...

Страница 153: ...block 5V 0V 24V 1 Handle the power supply circuit correctly in accordance with Chapter 9 Preparation for Wiring and Power Supply Wiring Procedures 2 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required 3 In the case of sink input wiring short circuit the terminals of the extension units as well as the S S terminal and the 24V terminal...

Страница 154: ...roximity sensor 24V 0V Sink and source input type Sink input type 1 Handle the power supply circuit correctly in accordance with Chapter 9 Preparation for Wiring and Power Supply Wiring Procedures 2 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required 3 In the case of sink input wiring short circuit the S S terminal and the 24V termin...

Страница 155: ...block 5V 0V 24V Fuse Class D grounding Input impedance Input terminal Input terminal Input terminal Three wire sensor Input terminal 2 Two wire proximity sensor 0V 0V 24V 24V 1 Handle the power supply circuit correctly in accordance with Chapter 9 Preparation for Wiring and Power Supply Wiring Procedures 2 For an input device having a parallel resistance or a two wire proximity switch a bleeder re...

Страница 156: ...pe Sink and source input type Three wire sensor Two wire proximity sensor Class D grounding Input impedance Input terminal Input terminal Input terminal Input terminal Handle the power supply circuit correctly in accordance with Chapter 9 Preparation for Wiring and Power Supply Wiring Procedures For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance ma...

Страница 157: ...t extension block 5V 0V 24V 5V 0V 24V Fuse 5V 0V 24V 5V 0V 24V Input impedance 1 2 Sink input type Use of input output extension units blocks of sink input type Class D grounding 3 4 Sink and source input type Three wire sensor Two wire proximity sensor Input terminal Input terminal Input terminal Input terminal Handle the power supply circuit correctly in accordance with Chapter 9 Preparation for...

Страница 158: ...ut terminal Input terminal Three wire sensor Input terminal 1 2 Two wire proximity sensor 1 2 3 4 Sink and source input type Class D grounding 4 3 3 Handle the power supply circuit correctly in accordance with Chapter 9 Preparation for Wiring and Power Supply Wiring Procedures For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required In th...

Страница 159: ... Input 1 Input terminal When voltage of 100 to 120V AC is applied between the input terminal and COM terminal the input terminal is turned on The input display LED lights Do not connect the COM terminal of an AC input type input output powered extension unit block with the COM terminal of a DC system 2 Input circuit The primary input circuit and the secondary input circuit are insulated with a pho...

Страница 160: ...required 3 Do not take input signals from loads generating surge 24V DC input type Sink wiring X000 S S 0V 24V Main unit N L X001 X0 S S X1 Input extension block X0 Input output powered extension unit FX2N 48ER UA1 UL N L X1 5V 0V 24V Fuse Class D grounding Input impedance Input terminal Input terminal Input terminal 1 2 24V 0V Two wire proximity sensor COM COM 100V AC input type Three wire sensor...

Страница 161: ...002 and X005 For details on programming refer to the programming manual 10 4 1 Allocation of pointers to input numbers input signal ON OFF duration 10 4 2 Cautions for input interruption 1 Non overlap of input numbers The input terminals X000 to X005 can be used for high speed counter input interruption pulse catch SPD ZRN and DSZR instructions and general purpose inputs Take care not to overlap t...

Страница 162: ...ing using X000 When another input terminal is used wire it according to the following diagrams 1 When 24V DC service power supply is used 2 When 24V DC external power supply is used S S L N 24V Class D grounding Fuse Sink wiring 0V X000 Three wire S S L N 24V Fuse Source wiring 0V X000 Three wire The grounding resistance should be 100Ω or less Class D grounding S S L N 24V Fuse 24V DC Sink wiring ...

Страница 163: ... For details on programming refer to the programming manual 10 5 1 Allocation of special memories to input numbers ON duration of input signals 10 5 2 Cautions for pulse catch 1 Non overlap of input numbers The input terminals X000 to X005 can be used for high speed counter input interruption pulse catch speed detection SPD instructions and general purpose input Take care not to overlap the input ...

Страница 164: ... X000 When another input terminal is used wire it according to the following diagrams 1 When 24V DC service power supply is used 2 When 24V DC external power supply is used S S L N 24V Class D grounding Fuse Sink wiring 0V X000 Three wire S S L N 24V Fuse Source wiring 0V X000 Three wire The grounding resistance should be 100Ω or less Class D grounding S S L N 24V Fuse 24V DC Sink wiring 0V X000 S...

Страница 165: ...t function 1 Non overlap of input numbers The input terminals X000 X001 X003 and X004 can be used for high speed counter input interruption pulse catch speed detection SPD instructions and general purpose input Take care not to overlap the input numbers However overlap of input numbers is allowed for input interruptions 2 When the pulse width period measurement function and high speed counters are...

Страница 166: ...dth measurement wiring using X000 When another input terminal is used wire it according to the following diagrams 1 When 24V DC service power supply is used 2 When 24V DC external power supply is used S S L N 24V Class D grounding Fuse Sink wiring 0V X000 Three wire S S L N 24V Fuse Source wiring 0V X000 Three wire The grounding resistance should be 100Ω or less Class D grounding S S L N 24V Fuse ...

Страница 167: ...ations The input terminal assignments for FX3G PLC high speed counters can be switched when used in combination with a special auxiliary relay This section classifies these high speed counter devices under the following notations Note that an OP input cannot be programmed 11 2 3 Cautions in connecting mating device Encoders with the output forms in the following table can be connected to the input...

Страница 168: ...frequency refer to Section 11 7 Counter type Device No counter Response Frequency 1 kHz Data length External reset input terminal External start input terminal 1 phase 1 count input C235 60 32 bit bi directional counter None None C236 C237 10 C238 60 C239 C240 10 C241 60 Provided None C242 10 C243 C244 Provided Provided C245 1 phase 2 count input C246 C248 OP 60 32 bit bi directional counter None ...

Страница 169: ...own count input A A phase input B B phase input R External reset input S External start input 1 When a special auxiliary relay is driven in a program the input terminals and their associated functions are switched For the function switching method refer to Subsection 11 9 2 11 4 2 Restriction of redundant use of input numbers The input terminals X000 to X007 can be used for high speed counters inp...

Страница 170: ...or this example is the data of the indirectly designated data register D1 D0 C244 can be reset by X011 on the sequence For C244 X001 is allocated as the external reset input The counter resets immediately when X001 turns on The counters C235 to C245 switch to the down count or up count mode by turning on or off M8235 to M8245 Example of operation The above counter C235 operates as shown below X000...

Страница 171: ...ters are backed up kept even if the power is turned off 11 5 2 1 phase 2 count input These counters are 32 bit up count down count binary counters The operations of the output contact according to the current value are the same as those of the above mentioned 1 phase 1 count input high speed counters Examples of program 1 For C246 While X012 is on C246 increments the value when the input terminal ...

Страница 172: ... terminal X006 is turned on while X012 is on The count input terminals are X000 A phase and X001 B phase C254 is reset by X011 on the sequence and it is reset immediately when X002 is turned on When the current value exceeds the setting D1 D0 Y004 operates and when the current value becomes lower than the setting Y004 turns off Y005 turns on down count or off up count according to the counting dir...

Страница 173: ...s only when high speed processing is not required because these instructions are processed in the operation cycle of the PLC and operation delay is generated before the comparison output result is obtained Use the comparison instructions for high speed counters HSCS HSCR and HSZ described below if it is necessary to execute comparison and change the output contact Y at the same time when the curre...

Страница 174: ...s related to positioning DRVI instruction Y000 and DRVA instruction Y001 are used Overall frequency 200kHz 2 axes x 40kHz 120kHz Example2 When HSCS HSCR or HSZ instruction is not used and instructions related to positioning DRVI instruction Y000 are used Number of pulse width cycle measurement inputs X003 Overall frequency 200 kHz 1 axes 1 input x 40 kHz 120 kHz Counter type Response Frequency Ove...

Страница 175: ...f wiring apply to the cases where C235 is used When another high speed counter number is used wire the counter referring to the following diagrams It is recommended to use shielded twisted pair cables for connection cables Ground the shield of each shielded cable only on the PLC side 1 NPN open collector transistor output rotary encoder 2 PNP open collector transistor output rotary encoder The gro...

Страница 176: ... shielded twisted pair cables for connection cables Ground the shield of each shielded cable only on the PLC side 1 NPN open collector transistor output rotary encoder 2 PNP open collector transistor output rotary encoder The grounding resistance should be 100Ω or less PLC S S L N 24V 0V 24V Rotary encoder Class D grounding Fuse 24V DC In the case of sink wiring 0V X000 X001 Phase A Phase B Phase ...

Страница 177: ...of 1 phase 2 count input and 2 phase 2 count input counters 3 For switching high speed counter function Counter type Counter No Specifying device Up counting Down counting 1 phase 1 count input C235 M8235 OFF ON C236 M8236 C237 M8237 C238 M8238 C239 M8239 C240 M8240 C241 M8241 C242 M8242 C243 M8243 C244 M8244 C245 M8245 Counter type Counter No Monitoring device OFF ON 1 phase 2 count input C246 M8...

Страница 178: ...t relays not being used for high speed counters remains at 10 ms initial value The inputs X000 to X007 are used for high speed counters input interrupt pulse catch SPD DSZR ZRN instructions and general purpose inputs There should be no overlap between each input number Make sure that the signal speed for high speed counters does not exceed the response frequency described above If an input signal ...

Страница 179: ... an overload occurs the voltage automatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 4 Note that when an error occurs in a relay triac or transistor output device the output could be held either on or off For output signals that may lead to serious accidents external c...

Страница 180: ...he product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Tighten the screws using a Phillips head screwdriver No 2 shaft diameter 6mm 0 24 or less Make sure that the screwdriver does not touch the partition part of the terminal block Make sure to properly wire to the terminal block European t...

Страница 181: ...wer supply of 30V DC or less or 240V AC or less 250V AC or less when the unit does not comply with CE UL or cUL standards for loads 3 Circuit insulation The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and contact The common terminal blocks are separated from one another 4 Display of operation When power is applied to the output relay coi...

Страница 182: ...ge absorber combined CR components such as a surge killer and spark killer etc parallel to the load Select the rated voltage of a surge absorber that is suitable for the load being used Refer to the table below for other specifications Reference 3 Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external interlock ...

Страница 183: ... product Output extension block relay output Y0 COM1 Y7 Y0 COM2 Y7 Y0 COM5 Y7 Y0 COM1 Y1 Y2 Y3 AC power supply 100 to 240V PL Power ON Emergency stop MC MC MC MC DC power supply Power supply for load connected to PLC output For details on emergency stop operation refer to DESIGN PRECAUTIONS at Safety Precautions field Load Load Load Load Input output powered extension unit relay output Fuse 1 Fuse...

Страница 184: ...specifications on the input output powered extension unit refer to Chapter 15 For the specifications on the input output extension block refer to Chapter 16 12 2 1 Transistor Output Sink and Source FX3G Series main units FX2N Series input output extension units blocks of transistor sink output type and of transistor source output type are available 1 Differences in circuit Sink output common Outpu...

Страница 185: ...erminals are not connected internally Source output Connect each V number terminal to the plus side of the load power supply The V terminals are not connected internally 2 External power supply For driving the load use a smoothing power supply of 5 30 V DC that can output current two or more times the rated current of the fuse connected to the load circuit 3 Insulation of circuit The internal circ...

Страница 186: ... train output or positioning make sure to set the load current to 10 to 100mA 5 24 V DC Y002 or more 0 2ms or less 24V DC 200 mA or more 1 Main unit 40 60 point type Y000 to Y002 5 s or less 5 24 V DC 10mA or more When using an instruction related to pulse train output or positioning make sure to set the load current to 10 to 100mA 5 24 V DC Y003 or more 0 2ms or less 24V DC 200mA or more 1 Input ...

Страница 187: ...larger than the total rated fuse capacity 2 Contact protection circuit for inductive loads When an inductive load is connected connect a diode for commutation in parallel with the load as necessary The diode for commutation must comply with the following specifications 3 Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneousl...

Страница 188: ...C MC MC DC power supply Power supply for load connected to PLC output For details on emergency stop operation refer to DESIGN PRECAUTIONS at Safety Precautions field Load Load Load The output circuit of this PLC does not have a built in fuse Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by output element fracture due to load short circuiting repre...

Страница 189: ...duct Y0 V0 Y7 Y0 V1 Y7 Y0 V0 Y7 Y0 V1 Y7 PL Power ON Emergency stop MC MC MC MC DC power supply Power supply for load connected PLC output For details on emergency stop operation refer to DESIGN PRECAUTIONS at Safety Precautions field Load Load Load Load 1 The output circuit of this PLC does not have a built in fuse Provide a fuse suitable to each load to prevent blowout of the wires on the circui...

Страница 190: ...nse time The time from when the photo thyristor is driven or shut down until the output triac is turned on and until it is turned off is 1ms or less and 10ms or less respectively 5 Output current The max current per output point is 0 3A However to restrict temperature rise the max current per one output from four points should be 0 8A average per point is 0 2A When a load with high rush current is...

Страница 191: ...When connecting a very low current load of 0 4VA 100V AC or less or 1 6VA 200V AC or less please connect a surge absorber parallel to the load Select the rated voltage of a surge absorber that is suitable for the load being used Refer to the table below for other specifications Reference 3 Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switch...

Страница 192: ...MC MC MC MC Power supply for load connected to PLC output For details on emergency stop operation refer to DESIGN PRECAUTIONS at Safety Precautions field Load Load Fuse 1 Output extension block triac output Input output powered extension unit triac output AC power supply 100 to 240V Breaker 2 2 The output circuit of this PLC does not have a built in fuse Provide a fuse suitable to each load to pre...

Страница 193: ...n blocks If an overload occurs the voltage automatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 4 Note that when an error occurs in a relay triac or transistor output device the output could be held either on or off For output signals that may lead to serious accidents...

Страница 194: ...oles or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Make sure to properly wire the FX3G Series main unit and FX2N FX3U Series extension equipment in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or da...

Страница 195: ... capturing values from a 4 digit digital switch to the data register D100 are given below 1 Main unit Example of program Example of wiring 1 In the case of sink wiring When inputs are used for both sink and source and outputs are the transistor sink type in the used main unit 2 In the case of source wiring When inputs are used for both sink and source and outputs are the transistor source type in ...

Страница 196: ...haded areas are provided on input output powered extension units ex FX2N 32ET Output extension blocks donot have the terminals 1 2 Digital switch of BCD 1 2 4 8 103 102 101 100 X010 X011 X012 X013 24V 0V S S Y030 Y031 Y032 Y033 Transistor output sink 24 COM COM1 X 103 102 101 100 Input output powered extension unit Output extension block 0 1A 50V diode is necessary Main unit 1 2 4 8 103 102 101 10...

Страница 197: ...ly and outputs are the transistor sink type in the used input output powered extension unit 2 In the case of source wiring When inputs are used for both sink and source and outputs are the transistor source type in the used extension unit M8000 X060 Y050 D100 K1 DSW First input group 0 1A 50V diode is necessary Digital switch of BCD Input output powered extension unit FX2N 32ET FX2N 48ET COM COM1 ...

Страница 198: ...it or input output powered extension unit 2 In the case of sink wiring When inputs are used for sink only in the used input output powered extension unit 3 In the case of source wiring When inputs are used for both sink and source in the used main unit or input output powered extension unit M8000 K2X010 D102 BIN X010 X011 X012 X013 X015 X014 X016 X017 1 2 4 8 1 2 4 8 101 100 S S Main unit Input ou...

Страница 199: ...the case of sink wiring When inputs are used for both sink and source and outputs are the transistor sink type in the used main unit 2 In the case of source wiring When inputs are used for both sink and source and outputs are the transistor source type in the used main unit M8000 X020 Y010 M30 K3 MTR Main unit Ex FX3G 40MT ES X020 X021 X022 X023 24V 0V S S Y010 Y011 Y012 COM4 X024 X025 X026 X027 M...

Страница 200: ...nits ex FX2N 32ET Output extension blocks do not have the terminals X020 X021 X022 X023 24V 0V S S Main unit Y050 Y051 Y052 24 COM COM1 X X024 X025 X026 X027 M30 M31 M32 M33 M34 M35 M36 M37 M40 M41 M42 M43 M44 M45 M46 M47 M50 M51 M52 M53 M54 M55 M56 M57 X021 X022 X023 X024 X025 X026 X027 X021 X022 X023 X024 X025 X026 X027 Input output powered extension unit block X020 X021 X022 X023 24V 0V S S Mai...

Страница 201: ...ring When inputs are used for both sink and source and outputs are the transistor source type in the used extension unit M8000 X060 Y050 M30 K3 MTR Transistor output sink FX2N 32ET FX2N 48ET Input output powered extension unit 0 1A 50V diode is necessary COM X060 COM1 X061 X062 X063 X064 X065 X066 X067 Y050 Y051 Y052 Y053 Y054 Y055 Y056 Y057 M30 M31 M32 M33 M34 M35 M36 M37 M40 M41 M42 M43 M44 M45 ...

Страница 202: ...rce wiring When inputs are used for both sink and source and outputs are the transistor source type in the used main unit M8000 D100 Y010 K1 SEGL Use a 7 segment display with a latch and a built in BCD decoder 103 102 101 100 1 2 4 8 103 102 101 100 1 2 4 Y011 Y010 Y012 Y013 COM5 Y014 Y015 Y016 Y017 8 COM4 Transistor output sink Main unit Ex FX3G 40MT ES Signal Internal circuit 7 segment display Y...

Страница 203: ...e of source wiring When inputs are used for both sink and source and outputs are the transistor source type in the used extension unit M8000 D100 Y020 K1 SEGL Use a 7 segment display with a latch and a built in BCD decoder Signal Internal circuit 7 segment display Y COM1 PLC 7 segment display to be used for sink wiring in the case of transistor output Input output powered extension unit FX2N 32ET ...

Страница 204: ...in the used main unit 2 In the case of source wiring When inputs are used for both sink and source and outputs are the transistor source type in the used main unit M8000 D100 K2Y010 BCD Transistor output sink Main unit Ex FX3G 40MT ES Signal Internal circuit 7 segment display Y COM1 PLC 7 segment display to be used for sink wiring in the case of transistor output Y010 COM4 Y011 Y012 Y013 Y014 Y015...

Страница 205: ...transistor sink type in the used input output powered extension unit 2 In the case of source wiring When inputs are used for both sink and source and outputs are the transistor source type in the used extension unit M8000 D100 K2Y020 BCD Signal Internal circuit 7 segment display Y COM1 PLC 7 segment display to be used for sink wiring in the case of transistor output Input output powered extension ...

Страница 206: ...ette is attached or detached while the PLC s power is on the data in the memory may be destroyed or the memory cassette may be damaged Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative Turn off the power to the PLC before connecting or disconnecting any extension cable Failure to do so ma...

Страница 207: ...en the cable and the main unit 2 For continuous use of a peripheral device such as GOT Cut off the area shown in the left figure below of the peripheral device connector cover main unit using a nipper etc and connect the peripheral device as shown in the right figure below Notes The dielectric withstand voltage and insulation resistance test of the PLC should be measured in accordance with the fol...

Страница 208: ...hown in the left figure below of the connector conversion adapter using a nipper etc and connect the peripheral device as shown in the right figure below 14 1 3 Connection to built in programming connector USB Connect and disconnect the communication cable for the peripheral device personal computer At connection confirm the cable and connector shape Communication cable Connection example Cut off ...

Страница 209: ...ircuit errors and grammatical errors with the program check function of the program ming tool 3 Transfer the sequence program Write the program to the PLC with the programming tool When the memory cassette is used Make sure to set the PROTECT switch of the memory cassette to OFF shown right For details on handling of the memory cassette refer to Chapter 21 4 Verify the sequence program Verify that...

Страница 210: ...igure below When the specified input terminal is turned on the PLC starts When it is turned off the PLC is started or stopped depending on the state of the built in RUN STOP switch 1 X000 to X007 in 14 point type main units and X000 to X015 in 24 point type main units For details refer to Kinds of Parameters and Settings in Programming Manual Operation with two switches RUN and STOP The PLC can be...

Страница 211: ...STOP switch and the general purpose RUN terminal are used without remote running stopping operation from the programming software The RUN STOP status of the PLC is determined by the conditions shown in the following table Use either built in RUN STOP switch or the general input specified as RUN terminal When specifying the general purpose terminal as the RUN terminal always set the built in RUN ST...

Страница 212: ...ining circuit The operation to forcibly turn on timers is effective only when the timers are driven by the program The results of forcible ON OFF operation performed while the PLC in the stopped state or performed for devices not used in the program are retained However the results of the operation performed for the input relays X are not retained because the relays refresh input even while the PL...

Страница 213: ...riable analog potentiometer is turned clockwise The current value of each variable analog potentiometer is stored in special data registers shown below 1 Use example 1 of variable analog potentiometer The current value of VR1 is used as the set value of a timer 2 Use example 2 of variable analog potentiometer The current value of VR2 multiplied by 10 is used as the set value of a timer Item In run...

Страница 214: ...y check the following points Check that the temperature in the panel is not abnormally increased by other heat generating bodies or direct sunlight Check that dust or conductive dust has not entered the panel Check for loosening of wiring and other abnormalities 3 Battery Replacement When the battery voltage drops while the PLC power is on the ALM LED on the panel is lit in red and M8005 and M8006...

Страница 215: ...ves is 500 000 operations at 20VA The following table shows the approximate life of a relay based on the results of an operation life test Test condition 1 sec ON 1 sec OFF 2 FX Series terminal blocks For the applicable models refer to Chapter 3 The standard life of contacts used for Inductive loads such as contactors and solenoid valves is 500 000 operations at 35VA The following table shows the ...

Страница 216: ...ent 20 to 40 times the stationary current Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load Capacitive loads such as capacitors may be present in electronic circuit loads including inverters About the maximum load specifications of the resistance load refer to the specification for each model For specifications on the main unit refer...

Страница 217: ...oblems may have occurred Power of the specified voltage and current is not being supplied to the power supply terminal External wiring is incorrect Internal error of PLC Check the supply voltage After disconnecting the cables other than the power cable re apply power to the PLC and check for changes in the state If the problem persists consult your local Mitsubishi Electric representative Off One ...

Страница 218: ...several times in one scan Change the setting of the watchdog timer Change the watchdog timer setting D8000 in the program so that the setting is larger than the maximum value of the scan time D8012 2 Remove the PLC and supply power to it from another power supply on a desk If the ERR LED goes off noise may have affected the PLC Take the following measures Check the ground wiring and reexamine the ...

Страница 219: ...t 18 Other Extension Units and Options 19 Display Module 20 Terminal Block 14 6 Judgment by Error Codes and Representation of Error Codes Error codes can be checked with the programming tool and display module 14 6 1 Operation and check by GX Works2 1 Connect the personal computer and the PLC 2 Execute the PLC diagnosis Click Diagnostics PLC Diagnostics on the tool menu and the diagnosis of PLC wi...

Страница 220: ...sor moves quickly When the cursor is in the uppermost position the button is ineffective The cursor moves downward When the button is held for 1 second or more the cursor moves quickly When the cursor is in the lowermost position the button is ineffective OK The flashing item at the cursor is selected Button Operation Description ESC The screen returns to the Menu screen 1 error or less Ineffectiv...

Страница 221: ...nd GX Developer This manual GX Works2 I O configuration error I O Configuration Error PLC hardware error PLC Hardware Error PLC PP communication error PLC PP Communication Error Serial communication error 1 ch1 Link Error Serial communication error 2 ch2 Serial Communication Error 2 ch2 Parameter error Parameter Error Syntax error Syntax Error Circuit error Ladder Error Operation error Operation E...

Страница 222: ...ror 3806 Communication time out detected 3807 Modem initialization error 3808 N N network parameter error 3809 N N Network setting error 3812 Parallel link character error 3813 Parallel link sum error 3814 Parallel link format error 3820 Inverter communication error 3821 MODBUS communication error 3840 Special adapter connection error Check connection of the special adapter PLC hardware error M806...

Страница 223: ... Remote maintenance Ensure modem power is ON and check the settings of the AT commands Wiring Check the communication cables for correct wiring 6302 Communication character error 6303 Communication data sum check error 6304 Communication data format error 6305 Command error 6306 Communication time out detected 6307 Modem initialization error 6308 N N network parameter error 6309 N N Network settin...

Страница 224: ...tions in the program mode so that their mutual relationship becomes correct 6611 More ANB ORB instructions than LD LDI instructions 6612 Less ANB ORB instructions than LD LDI instructions 6613 MPS is continuously used 12 times or more 6614 No MPS instruction 6615 No MPP instruction 6616 No coil between MPS MRD and MPP or incorrect combination 6617 Instruction below is not connected to bus line STL...

Страница 225: ...or operand of applied instruction exceeds limit 6707 File register is accessed without parameter setting of file register 6708 FROM TO instruction error This error occurs in the execution of operation Review the program and check the contents of the operands used in applied instructions Verify that the specified buffer memories exist in the counterpart equipment Verify that extension cables are co...

Страница 226: ...hed PID operation is not started The operation direction estimated from the measured value at the start of auto tuning was different from the actual operation direction of the output during auto tuning Correct the relationship among the target value output value for auto tuning and the measured value and then execute auto tuning again 6752 Step response method Improper auto tuning result Auto tuni...

Страница 227: ...r ZRN instruction is already used in another instruction Check to make sure the input X as specified by DSZR or ZRN instruction is not being used for the following purposes Input interrupt High speed counter C235 to C255 Pulse catch M8170 to M8175 SPD instruction 6764 Pulse output number is already used in a positioning instruction or pulse output instruction PLSY PWM etc Check to make sure the pu...

Страница 228: ...ial adapters special blocks and set special parameters correctly Set special parameters correctly turn OFF the power and then turn ON the power 03 1 Special parameter transfer target unconnected error Special parameters are set but special adapters special blocks are not connected Check whether special adapters special blocks are connected 04 1 Special parameter unsupported function Check that spe...

Страница 229: ...itsubishi Electric representative 2 Output does not turn off Stop the PLC and check that the output turns off Check for trouble with external wiring For the procedures on running and stopping the PLC refer to Section 14 2 When the output turns off The output may be turned on unintentionally in the program Check that there are no duplicate coils in the program When the output does not turn off The ...

Страница 230: ...rate the PLC online from the programming tool depending on the type of the programming tool and the registered keyword 2 Caution on using a peripheral device which does not support the second keyword and customer keyword Sequence programs in which the second keyword and customer keyword are registered cannot be all cleared using a peripheral device that does not support the second keyword and cust...

Страница 231: ...urs in an input output control block output control may be disabled External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 3 Note that the output current of the 24V DC service power supply varies depending on the model and the absence presence of extension blocks If an overload occurs the voltage automatically drops inputs in the PLC are disabled and ...

Страница 232: ...n this manual If an AC power supply is connected to a DC input output terminal or DC power supply terminal the PLC will burn out Connect the DC power supply wiring to the dedicated terminals described in this manual If an AC power supply is connected to a DC input output terminal or DC power supply terminal the PLC will burn out Do not wire vacant terminals externally Doing so may damage the produ...

Страница 233: ...input output powered extension units we recommend you to add the same types of units as the main unit or the sink and source type Sink common Source common Model Input Output Connection type Type Number of points Common wiring system Type Number of points Common wiring system AC power supply common to 24V DC sink and source input FX2N 32ER ES UL 24V DC 16 Relay 16 Terminal block FX2N 48ER ES UL 24...

Страница 234: ...n FX2N powered extension unit Classification FX2N powered extension unit Supply voltage 100 to 240 V AC Supply voltage 24 V DC Voltage fluctuation range 15 10 Voltage fluctuation range 20 30 Power fuse 250 V 5 A Power fuse 250 V 5 A Rush current 100 V AC Up to 40 A 5 ms or less Power consumption 30 W 200 V AC Up to 60 A 5 ms or less 24 V DC service power supply None Power consumption 35 W Connecti...

Страница 235: ... assigns input numbers in ascending order from A B C below 5 Terminal block covers The covers can be opened about 90 for wiring Keep the covers closed while the PLC is running the unit power is on 6 Extension device connecting connector cover Connect the extension cable of input output powered extension unit block or special function unit block to the extension device connecting connector under th...

Страница 236: ...e shown 13 Terminal block covers Protects the upper and lower stages of the terminal block 14 Output Y terminals Wire the intended loads contactors solenoid valves etc to these terminals 15 Protective terminal covers A protective terminal cover refer to the following drawing is fitted to the lower stage of each terminal block to prevent fingers from touching terminals thereby improving the safety ...

Страница 237: ...ons refer to Section 15 2 2 Input specifications for sink input and source input 1 Do not connect with 0V and 24V terminals Item FX2N 32ER ES UL FX2N 48ER ES UL FX2N 48ER DS Input points 16 points 24 points Connection type Removable terminal block M3 screw Input form sink source Input signal voltage AC power supply type 24V DC 10 DC power supply type 24V DC 20 30 Input signal current 5mA 24V DC In...

Страница 238: ...light the LED indicator lamp on panel Max load Resistance load 2A point The total load current per common terminal should be the following value 4 output points common terminal 8A or less The total load current per common terminal should be the following value 4 output points common terminal 8A or less 8 output points common terminal 8A or less Inductive load 80VA For the product life refer to Sub...

Страница 239: ...32ER ES UL FX2N 48ER ES UL FX2N 48ER DS 182 7 17 172 6 78 mounting hole pitch 80 3 15 mounting hole pitch 90 3 55 9 0 36 Unit mm inches 87 3 43 4 4 5 mounting holes X0 S S 0V 24V N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 COM2 Y1 Y0 COM1 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM3 COM4 FX2N 32ER ES UL X0 S S 0V 24V N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 COM2 Y1 Y0 COM1 ...

Страница 240: ...S UL FX2N 48ET ESS UL FX2N 48ET DSS Input points 16 points 24 points Connection type Removable terminal block M3 screw Input form sink source Input signal voltage AC power supply type 24V DC 10 DC power supply type 24V DC 20 30 Input signal current 5mA 24V DC Input impedance 4 3 k Input response time Input ON current 3 5mA or more 24V DC Input OFF current 1 5mA or less Input response time Approx 1...

Страница 241: ...ght the LED indicator lamp on panel Max load Resistance load 0 5A point The total load current per common terminal should be the following value 4 output points common terminal 0 8A or less 0 5A point The total load current per common terminal should be the following value 4 output points common terminal 0 8A or less 8 output points common terminal 1 6A or less Inductive load 12W 24V DC The total ...

Страница 242: ... mm inches 87 3 43 4 4 5 mounting holes X0 S S 0V 24V N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 V1 Y1 Y0 V0 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V2 V3 FX2N 32ET ESS UL X0 S S 0V 24V N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 Y1 Y0 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 X0 X1 X2 X3 X4 X5 X6 X7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 FX2N 48ET ESS UL V0 V1 V2 V3 V4 X0 S S 0V 24V X1 X2 X3 X4 X5 ...

Страница 243: ...to Chapter 12 for output wiring 1 Power supply specifications For the power supply specifications refer to Section 15 2 2 Input specifications sink input 1 Do not connect with 24 terminals Item FX2N 32ER FX2N 48ER FX2N 48ER D Input points 16 points 24 points Connection type Removable terminal block M3 screw Input form sink Input signal voltage AC power supply type 24V DC 10 DC power supply type 24...

Страница 244: ...otal load current per common terminal should be the following value 8 output points common terminal 8A or less 2A point The total load current per common terminal should be the following value 4 output points common terminal 8A or less 8 output points common terminal 8A or less Inductive load 80VA For the product life refer to Subsection 14 4 3 For cautions on external wiring refer to Subsection 1...

Страница 245: ...out FX2N 32ER FX2N 48ER FX2N 48ER D 182 7 17 172 6 78 mounting hole pitch 80 3 15 mounting hole pitch 90 3 55 9 0 36 Unit mm inches 87 3 43 4 4 5 mounting holes X0 COM 24 N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 COM2 Y1 Y0 COM1 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM3 COM4 FX2N 32ER X0 COM 24 N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 COM2 Y1 Y0 COM1 Y5 Y6 Y7 Y0 Y1 Y2 ...

Страница 246: ... sink input 1 Do not connect with 24 terminals Item FX2N 32ET FX2N 48ET FX2N 48ET D Input points 16 points 24 points Connection type Removable terminal block M3 screw Input form sink Input signal voltage AC power supply type 24V DC 10 DC power supply type 24V DC 20 30 Input signal current 5mA 24V DC Input impedance 4 3 k Input response time Input ON current 3 5mA or more 24V DC Input OFF current 1...

Страница 247: ...amp on panel Max load Resistance load 0 5A point The total load current per common terminal should be the following value 4 output points common terminal 0 8A or less 0 5A point The total load current per common terminal should be the following value 4 output points common terminal 0 8A or less 8 output points common terminal 1 6A or less Inductive load 12W 24V DC The total of inductive loads per ...

Страница 248: ...4 5 mounting holes X0 COM 24 N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 COM2 Y1 Y0 COM1 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM3 COM4 FX2N 32ET X0 COM 24 N L X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7 Y4 Y2 Y3 COM2 Y1 Y0 COM1 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM3 COM4 X0 X1 X2 X3 X4 X5 X6 X7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM5 FX2N 48ET X0 COM 24 X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7...

Страница 249: ...er to Chapter 9 for power supply wiring Refer to Chapter 10 for input wiring Refer to Chapter 12 for output wiring 1 Power supply specifications For the power supply specifications refer to Section 15 2 2 Input specifications sink input Item FX2N 32ES Input points 16 points Connection type Removable terminal block M3 screw Input form sink Input signal voltage 24V DC 10 Input signal current 5mA 24V...

Страница 250: ...ator lamp on panel Max load Resistance load 0 3A point The total load current per common terminal should be the following value 4 output points common terminal 0 8A or less Inductive load 15VA 100V AC 30VA 200V AC Open circuit leakage current 1mA 100V AC 2mA 200V AC Min load 0 4VA 100V AC 1 6VA 200V AC Response time OFF ON 1ms or less ON OFF 10ms or less Output circuit configuration Load Fuse DC p...

Страница 251: ...r 10 for input wiring Refer to Chapter 12 for output wiring 1 Power supply specifications For the power supply specifications refer to Section 15 2 2 Input specifications 100V AC Input Item FX2N 48ER UA1 UL Input points 24 points Connection type Removable terminal block M3 screw Input form AC input Input signal voltage 100 to 120V AC 10 15 50 60 Hz Input signal current 4 7 mA 100V AC 50 Hz 70 or l...

Страница 252: ... load current of resistance loads per common terminal should be the following value 4 output points common terminal 8A or less 8 output points common terminal 8A or less Inductive load 80VA For the product life refer to Subsection 14 4 3 For cautions on external wiring refer to Subsection 12 1 2 Open circuit leakage current Min load 5V DC 2mA reference value Response time OFF ON Approx 10ms ON OFF...

Страница 253: ...an input output control block output control may be disabled External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 3 Note that the output current of the 24V DC service power supply varies depending on the model and the absence presence of extension blocks If an overload occurs the voltage automatically drops inputs in the PLC are disabled and all out...

Страница 254: ...cribed in this manual If an AC power supply is connected to a DC input output terminal or DC power supply terminal the PLC will burn out Do not wire vacant terminals externally Doing so may damage the product When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Make sure to prope...

Страница 255: ...nputs and four outputs are occupied as unused numbers 2 For input extension Sink common Source common Model Input Output Connection type Type Number of points Common system Type Number of points Common system Common to both sink and source inputs FX2N 8ER ES UL 24V DC 4 8 1 Relay 4 8 1 Terminal block Dedicated to sink input only FX2N 8ER 24V DC 4 8 1 Relay 4 8 1 Terminal block Model Input Output C...

Страница 256: ...EYR S ES UL Relay 8 Terminal block FX2N 8EYR Relay 8 Terminal block FX2N 16EYR ES UL Relay 16 Terminal block FX2N 16EYR Relay 16 Terminal block Dedicated to sink output only FX2N 8EYT Transistor 8 Terminal block FX2N 8EYT H Transistor 8 Terminal block FX2N 16EYT Transistor 16 Terminal block FX2N 16EYT C Transistor 16 Connector FX2N 16EYS Transistor 16 Terminal block Dedicated to source output only...

Страница 257: ...and source inputs Item FX2N 8ER ES UL Product type FX2N extension block Rated voltage 24V DC supplied from main unit and input output powered extension unit Item FX2N 8ER ES UL MASS Weight Approx 0 2kg 0 44lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item F...

Страница 258: ... with CE UL or cUL standards Output circuit insulation Mechanical insulation Indication of output operation Supplying power to the relay coil will light the LED indicator lamp on panel Max load Resistance load 2A point The total resistance load current per common should be as follows 4 output points common 8A or less Inductive load 80VA For the product life refer to Subsection 14 4 3 For cautions ...

Страница 259: ... Maintenance Troubleshooting 15 Input Output Powered Extension Units 16 Input Output Extension Blocks 17 Extension Power Supply Unit 18 Other Extension Units and Options 19 Display Module 20 Terminal Block 16 2 FX2N 8ER ES UL 24V DC Sink Source Input Relay Output 16 2 3 External dimensions 43 1 7 9 0 36 80 3 15 mounting hole pitch 87 3 43 90 3 55 Unit mm inches 2 4 5 mounting holes ...

Страница 260: ... from main unit and input output powered extension unit Item FX2N 8ER MASS Weight Approx 0 2kg 0 44lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8ER Input points 4 points Connection type Vertical terminal block M3 screws Input form Sink Input signa...

Страница 261: ... block M3 screws Output type Relay External power supply 30V DC or less 240V AC or less 250V AC or less when the unit does not comply with CE UL or cUL standards Output circuit insulation Mechanical insulation Indication of output operation Supplying power to the relay coil will light the LED indicator lamp on panel Max load Resistance load 2A point The total resistance load current per common sho...

Страница 262: ...56 FX3G Series Programmable Controllers User s Manual Hardware Edition 16 3 FX2N 8ER 24V DC Sink Input Relay Output 16 3 3 External dimensions 43 1 7 9 0 36 80 3 15 mounting hole pitch 87 3 43 90 3 55 Unit mm inches 2 4 5 mounting holes ...

Страница 263: ...roduct type FX2N extension block Rated voltage 24V DC supplied from main unit and input output powered extension unit Item FX2N 8EX ES UL FX2N 16EX ES UL MASS Weight Approx 0 2kg 0 44lbs Approx 0 3kg 0 66lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2...

Страница 264: ...ber is assigned 8 points on the upper side will be used for the lower input numbers and 8 points on the lower side will be used for the higher input numbers With cover Input indicator lamps LED lamps Without cover Rear line extension connector S S X0 X1 X2 X3 X4 X5 X6 X7 With cover Input indicator lamps LED lamps Input indicator lamps LED lamps Without cover Rear line extension connector X0 S S X1...

Страница 265: ...nits 16 Input Output Extension Blocks 17 Extension Power Supply Unit 18 Other Extension Units and Options 19 Display Module 20 Terminal Block 16 4 FX2N 8EX ES UL FX2N 16EX ES UL 24V DC Sink Source Input 16 4 3 External dimensions FX2N 8EX ES UL FX2N 16EX ES UL 43 1 7 Unit mm inches 80 3 15 mounting hole pitch 90 3 55 87 3 43 9 0 36 2 4 5 mounting holes 87 3 43 80 3 15 mounting hole pitch 90 3 55 U...

Страница 266: ...nsion unit Item FX2N 8EX FX2N 16EX FX2N 16EX C MASS Weight Approx 0 2kg 0 44lbs Approx 0 3kg 0 66lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8EX FX2N 16EX FX2N 16EX C Input points 8 points 16 points Connection type Vertical terminal block M3 scre...

Страница 267: ...FX2N 8EX FX2N 16EX and FX2N 16EX C 16 5 2 Parts identification and terminal arrangement FX2N 8EX FX2N 16EX When an input X number is assigned 8 points on the upper side will be used for the lower input numbers and 8 points on the lower side will be used for the higher input numbers With cover Input indicator lamps LED lamps Without cover Rear line extension connector 24 X0 X1 X2 X3 X4 X5 X6 X7 Wit...

Страница 268: ...s FX2N 8EX FX2N 16EX Connector type Terminal arrangement With cover Input indicator lamps LED lamps Input indicator lamps LED lamps Without cover Rear line extension connector B X0 X1 X2 X3 X4 X5 X7 X6 24 Side Side A 1 2 3 4 5 6 8 7 9 No 10 11 12 13 14 15 16 18 17 19 No 20 X0 X1 X2 X3 X4 X5 X7 X6 24 Connector pin arrangement Lower numbers Higher numbers 43 1 7 Unit mm inches 80 3 15 mounting hole ...

Страница 269: ...EX C FX2N 16EX C How to connect connector FX2N 16EX C 80 3 15 mounting hole pitch Unit mm inches 87 3 43 90 3 55 9 0 36 40 1 58 2 4 5 mounting holes 20 20 The polarity is shown in the following table Connection face of connector Cross section of 20 core flat cable Socket FX 16E CAB type cable Be sure to check the wire number B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 A 1 2 3 4 5 6 7 8 9 ...

Страница 270: ...X2N 16EXL C MASS Weight Approx 0 3kg 0 66lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 16EXL C Input points 16 points Connection type Connector terminal block Input form TTL level Input signal voltage 5V DC 5 Input signal current 40mA at 5V DC maxi...

Страница 271: ...e used for the lower input numbers and 8 points on side B will be used for the higher input numbers 16 6 3 External dimensions 16 6 4 Example of wiring 1 Wiring on input side Sink input Connector type Terminal arrangement With cover Input indicator lamps LED lamps Input indicator lamps LED lamps Without cover Rear line extension connector X0 X1 X2 X3 X4 X5 X7 X6 5 1 2 3 4 5 6 8 7 9 No 10 11 12 13 ...

Страница 272: ...Connection face of connector Cross section of 20 core flat cable Socket FX 16E CAB type cable Be sure to check the wire number B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 5 X7 X5 X6 X4 X3 X2 X1 X0 5 X7 X5 X6 X4 X3 X2 X1 X0 Side A Side B Side B is for the higher input numbers and side A is for the lower input numbers Exe Side B X050 to X...

Страница 273: ...m FX2N 8EX UA1 UL Product type FX2N extension block Rated voltage 24V DC supplied from main unit and input output powered extension unit Item FX2N 8EX UA1 UL MASS Weight Approx 0 2kg 0 44lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8EX UA1 UL Inpu...

Страница 274: ...N 8EX UA1 UL 100V AC Input 16 7 2 Parts identification and terminal arrangement 16 7 3 External dimensions With cover Input indicator lamps LED lamps Without cover Rear line extension connector X0 X1 X2 X3 X4 X5 X6 X7 COM 43 1 7 Unit mm inches 80 3 15 mounting hole pitch 90 3 55 87 3 43 9 0 36 2 4 5 mounting holes ...

Страница 275: ...ht Approx 0 2kg 0 44lbs Approx 0 3kg 0 66lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8EYR ES UL FX2N 16EYR ES UL FX2N 8EYR S ES UL Output Points 8 points 16 points 8 points All points have separate reference terminals commons Connection type Vert...

Страница 276: ...UL Relay Output 16 8 2 Parts identification and terminal arrangement FX2N 8EYR ES UL FX2N 8EYR S ES UL With cover Output indicator lamps LED lamps Without cover Rear line extension connector Y1 Y0 Y3 Y2 Y4 Y5 Y6 COM1 COM2 Y7 With cover Output indicator lamps LED lamps Without cover Rear line extension connector Y0 Y1 Y2 Y3 Y3 Y4 Y4 Y5 Y7 Y7 Y6 Y6 Y5 Y0 Y1 Y2 ...

Страница 277: ...sion Units and Options 19 Display Module 20 Terminal Block 16 8 FX2N 8EYR ES UL FX2N 8EYR S ES UL FX2N 16EYR ES UL Relay Output FX2N 16EYR ES UL When an output Y number is assigned 8 points on the upper side will be used for the lower output numbers and 8 points on the lower side will be used for the higher output numbers With cover Output indicator lamps LED lamps Output indicator lamps LED lamps...

Страница 278: ...Output 16 8 3 External dimensions FX2N 8EYR ES UL FX2N 8EYR S ES UL FX2N 16EYR ES UL 43 1 7 87 3 43 80 3 15 mounting hole pitch 90 3 55 Unit mm inches 9 0 36 2 4 5 mounting holes 87 3 43 80 3 15 mounting hole pitch 90 3 55 9 0 36 40 1 58 2 φ4 5 mounting holes Unit mm inches 87 3 43 80 3 15 mounting hole pitch 90 3 55 Unit mm inches 9 0 36 40 1 58 2 4 5 mounting holes ...

Страница 279: ...unit Item FX2N 8EYT ESS UL FX2N 16EYT ESS UL MASS Weight Approx 0 2kg 0 44lbs Approx 0 3kg 0 66lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8EYT ESS UL FX2N 16EYT ESS UL Output Points 8 points 16 points Connection type Vertical terminal block M3 s...

Страница 280: ...is assigned 8 points on the upper side will be used for the lower output numbers and 8 points on the lower side will be used for the higher output numbers With cover Output indicator lamps LED lamps Without cover Rear line extension connector Y1 Y0 Y3 Y2 Y4 Y5 Y6 V0 V1 Y7 With cover Output indicator lamps LED lamps Output indicator lamps LED lamps Without cover Rear line extension connector Y0 V0 ...

Страница 281: ...its 16 Input Output Extension Blocks 17 Extension Power Supply Unit 18 Other Extension Units and Options 19 Display Module 20 Terminal Block 16 9 FX2N 8EYT ESS UL FX2N 16EYT ESS UL Transistor Output 16 9 3 External dimensions FX2N 8EYT ESS UL FX2N 16EYT ESS UL 43 1 7 87 3 43 80 3 15 mounting hole pitch 90 3 55 Unit mm inches 9 0 36 2 4 5 mounting holes 87 3 43 80 3 15 mounting hole pitch 90 3 55 U...

Страница 282: ...s already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8EYR FX2N 16EYR Output Points 8 points 16 points Connection type Vertical terminal block M3 screws Output type Relay External power supply 250V AC 30V DC or less Output circuit insulation Mechanical insulation Indication of output op...

Страница 283: ...FX2N 16EYR Relay Output 16 10 2 Parts identification and terminal arrangement FX2N 8EYR FX2N 16EYR When an output Y number is assigned 8 points on the upper side will be used for the lower output numbers and 8 points on the lower side will be used for the higher output numbers With cover Output indicator lamps LED lamps Without cover Rear line extension connector Y1 Y0 Y3 Y2 Y4 Y5 Y6 COM1 COM2 Y7 ...

Страница 284: ...rdware Edition 16 10 FX2N 8EYR FX2N 16EYR Relay Output 16 10 3 External dimensions FX2N 8EYR FX2N 16EYR 43 1 7 87 3 43 80 3 15 mounting hole pitch 90 3 55 Unit mm inches 9 0 36 2 4 5 mounting holes 87 3 43 80 3 15 mounting hole pitch 90 3 55 Unit mm inches 9 0 36 40 1 58 2 4 5 mounting holes ...

Страница 285: ...xtension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8EYT FX2N 16EYT FX2N 16EYT C Output Points 8 points 16 points Connection type Vertical terminal block M3 screws Connector terminal block Output unit type Transistor sink output External power supply 5 30 V DC Output circuit insulation Photo coupler insulation I...

Страница 286: ...d 8 points on the upper side will be used for the lower output numbers and 8 points on the lower side will be used for the higher output numbers With cover Output indicator lamps LED lamps Without cover Rear line extension connector Y1 Y0 Y3 Y2 Y4 Y5 Y6 COM1 COM2 Y7 With cover Output indicator lamps LED lamps Output indicator lamps LED lamps Without cover Rear line extension connector Y0 COM1 Y1 Y...

Страница 287: ...oints on side A will be used for the lower output numbers and 8 points on side B will be used for the higher output numbers 16 11 3 External dimensions FX2N 8EYT FX2N 16EYT Connector type Terminal arrangement With cover Output indicator lamps LED lamps Output indicator lamps LED lamps Without cover Rear line extension connector Y0 Y1 Y2 Y3 Y4 Y5 Y7 Y6 COM 1 2 3 4 5 6 8 7 9 No 10 11 12 13 14 15 16 ...

Страница 288: ... mounting holes 20 20 The polarity is shown in the following table Connection face of connector Cross section of 20 core flat cable Socket FX 16E CAB type cable Be sure to check the wire number B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Y7 Y5 Y6 Y4 Y3 Y2 Y1 Y0 Y7 Y5 Y6 Y4 Y3 Y2 Y1 Y0 Side A Side B Side B is for the higher input numbers...

Страница 289: ...ge 24V DC supplied from main unit and input output powered extension unit Item FX2N 8EYT H MASS Weight Approx 0 2kg 0 44lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 8EYT H Output Points 8 points Connection type Vertical terminal block M3 screws Ou...

Страница 290: ...YT H Transistor Output 16 12 2 Parts identification and terminal arrangement 16 12 3 External dimensions With cover Output indicator lamps LED lamps Without cover Rear line extension connector Y1 Y0 Y3 Y2 Y4 Y5 Y6 COM1 COM2 Y7 43 1 7 87 3 43 80 3 15 mounting hole pitch 90 3 55 Unit mm inches 9 0 36 2 4 5 mounting holes ...

Страница 291: ...roduct type FX2N extension block Rated voltage 24V DC supplied from main unit and input output powered extension unit Item FX2N 16EYS MASS Weight Approx 0 3kg 0 66lbs Other The extension cable is already connected to the extension block Accessories Label for indication of input output number The DIN46277 rail width 35 mm 1 38 or direct installation Item FX2N 16EYS Output Points 16 points Connectio...

Страница 292: ...per side will be used for the lower output numbers and 8 points on the lower side will be used for the higher output numbers 16 13 3 External dimensions With cover Output indicator lamps LED lamps Output indicator lamps LED lamps Without cover Rear line extension connector Y0 COM1 Y1 Y2 Y3 Y4 Y5 Y7 Y6 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM2 Lower numbers Higher numbers 87 3 43 80 3 15 mounting hole pitch 90 ...

Страница 293: ...erlock circuit to prevent damage to the equipment at the upper and lower positioning limits 2 Note that when the PLC CPU detects an error such as a watchdog timer error during self diagnosis all outputs are turned off Also when an error that cannot be detected by the PLC CPU occurs in an input output control block output control may be disabled External circuits and mechanisms should be designed t...

Страница 294: ...ange 15 10 Rated frequency 50 60Hz Allowable instantaneous power failure time The allowable momentary power failure time depends on the power supply used 100V AC power supply system The operation is continued to the momentary power failure for 10 or less ms 200V AC power supply system The operation is continued to the momentary power failure for 100 or less ms Rush current 30A max 5ms or less 100V...

Страница 295: ... supply type main unit 2 The power is supplied as follows when the input extension block including the FX2N 8ER ES UL and FX2N 8ER is used on the downstream side of the extension power supply unit When the main unit is located on the upstream side of the extension power supply unit The power is supplied from the main unit For details refer to Chapter 6 When the input output powered extension unit ...

Страница 296: ...block number Manual supplied with product Terminal block M3 screws The extension cable is already connected to the extension block 18 1 2 FX2N 2DA External Dimensions Terminal Layout MASS Weight Approx 0 2kg 0 44lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Manual supplied with product Terminal block M3 screws The extension ...

Страница 297: ... Label for indication of special unit block number Dust Proof sheet Manual supplied with product Terminal block M3 screws The extension cable is already connected to the extension block 18 1 4 FX3U 4DA External Dimensions Terminal Layout MASS Weight Approx 0 2kg 0 44lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Dust Proof sh...

Страница 298: ...is already connected to the extension block 18 1 6 FX2N 4DA External Dimensions Terminal Layout MASS Weight Approx 0 3kg 0 66lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Manual supplied with product Terminal block M3 screws The extension cable is already connected to the extension block 87 3 43 80 3 15 mounting hole pitch 9...

Страница 299: ...crews Accessories Label for indication of special unit block number Manual supplied with product Terminal block M3 screws The extension cable is already connected to the extension block 18 1 8 FX2N 4AD TC External Dimensions Terminal Layout MASS Weight Approx 0 3kg 0 66lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Manual sup...

Страница 300: ...eight Approx 0 4kg 0 88lbs Installation 35mm 1 38 wide DIN rail or screws Accessories Label for indication of special unit block number Dust proof sheet Manual supplied with product Terminal block M3 screws The extension cable is already connected to the extension block Terminal Layout 87 3 43 80 3 15 mounting hole pitch 90 3 55 Unit mm inches 4 0 16 9 0 36 55 2 17 2 4 5 mounting holes 24 24 V I V...

Страница 301: ...unit block number Manual supplied with product Terminal block M3 screws The extension cable is already connected to the extension block 18 1 12 FX2N 8AD External Dimensions Terminal Layout MASS Weight Approx 0 4kg 0 88lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Manual supplied with product Terminal block M3 5 screws The ex...

Страница 302: ...onnection terminal block mounting screws black The extension cable is already connected to the extension block 18 1 14 FX2N 16CCL M External Dimensions Terminal Layout MASS Weight Approx 0 4kg 0 88lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Terminal resistor 2 resistors for CC Link dedicated cable 2 resistors for CC Link d...

Страница 303: ...f special unit block number Manual supplied with product Terminal block M3 screws The extension cable is already connected to the extension block 18 1 16 FX3U 64CCL External Dimensions Terminal Layout MASS Weight Approx 0 3kg 0 66lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Dust Proof sheet Manual supplied with product Term...

Страница 304: ...on the front face of the product The extension cable is already connected to the extension block 18 1 18 FX3U 128ASL M External Dimensions Terminal Layout MASS Weight Approx 0 2kg 0 44lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Label for indication of special unit block number Dust proof protection sheet Manual supplied with product The extension cable is already connecte...

Страница 305: ... and Terminal Arrangement 18 1 19 FX3U 32DP External Dimensions Pin Configuration MASS Weight Approx 0 2 kg 0 44lbs Installation DIN rail of 35 mm 1 38 in width or screws Accessories GSD file CD ROM Label for indication of special unit block number Dust proof protection sheet Manual supplied with product Connector PROFIBUS DP interface connector D SUB 9 pin female The extension cable is already co...

Страница 306: ...t Terminal block European type 18 2 3 FX3U 3A ADP External Dimensions Terminal Layout MASS Weight Approx 0 1kg 0 22lbs Installation DIN rail of 35 mm 1 38 in width or screws Accessories Manual supplied with product Terminal block European type 7 0 28 15 1 0 6 17 6 0 7 98 3 86 mounting hole pitch 90 3 55 106 4 18 Unit mm inches 74 2 92 15 5 0 62 2 4 5 mounting holes 24 24 V1 I1 COM1 V2 I2 COM2 V3 I...

Страница 307: ...inal Layout MASS Weight Approx 0 1kg 0 22lbs Installation DIN rail of 35 mm 1 38 in width or screws Accessories Manual supplied with product Terminal block European type 18 2 6 FX3U 4AD TC ADP External Dimensions Terminal Layout MASS Weight Approx 0 1kg 0 22lbs Installation DIN rail of 35 mm 1 38 in width or screws Accessories Manual supplied with product Terminal block European type 7 0 28 15 1 0...

Страница 308: ...prox 80g 0 18lbs Installation DIN rail of 35 mm 1 38 in width or screws Accessories Label for indication of link station number Manual supplied with product Terminal block European type Terminal resistance 330 110 built in Terminal Layout 7 0 28 15 1 0 6 17 6 0 7 98 3 86 mounting hole pitch 90 3 55 106 4 18 Unit mm inches 74 2 92 7 5 0 3 2 4 5 mounting holes 9 8 7 6 5 4 3 2 1 1 CD DCD 2 RD RXD 3 S...

Страница 309: ... 20 Terminal Block 18 Other Extension Devices and Optional Units External Dimensions and Terminal Arrangement 18 2 9 FX3U ENET ADP External Dimensions MASS Weight Approx 0 1kg 0 22lbs Installation DIN rail of 35 mm 1 38 in width or screws Accessories Manual supplied with product Connector 10BASE T 100BASE TX RJ45 Terminal block External ground terminal M2 5 terminal block screw Pin Configuration U...

Страница 310: ...Manual supplied with product Terminal block European type Terminal Layout LEDs correspond to each input terminal 18 3 2 FX3G 2EYT BD External Dimensions MASS Weight Approx 20g 0 05lbs Accessories Two M3 8 tapping screws for installation of board Side cover Manual supplied with product Terminal block European type Terminal Layout LEDs correspond to each output terminal 14 1 15 1 0 6 0 56 35 1 38 Un...

Страница 311: ...al Arrangement 18 3 3 FX3G 232 BD External Dimensions MASS Weight Approx 20g 0 05lbs Accessories Two M3 8 tapping screws for installation of board Side cover Manual supplied with product Connector RS 232C D SUB 9 pin male Pin Configuration 18 3 4 FX3G 422 BD External Dimensions MASS Weight Approx 20g 0 05lbs Accessories Two M3 8 tapping screws for installation of board Side cover Manual supplied w...

Страница 312: ... FX3G 485 BD RJ External Dimensions MASS Weight Approx 20g 0 05lbs Accessories Two M3 8 tapping screws for installation of board Side cover Label for indication of link station number 2 types Manual supplied with product Terminal block European type for grounding Connector RJ45 Terminal resistance 330 110 built in Unit mm inches 35 1 38 14 1 0 56 15 1 0 6 51 2 2 02 5 poles 330 OPEN 110 R D A R D B...

Страница 313: ...ternal Dimensions and Terminal Arrangement 18 3 7 FX3G 2AD BD External Dimensions MASS Weight Approx 20g 0 05lbs Accessories Two M3 8 tapping screws for installation of board Side cover Manual supplied with product Terminal block European type Terminal Layout 18 3 8 FX3G 1DA BD External Dimensions MASS Weight Approx 20g 0 05lbs Accessories Two M3 8 tapping screws for installation of board Side cov...

Страница 314: ...l Units External Dimensions and Terminal Arrangement 18 3 9 FX3G 8AV BD External Dimensions MASS Weight Approx 20g 0 05lbs Accessories Two M3 8 tapping screws for installation of board Side cover Trimmer layout label Manual supplied with product Trimmer Layout Unit mm inches 35 1 38 12 0 48 51 2 2 02 VR0 VR3 VR2 VR1 VR4 VR7 VR6 VR5 ...

Страница 315: ...gement 18 4 Power Supply 18 4 1 FX2N 20PSU External Dimensions Terminal Layout MASS Weight Approx 0 3kg 0 66lbs Installation DIN rail of 35mm 1 38 in width or screws Accessories Manual supplied with product Terminal block M3 5 screws 18 5 Connector Conversion Adapter 18 5 1 FX3G CNV ADP External Dimensions MASS Weight Approx 0 1kg 0 22lbs Accessories Four M3 8 tapping screws for installation of ad...

Страница 316: ...2N CNV BC External Dimensions MASS Weight Approx 40g 0 09lbs Installation Screws only 18 6 Interface Module 18 6 1 FX 232AWC H External Dimensions MASS Weight Approx 0 1kg 0 22lbs Accessories Manual supplied with product Connector RS 232C D SUB 25 pin female RS 422 D SUB 25 pin female 60 5 2 39 30 1 19 40 1 58 Unit mm inches 16 4 0 65 2 3 2 mounting holes Unit mm inches 25 0 99 80 3 15 60 2 37 ...

Страница 317: ...n An operation error may damage the machinery or cause accidents STARTUP AND MAINTENANCE PRECAUTIONS Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative Turn off the power to the PLC before attaching or detaching the following devices Failure to do so may cause equipment failures or malfunc...

Страница 318: ...unction of operation button ESC Use this button to cancel the operation and to return to the previous screen Use this button to move the cursor or to set a numeric value Use this button to move the cursor or to set a numeric value OK Use this button to select an item or to determine the set numeric value Liquid crystal screen ESC button button button OK button Cut off the part when using an expans...

Страница 319: ...F when installing the display module 19 2 1 Installation when the expansion board connector conversion adapter is not used together The FX3G 40MT ES is used as the main unit in this example 1 Remove the top cover Remove the top cover A in the figure on the right as shown in the right figure Caution Display module cannot attach in the top cover S side of a 40 60 point types main unit 2 Install remo...

Страница 320: ...op cover S side of the 40 60 point type main unit 2 Remove the upper connector cover A in the right figure 3 Remove the part B shown in the right figure using a nipper etc Caution Removal of the part B is not necessary when the connector conversion adapter is used together and the main unit is the 14 24 point type 4 Attach the display module to the option connector of the expansion board connector...

Страница 321: ...Button operation Section 19 6 ErrorCheck Performs error checks and displays the results Button operation Section 19 7 LANGUAGE selects the menu display language Selects either Japanese or English as the menu display language Button operation Section 19 8 Contrast Adjusts the contrast 5 to 10 default setting 0 Button operation Section 19 9 ClockMenu Display Displays the current time Button operatio...

Страница 322: ...etails of the specified device monitor function Although the year displays in a 2 digit format 08 this can be changed to a 4 digit format 2008 by revising the program Refer to Subsection 19 10 3 for the 2 digit year to 4 digit year change procedure 19 4 3 Menu screen As shown in the figure at right the menu screen displays 4 lines of the total menu Press the button to scroll downward through the m...

Страница 323: ...k Mo n i t o r T e s t Display example Display example Top screen Time display F X 3 G S e r i e s ME L S EC F V e r 1 1 0 D 1 6 b i DD 3 2 t b i t T 1 6 b i t R 3 2 b i t C R D E D 1 6 b i t R 3 2 b i t R E X Y M S OK ESC OK or ESC ESC OK ESC L A GUA N E G L A GUA N E G n E g l i h s OK ESC OK ESC OK ESC ESC ESC Specified device monitor screen X 0 1 0 3 4 5 6 7 S p e c i f i e d 0 1 0 0 8 2 3 5 9...

Страница 324: ...mmable Controllers User s Manual Hardware Edition 19 5 Menu Structure K e w r y o OK ESC OK ESC Display example C a s s e t t e d Display example P L P L C a s e t t s e C a s e t t s e Mem r y o C a s e t t s e C C e h T K e y o w d n s i o t e s t r ...

Страница 325: ...uits when the PLC is running Moreover a forced ON OFF result is retained for devices Y M S which are not being driven by an OUT instruction etc in the program 2 Setting values of timer and counter can be changed when the PLC status is as shown below 3 The C200 to C255 32 bit up down counters and the high speed counters have counting directions 4 Extended file registers stored in the EEPROM in the ...

Страница 326: ...is turned on the display begins with device No 1 b At subsequent power ONs the device which was being monitored at the previous operation is displayed they are saved in memory for each device type 4 Use the and buttons to move the cursor or the screen to the until the device to be monitored is displayed Refer to Subsection 19 6 3 for status display Selected Device Type Button Operation Description...

Страница 327: ...a register D 16 bit extended register R 16 bit extended file register ER 16 bit 2 Data register DD 32 bit extended register DR 32 bit extended file register DER 32 bit File register D The file register D current value cannot be directly monitored at the display module 3 Timer T 1 When not using it in a program a setting value is displayed as Display Content 1 Device No 2 Current value Display Cont...

Страница 328: ...P count DOWN count Blank 32 bit up down counter and high speed counter only 5 Current value 6 Setting value 1 Display Content 1 Device No at beginning of line Input X and output Y 8 points per line Auxiliary relay M special auxiliary relay M and state S 10 points per line 2 ON OFF status ON Last digit of device No OFF 0 C 0 R 0 0 1 C0 to C199 1 5 6 0 U C 0 R 1 C200 to C255 3 4 5 5 6 0 2 S 2 2 3 1 ...

Страница 329: ...nt value is to be changed Refer to Subsection 19 6 2 for monitor function operation 2 Hold the OK button for 1 second or longer to switch to the test mode The current value begins blinking refer to fig at right 3 Use the buttons to change the value as desired To cancel the operation and return to the monitor screen press ESC 4 Press OK to register the current value and return to the monitor screen...

Страница 330: ...alue change setting value change Use the buttons to change the value as desired then press OK to register the changed value 6 After the setting operation is completed return to the test subject selection screen where the ESC button can then be pressed to return to the monitor screen Test Subject Test Description 1 Contact forced ON OFF 2 Current value change 3 Setting value change Test Subject Sta...

Страница 331: ...SC 3 Use the buttons to move the blinking position to the device where a forced ON OFF is desired To cancel the operation and return to the monitor screen press ESC 4 Press the OK button to highlight the contact s ON OFF status Return to the monitor screen press ESC 5 Press ESC to return to the monitor screen Button Operation Description ESC Cancels the operation and returns to the monitor screen ...

Страница 332: ...rites The allowable number of writes is 10 000 or less for the memory cassette EEPROM and 20 000 or less for the built in memory EEPROM 19 7 Error Check The main unit s error status displays at the ErrorCheck menu 1 At the menu screen use the buttons to move the cursor to the ErrorCheck item then press OK The error check result then displays at the error display screen refer to fig at right To can...

Страница 333: ...8 1 Changing to Japanese menus The procedure for changing from English menus to Japanese menus is described below 1 Turn the PLC power on Following a brief title screen display 1 5 seconds the top screen time display or a specified device monitor screen is displayed 2 Press the ESC button when the specified device screen is displayed Press the OK or ESC button when the time is displayed Then the m...

Страница 334: ...and return to the menu screen press ESC 3 Press OK to register the selected display language and return to the menu screen 19 8 3 D8302 changes by program and related devices Selections made at this menu are saved at D8302 A Language setting of 1 is specified at factory default D8302 changes by user program can also be specified 1 Latch device Button Operation Description ESC Cancels the operation...

Страница 335: ... factory default 1 At the menu screen use the buttons to move the cursor to the Contrast item then press OK to display the contrast adjustment screen To cancel the operation and return to the top screen time display press ESC 2 Use the buttons to adjust the contrast To cancel the operation and return to the menu screen press ESC 3 Press the OK button to register the selected setting and return to ...

Страница 336: ...d then press OK to register the change Settings are performed in the following sequence Year Month Day Hours Minutes Seconds After pressing OK to register the final seconds setting a Current time is set message is displayed completing the current time setting procedure 5 Press OK or ESC to return to the selection screen 6 Press ESC to return to the menu screen Button Operation Description ESC Retu...

Страница 337: ... time item To cancel the operation and return to the menu screen press ESC 3 Press the OK button to display the current time To cancel the operation and return to the selection screen press ESC 4 Press OK or ESC to return to the selection screen 5 Press ESC to return to the menu screen 19 10 3 Changing the current time s Year from 2 digit format to 4 digit format The Year data displays as 2 digit ...

Страница 338: ...Function disabled 1 Customer keyword Permanent PLC lock included However permanent PLC lock does not have a keyword input Number Of Digits Registration Method Peripheral Device Keyword Registration Level Keyword Description FX3G Compatible Not FX3G Compatible 16 digit 1 By selecting the keyword registration level at the GX Works2 etc setting screen Reading writing prohibited 16 digit hexadecimal v...

Страница 339: ...to the Keyword item then press OK to display one of the 4 screens shown below the screen that displays depends on the keyword status If no keywords are registered press ESC to return to the menu screen To cancel the operation and return to the top screen time display press ESC K e y w o r 0 0 b t y h e T s i h o p e r K e y a C s e t t s Menu screen When switching to menu prohibited by keyword occ...

Страница 340: ...en if pressed when the keyword s left most digit highest order digit is blinking Cancels the input and moves leftward to the next digit higher order digit if pressed when a digit other than the left most digit is blinking Reduces the value F E 2 1 0 Hold for 1 second or longer for high speed reduction Increases the value 0 1 2 E F Hold for 1 second or longer for high speed increase OK Highest orde...

Страница 341: ...and Options 19 Display Module 20 Terminal Block 19 11 Keyword 19 11 6 Enabling a keyword 1 At the menu screen use the buttons to move the cursor to the keyword item then press OK to display the enable keyword screen 2 Press the OK button to enable the keyword Or to retain the keyword s canceled status press ESC Button Operation Description ESC Cancels the operation and returns to the menu screen D...

Страница 342: ...e top screen time display press ESC 2 Use the buttons to move the cursor to the Cassette PLC item then press OK to display the screen shown to the right To cancel the operation and return to the memory cassette transfer screen press ESC 3 Press OK to begin the transfer Or press ESC to cancel the operation Caution Do not turn the PLC power off or perform writing from the programming tool while a pr...

Страница 343: ...e menu screen 19 12 2 Transfer from memory cassette to internal EEPROM Cassette PLC 1 At the menu screen use the buttons to move the cursor to the Cassette item then press OK to display the memory cassette transfer screen To cancel the operation and return to the top screen time display press ESC 2 Use the buttons to move the cursor to the Cassette PLC item then press OK to display the screen show...

Страница 344: ...ve The transfer is not executed if a Transfer failed message appears In this case turn the power off check the memory cassette connection then attempt the operation again from the first step A Transfer completed message appears when the transfer is completed When this message appears press OK or ESC to display the memory cassette transfer screen 5 Press ESC to display the menu screen P L C i s r u...

Страница 345: ...ple The following is a program example in which the system information has been assigned to D50 to D54 and M50 to M64 Specified device monitor function Refer to Section 19 14 for details Screen saver function Refer to Section 19 15 for details Display screen protect function Refer to Section 19 16 for details Operation button ON OFF information Refer to Section 19 17 for details Monitor test funct...

Страница 346: ...ue written in D If any numeric value outside the range from 1 to 10 is written in D the specified device monitor function is disabled 2 System signal 2 1 Turns ON after completion of a test operation for a specified device monitor or when the OK or ESC key operated To turn OFF the request edit of a specified device monitor is turned off or it is turned off in the user s program System Information ...

Страница 347: ...nitor test screen 19 14 3 Program example1 when monitoring testing a timer In this program example the device type to be displayed on the specified device monitor screen is set to timer T Sets the device No to T10 For testing the timer T10 turn ON M0 to enable the test operation In this program example system information is assigned from D50 to D54 and from M50 to M64 D 1 0 0 3 2 7 6 S p e c i f i...

Страница 348: ...ram example system information is assigned from D50 to D54 and from M50 to M64 Initial pulse MOV K50 D8300 MOV K50 D8301 M8002 System information system No 1 is set at D50 to D54 System information system No 2 is set at M50 to M64 Sets the device type to Timer MOV K5 D50 RST D51 Resets the device number D51 INCP D51 DECP D51 M56 M55 M59 M55 M56 M59 MOV K0 D51 MOV K10 D51 K 1 D51 K11 D51 The device...

Страница 349: ...device numbers T1 T5 T10 and T20 during monitoring In this program example system information is assigned from D50 to D54 and from M50 to M64 Initial pulse MOV K50 D8300 MOV K50 D8301 M8002 System information system No 1 is set at D50 to D54 System information system No 2 is set at M50 to M64 Sets the device type to Timer MOV K5 D50 RST Z0 MOV K1 D100 MOV K5 D101 MOV K10 D102 MOV K20 D103 Transfer...

Страница 350: ...utton to return to the menu screen 19 14 7 Specified device monitor screen for monitoring Refer to Section 19 18 for the procedure used to display the current values as hexadecimal values 1 Data register D 16 bit extended register R 16 bit 2 Data register DD 32 bit extended register DR 32 bit File register D The file register D current value cannot be directly monitored at the display module 3 Tim...

Страница 351: ...ts and Options 19 Display Module 20 Terminal Block 19 14 Specified Device Monitor Function 5 Input X Output Y Auxiliary Relay M State S 19 14 8 Test operation on specified device monitor screen To perform the test operation on the specified device monitor screen it is necessary to turn ON M in the system information system signal 2 The device test operation is same as the operation in the monitor ...

Страница 352: ...he first time after the dedicated screen appeared resets the screen saver function and is invalid as a key operation 19 15 3 Program example screen saver time setting In this program example the screen saver time is set to 5 minutes Use this program as a reference when other time settings are specified In this program example system information is assigned from D50 to D54 and from M50 to M64 Syste...

Страница 353: ...ection 19 13 for system information setting 19 16 1 System information display screen protect function 1 System signal 1 2 System signal 2 System signal 2 is unrelated to this function 19 16 2 Program example screen protect function setting In this program example the display screen protect function is set to level 2 Use this program as a reference when other level settings are specified In this p...

Страница 354: ...eywords and the display screen protect function is shown below Function Name Keyword Display Screen Protect 16 digit keyword 1 setting None All online operations prohibited Writing prohibited Reading writing prohibited None 1 2 8 digit keyword setting level A All operations prohibited B Read Incorrect write protection C Erroneous write prohibited Top screen time display Top screen specified device...

Страница 355: ...rd Input Example All online operations prohibited A to F 0 to 9 16 digit value 0ABCDEF262297529 AABCDEBF34523724 Writing prohibited A to F 0 to 9 16 digit value B123456789012345 7ABCDEF73DAEB93A Reading writing prohibited A to F 0 to 9 16 digit value 2890445234817567 CDEF567FABDFEA46 Specified device monitor function Display screen protect function status None 1 Initial screen fixing function 2 Te...

Страница 356: ... the display module s monitor test function to change the system information s system signal 1 D 3 current value to 1 or 2 Once the setting is made it cannot be canceled from the display module To cancel the setting use the programming tool to change the system information s system signal 1 D 3 current value to a value other than 1 and 2 If the system information s system signal 1 D 3 is set in a ...

Страница 357: ...tion checks The programming tool can be used to monitor the system information s system signal 2 operation button ON OFF information to verify that operation buttons are functioning properly 2 Specified device monitor function device changes Devices handled in the specified device monitor function can be changed over by using both the specified device monitor display status and operation button ON...

Страница 358: ...ng values which display at the Monitor Test screen In this program example system information is assigned from D50 to D54 and from M50 to M64 19 18 3 Program example 2 specifying a decadal data display format The following program example specifies a decimal display format for current values and setting values which appear at the Monitor Test screen In this program example system information is as...

Страница 359: ...red Keyword cannot be registered from the display module A programming tool such as GX Works2 etc is required to register keyword Incorrect Keyword The entered keyword does not match the registered keyword Verify the registered keyword then enter the correct keyword Monitor test setting change 1 Memory cassette transfer PLC is running Stop the PLC then attempt the operation again Memory Cassette i...

Страница 360: ...reen and check to refer to if the Fatal error occurred message appears If the Fatal error occurred message appears perform the corrective action described at item 2 below If the Fatal error occurred message does not appear set the PLC to a RUN state then check again if the message appears If the message appears a watchdog timer error has probably occurred In this case the program should be re exam...

Страница 361: ...enu Display Characters Japanese and English Display Character Correspondence Table Menu Screen Japanese English Menu Monitor Test ErrorCheck LANGUAGE Contrast ClockMenu Keyword Cassette ErrorCheck ErrorCheck No errors ErrorCheck Error code LANGUAGE LANGUAGE Japanese English Contrast Contrast ClockMenu Current time Clock setting Clock setting Current time is set Keyword Please input Keyword Make Ke...

Страница 362: ...s the voltage automatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 4 Note that when an error occurs in a relay triac or transistor output device the output could be held either on or off For output signals that may lead to serious accidents external circuits and mechan...

Страница 363: ...re to do so may cause device failures or malfunctions Peripheral devices display modules expansion boards and special adapters Extension units blocks and FX Series terminal blocks Battery and memory cassette WIRING PRECAUTIONS Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the produ...

Страница 364: ...al block is used to convert connector type input output terminals into a terminal block Moreover dedicated input and output terminal blocks built in element types can be used to receive AC input signals for conversion to relay transistor triac output types Terminal block Terminal block Optional cable or user fabricated cable ...

Страница 365: ... 1 FX 32E TB 32 input points 32 output points or 16 input 16 output points FX 16EX A1 TB 2 16 100V AC input type FX2N 16EX C sink input 4 FX 16EYR TB 3 16 Relay output type FX2N 16EYT C sink output 24V DC 80mA FX 16EYS TB 3 16 Triac output type FX2N 16EYT C sink output 24V DC 112mA FX 16EYT TB 3 16 Transistor output sink type FX2N 16EYT C sink output 24V DC 112mA FX 16EYT H TB 3 16 Transistor outp...

Страница 366: ...ut output No labels terminal block arrangement cards No Name Remarks 1 CN1 connector 2 CN2 connector Present at FX 32E TB 3 Operation indicator LED Present at FX 16EYR TB FX 16EYS TB FX 16EYT TB FX 16EYT H TB 4 POWER LED Present at FX 16EX A1 TB 5 CN2 terminal block M3 5 screws Present at FX 32E TB 6 CN1 terminal block M3 5 screws 7 Nameplate 8 DIN rail mounting groove DIN rail width 35mm 1 38 9 D...

Страница 367: ... connected to the FX2N 16EYT C 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Lower numbers Higher numbers When connected to the FX2N 16EX C 0 24 24 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 Lower numbers Higher numbers When connected to the FX2N 16EYT C CN1 When connected to the FX2N 16EX C CN2 CN1 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Lower numbers Higher numbers C...

Страница 368: ...ardware Edition 3 FX 16EX A1 TB 4 FX 16EYR TB FX 16EYS TB FX 16EYT TB FX 16EYT H TB 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM2 0 1 2 3 COM3 COM3 4 5 6 7 COM4 COM4 24 24 Lower numbers Higher numbers 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM2 0 1 2 3 COM3 COM3 4 5 6 7 COM4 COM4 24 24 Lower numbers Higher numbers ...

Страница 369: ... and terminal blocks 2 Align the top side of the DIN rail mounting groove refer to Fig 1 at right with the DIN rail 3 Press the product onto the DIN rail refer to Fig 2 at right 20 4 2 Removal 1 Turn the power supply OFF 2 Disconnect the wiring and input output cables 3 Place a flathead screwdriver against the DIN rail mounting hook in the posture shown refer to Fig 1 at right 4 Move the flathead ...

Страница 370: ... so may cause equipment failures or malfunctions When 1 wire is connected to 1 terminal Use a crimp terminal of the size shown below and install it as shown in the lower right figure When 2 wires are connected to 1 terminal Use a crimp terminal of the size shown below and install it as shown in the lower right figure Model Name Terminal Screw Size FX 16E TB FX 32E TB FX 16EX A1 TB FX 16EYR TB FX 1...

Страница 371: ...nector type extension block 20 5 1 Internal circuit Input Connector Output Connector Connectable models FX2N 16EX C sink input FX2N 16EYT C sink output 1 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 3 2 1 0 COM 7 6 5 4 3 2 1 0 CN1 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 ...

Страница 372: ...ock WIRING PRECAUTIONS Do not wire vacant terminals externally Doing so may damage the product WIRING PRECAUTIONS Do not wire vacant terminals externally Doing so may damage the product 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24V DC Input numbers in the FX2N 16EX C 24 24 24 0 to 7 Higher Nos 0 to 7 Lower Nos 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0...

Страница 373: ...or Connectable models FX2N 16EX C sink input Unsupported Applications High speed processing High speed counter input interruption pulse catch pulse width pulse period measurement speed detection SPD instruction Time division inputs Input matrix MTR instruction digital switch DSW instruction Other Absolute current value read ABS instruction Item AC Input Type Input output circuitry Input signal vol...

Страница 374: ...umbers 0 to 7 Higher numbers 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 4 to 7 20 COM 6 7 5 4 3 2 1 0 COM 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 CN1 Photo coupler Photo coupler Photo coupler Photo coupler 0 to 3 0 to 3 4 to 7 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 PLC input No Photo coupler power supply 100 to 120V AC 4 to 7 0 to 3...

Страница 375: ... PWM instruction DOG search zero return DSZR instruction batch data positioning mode TBL instruction absolute current value read ABS instruction zero return ZRN instruction variable speed pulse output PLSV instruction drive to increment DRVI instruction drive to absolute DRVA instruction Time division inputs Input matrix MTR instruction digital switch DSW instruction Time division output Seven seg...

Страница 376: ...4 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM 6 7 5 4 3 2 1 0 COM 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 to 7 Lower numbers 0 to 7 Higher numbers 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24V DC PLC output No Relay power supply Fuse Fuse 0 to 7 Lower numbers 0 to 7 High...

Страница 377: ...nect a diode for commutation parallel to the load The diode for commutation must comply with the following specifications 2 AC circuit Connect the surge absorber combined CR components such as a surge killer and spark killer etc parallel to the load Select the rated voltage of a surge absorber that is suitable for the load being used Refer to the table below for other specifications Reference 3 In...

Страница 378: ... of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut down For precautions on using inductive loads refer to Subsection 20 7 4 2 Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load...

Страница 379: ...matrix MTR instruction digital switch DSW instruction Time division output Seven segment with latch SEGL instruction Item Transistor output FX 16EYT TB FX 16EYT H TB Input output circuitry Load voltage 5 30 V DC Max load Resistance load 0 5A point The total load current of resistance loads per common terminal should be the following value 4 output points common terminal 0 8A or less 1A point The t...

Страница 380: ... 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 Photo coupler Photo coupler 3 3k 3 3k Photo coupler Photo coupler For the FX 16EYT H TB the output transistor elements are as shown in the figure below 0 to 7 Lower numbers 0 to 7 Higher numbers 3 3k 3 3k 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 PLC output No Photo ...

Страница 381: ...pply capacity that is at least 2 times larger than the total rated fuse capacity 2 Transistor protection circuit for inductive loads The transistor output circuit in the terminal block is equipped with a Zener diode 50V for protection When an inductive load is connected however a diode should be connected parallel to the load when required The diode must comply with the specifications shown below ...

Страница 382: ...ero return ZRN instruction variable speed pulse output PLSV instruction drive to increment DRVI instruction drive to absolute DRVA instruction Time division inputs Input matrix MTR instruction digital switch DSW instruction Time division output Seven segment with latch SEGL instruction Item Triac output Input output circuitry Load voltage 85 to 242V AC Max load Resistance load 0 3A point 1 The tot...

Страница 383: ...output external wiring 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM 6 7 5 4 3 2 1 0 COM 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 Photo thyristor Photo thyristor Photo thyristor U U U U Photo thyristor Surge absorbers are connected to each output 3 3k 0 to 7 Lower numbers 0 to 7 Higher numbers 3 3k 3 3k 3...

Страница 384: ...rated voltage of a surge absorber that is suitable for the load being used Refer to the table below for other specifications Reference 3 Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external interlock should be provided for interlocking the PLC s internal programs as shown to the right 4 In phase PLC output con...

Страница 385: ...eading PLC memory cassette 2 RD LED 3 WR key writing memory cassette PLC 4 WR LED 5 Memory cassette fixing holes 2 3 2 Mounting holes 6 PROTECT switch 7 Detachment lever 8 Main unit connector STARTUP AND MAINTENANCE PRECAUTIONS Turn off the power to the PLC before attaching or detaching the memory cassette If the memory cassette is attached or detached while the PLC s power is on the data in the m...

Страница 386: ... figure 2 Attach the side cover Attach the side cover B in the right figure as shown in the right figure Caution Make sure to attach the side cover before the memory cassette However attachment of the side cover is not necessary when using only the loader function and not always connecting the memory cassette Attachment of the side cover is not necessary when installing the memory cassette under t...

Страница 387: ...use they may damage the main unit 21 3 2 Installation when the expansion board connector conversion adapter is used together The FX3G 40MT ES is used as the main unit and the expansion board is used together in this example 1 Attach the expansion board connector conversion adapter to the main unit For the attachment method refer to Chapter 8 Caution Make sure to attach the expansion board connecto...

Страница 388: ...nector E in the right figure of the expansion board connector conversion adapter 6 Fix the memory cassette G in the right figure with provided M3 tapping screws F in the right figure to the expansion board connector conversion adapter Tightening torque 0 3 to 0 6 N m Caution Two types of M3 tapping screws are provided Use M3 16 longer screws Fixation is not necessary when using only the loader fun...

Страница 389: ...le 1 Raise the memory cassette detachment lever Raise the memory cassette detachment lever A 2 Remove the tapping screws B in the right fig ure which fix the memory cassette Proceed to the step 3 when the memory cassette is not fixed with tapping screws 3 Grasp the detachment lever and pull it Grasp the detachment lever C and pull it vertically to remove the memory cassette 4 Remove the side cover...

Страница 390: ... figure which fix the memory cassette Proceed to the step 3 when the memory cassette is not fixed with tapping screws 3 Grasp the detachment lever and pull it Grasp the detachment lever D and pull it vertically to remove the memory cassette 4 Attach the upper connector cover E in the right figure 5 Fix the expansion board with the tapping screws F in the right figure provided for fixing the memory...

Страница 391: ...G programming tool is selected The maximum number of points cannot be specified when a programming tool other than the FX3G is selected Item Description Saving Method Program Memory Parameters Memory capacity setting Memory capacity default setting 8k steps 2k 4k 8k 16k 32k steps Comment capacity File register capacity Modem initializing settings Battery mode settings RUN terminal settings RS RS2 ...

Страница 392: ...ECT switch knob by using the tip of a pair of tweezers a precision screwdriver or a tool with a tip width of approx 0 8mm 0 04 Do not use objects with round tips as the round tip can easily slip off the switch knob possibly resulting in an incorrect setting 2 Switch operation procedure As shown in the figure below the switch knob can be pushed or pulled When setting the switch do not set it in an ...

Страница 393: ...rocedure in the memory cassette For the data transfer method in the display module refer to Chapter 20 21 7 1 Writing WR 32L PLC A memory cassette program is written to the PLC s internal EEPROM memory Required condition The PLC must be stopped 1 Install the memory cassette on the main unit Setting the PROTECT switch to ON on memory cassette s rear face prevents accidental overwriting of memory ca...

Страница 394: ...dure 21 8 Operation Precautions 1 Tapping screws provided for fixing the memory cassette Two types of longer and shorter M3 tapping screws are packed together with the memory cassette Read carefully the installation method described in Section 21 3 and use the proper type 2 Number of available units Only one memory cassette may be connected to a FX3G main units 3 EEPROM memory writing count 10 000...

Страница 395: ...irectly Incorrect handling of the battery may cause heat excessive generation bursting ignition liquid leakage or deformation and lead to injury fire or failures and malfunctions of facilities and other equipment When replacing the battery make sure to use our specified product FX3U 32BL When a battery error occurs ALM LED is lit in red follow the description in this manual STARTUP AND MAINTENANCE...

Страница 396: ...ctor B in the right figure of the battery Push the battery into the battery holder C in the right figure Set the battery cable as shown in D in the right figure 4 Attach the top cover When the expansion board connector conversion adaptor or memory cassette was removed in the step 2 attach it again 22 3 2 Setting the battery mode using GX Works2 The following setting using a parameter is required t...

Страница 397: ... respect to ambient temperature When planning for battery replacement please estimate the battery life according to the graph to the right and order the replacement batteries in advance 22 4 2 Reading the date of manufacture How to read the battery lot number reference 22 4 3 Special battery low voltage device notification program example Prepare a system which allows constant external monitoring ...

Страница 398: ...he installation procedure refer to Subsection 22 3 1 5 Attach the top cover When the expansion board connector conversion adaptor or memory cassette was removed in the step 2 attach it again Caution 1 After replacing the battery check whether the backup target devices keep devices and clock data are backed up correctly confirm safety and then run the PLC 2 If the backup target devices keep devices...

Страница 399: ...N D8004 M 8005 Battery voltage low ON when battery voltage is below the value set in D8006 D8005 M 8006 Battery error latch It is set when battery voltage low is detected D8006 M 8007 Not used M 8008 M 8009 24V DC down ON when 24V DC power fails in any input output powered extension unit or special function block D8009 1 scan time RUN input M8000 M8001 M8002 M8003 M8061 Error occurrence Number and...

Страница 400: ... the last state of zero return mode M 8044 2 Zero point condition Set this when machine zero return is detected M 8045 All output reset disable Disables the all output reset function when the operation mode is changed M 8046 3 STL state ON ON when M8047 is ON and either of S0 to S899 or S1000 to S4095 is active M8047 M 8047 3 STL monitoring enable D8040 to D8047 are enabled when M8047 is ON D8040 ...

Страница 401: ...6 to D8091 M 8083 2 X004 Pulse period measurement mode D8092 to D8097 Flag M 8090 to M 8100 Not used Memory Information M 8101 Not used M 8102 M 8103 M 8104 M 8105 ON during writing in RUN mode M 8106 Not used M 8107 M 8108 Output Refresh Error M 8109 Output refresh error D8109 M 8110 Not used M 8111 FX3G 4EX BD M 8112 3 BX0 input M 8113 3 BX1 input M 8114 3 BX2 input M 8115 3 BX3 input Number and...

Страница 402: ...ulse Catch M 8170 3 Input X000 pulse catch M 8171 3 Input X001 pulse catch M 8172 3 Input X002 pulse catch M 8173 3 Input X003 pulse catch M 8174 3 Input X004 pulse catch M 8175 3 Input X005 pulse catch M 8176 Not used M 8177 Communication Port Channel Setting M 8178 Parallel link channel switch OFF ch1 ON ch2 M 8179 N N network channel switch 4 Number and name Operation and function Correspond in...

Страница 403: ...8218 C218 M 8219 C219 M 8220 C220 M 8221 C221 M 8222 C222 M 8223 C223 M 8224 C224 M 8225 C225 M 8226 C226 M 8227 C227 M 8228 C228 M 8229 C229 M 8230 C230 M 8231 C231 M 8232 C232 M 8233 C233 M 8234 C234 High Speed Counter Up down Counter Counting Direction M 8235 C235 When M8 is ON the corresponding C is changed to down mode ON Down count operation OFF Up count operation M 8236 C236 M 8237 C237 M 8...

Страница 404: ...357 Not used M 8358 Y001 Positioning instruction activation M 8359 1 Y001 Pulse output stop command M 8360 Y002 Pulse output monitor ON BUSY OFF READY M 8361 1 Y002 Clear signal output function enable M 8362 1 Y002 Zero return direction specification M 8363 Y002 Forward limit M 8364 Y002 Reverse limit M 8365 1 Y002 DOG signal logic reverse M 8366 1 Y002 Zero point signal logic reverse M 8367 Not u...

Страница 405: ...US request in process M 8422 2 MODBUS communication error D8422 M 8423 2 MODBUS communication error latched D8423 M 8424 to M 8427 Not used M 8428 2 Retry M 8429 2 Timeout M 8430 Not used MODBUS communication ch1 ch2 M 8411 2 MODBUS configuration request flag FX3U ENET ADP ch1 M 8404 3 FX3U ENET ADP unit ready M 8405 Not used M 8406 3 4 Time setting execution M 8407 to M 8410 Not used M 8411 3 4 E...

Страница 406: ... D 8008 Not used D 8009 24V DC failed device Lowest input device number of input output powered extension unit in which 24V DC has failed M8009 Present value Type of memory Protect switch 02H EEPROM memory cassette OFF 0AH EEPROM memory cassette ON 10H Built in memory in PLC 2 6 1 0 0 FX3G Series Version 1 00 8 0 6 0 8060 to 8068 when M8004 is ON in units of 0 1V 3 0 Battery voltage present value ...

Страница 407: ...or code for PLC hardware error M8061 D 8062 2 Error code for PC PP communication error or serial communication error 0 ch0 M8062 D 8063 2 Error code for serial communication error 1 ch1 M8063 D 8064 Error code for parameter error M8064 D 8065 Error code for syntax error M8065 D 8066 Error code for ladder error M8066 D 8067 3 Error code for operation error M8067 1 0 2 0 1 Input X 0 Output Y Device ...

Страница 408: ...35 Not used D 8136 Lower PLSY FNC 57 PLSR FNC 59 instructions Accumulated total number of pulses output to Y000 and Y001 D 8137 Upper D 8138 Not used D 8139 D 8140 Lower Accumulated number of pulses output to Y000 for PLSY FNC 57 and PLSR FNC 59 instructions D 8141 Upper D 8142 Lower Accumulated number of pulses output to Y001 for PLSY FNC 57 and PLSR FNC 59 instructions D 8143 Upper D 8144 Not us...

Страница 409: ...gister D 8195 Value of V7 register D 8196 Not used D 8197 D 8198 D 8199 N N Network monitoring D 8200 Not used D 8201 Current link scan time D 8202 Maximum link scan time D 8203 Number of communication error at master station M8183 to M8191 D 8204 Number of communication error at slave station No 1 D 8205 Number of communication error at slave station No 2 D 8206 Number of communication error at s...

Страница 410: ...time Default 100 RS2 FNC 87 ch0 D 8370 RS2 FNC 87 ch0 Communication format setting D 8371 Not used D 8372 1 RS2 FNC 87 ch0 Remaining points of transmit data M8372 D 8373 1 RS2 FNC 87 ch0 Monitoring receive data points M8373 D 8374 Not used D 8375 D 8376 D 8377 D 8378 Number and name Content of register Corres ponding special device D 8379 RS2 FNC 87 ch0 Time out time setting D 8380 RS2 FNC 87 ch0 ...

Страница 411: ...tocol D 8402 2 Communication error code M8402 D 8403 2 Error details M8403 D 8404 2 Error step numbe D 8405 2 Communication format display D 8406 Not used D 8407 2 Step number being executed D 8408 2 Current retry value D 8409 2 Slave response timeout D 8410 2 Turn around delay D 8411 2 Message to message delay D 8412 2 Number of retries D 8413 Not used D 8414 2 Slave node address D 8415 to D 8418...

Страница 412: ...Operation mode display Error Detection D 8438 2 Error code for serial communication error 2 ch2 M8438 RS2 FNC 87 ch2 and Computer Link ch2 D 8439 Operation mode display ch2 Error Detection D 8440 to D 8448 Not used D 8449 Special block error code M8449 D 8450 to D 8459 Not used Positioning D 8460 to D 8463 Not used D 8464 DSZR FNC150 and ZRN FNC156 instructions Y000 Clear signal device specificati...

Страница 413: ... and function column For details refer to the Analog Control Edition Appendix A 3 1 Special auxiliary relays M8260 to M8279 Number Operation and function FX3G 2AD BD FX3G 1DA BD Compatible Versions Ver 1 10 or later Ver 1 10 or later 1st expansion board M 8260 Input mode switching Ch1 Output mode switching M 8261 Input mode switching Ch2 Not used M 8262 Not used Not used M 8263 Not used Not used M...

Страница 414: ...sed D 8262 Not used Not used D 8263 Not used Not used D 8264 Averaging time for Ch1 1 to 4095 Not used D 8265 Averaging time for Ch2 1 to 4095 Not used D 8266 Not used Not used D 8267 Not used Not used D 8268 Error status Error status D 8269 Model code K3 Model code K4 2nd analog expansion board D 8270 Input data Ch1 Output data D 8271 Input data Ch2 Not used D 8272 Not used Not used D 8273 Not us...

Страница 415: ... Input mode switching Ch2 M 8282 Input mode switching Ch3 Output mode switching Ch3 Output mode switching M 8283 Input mode switching Ch4 Output mode switching Ch4 Not used M 8284 Not used Output hold mode cancel Ch1 Not used M 8285 Not used Output hold mode cancel Ch2 Not used M 8286 Not used Output hold mode cancel Ch3 Output hold mode cancel M 8287 Not used Output hold mode cancel Ch4 Sets whet...

Страница 416: ... Not used Not used Not used M 8283 Not used Not used Not used M 8284 Not used Not used Not used M 8285 Not used Not used Not used M 8286 Not used Not used Not used M 8287 Not used Not used Not used M 8288 Not used Not used Not used M 8289 Not used Not used Not used 2nd analog special adapter M 8290 Temperature unit selection Temperature unit selection Temperature unit selection M 8291 Not used Typ...

Страница 417: ...ed D 8284 Averaging time for Ch1 1 to 4095 Not used Averaging time for Ch1 1 to 4095 D 8285 Averaging time for Ch2 1 to 4095 Not used Averaging time for Ch2 1 to 4095 D 8286 Averaging time for Ch3 1 to 4095 Not used Not used D 8287 Averaging time for Ch4 1 to 4095 Not used Not used D 8288 Error status Error status Error status D 8289 Model code K1 Model code K2 Model code K50 2nd analog special ad...

Страница 418: ...for Ch3 1 to 4095 Averaging time for Ch3 1 to 4095 D 8287 Averaging time for Ch4 1 to 4095 Averaging time for Ch4 1 to 4095 Averaging time for Ch4 1 to 4095 D 8288 Error status Error status Error status D 8289 Model code PT K20 PTW K21 Model code K10 Model code K11 2nd analog special adapter D 8290 Ch1 temperature measurement data Ch1 temperature measurement data Ch1 temperature measurement data D...

Страница 419: ...n contacts ORI Parallel connection of NC normally closed contacts ORP Parallel connection of Rising edge pulse ORF Parallel connection of Falling trailing edge pulse Connection Instruction ANB Serial connection of multiple parallel circuits ORB Parallel connection of multiple contact circuits MPS Stores the current result of the internal PLC operations MRD Reads the current result of the internal ...

Страница 420: ...otation and Shift Operation 30 ROR Rotation Right 31 ROL Rotation Left 32 33 34 SFTR Bit Shift Right 35 SFTL Bit Shift Left 36 WSFR Word Shift Right 37 WSFL Word Shift Left 38 SFWR Shift Write FIFO FILO Control 39 SFRD Shift Read FIFO Control FNC No Mnemonic Function Data Operation 40 ZRST Zone Reset 41 DECO Decode 42 ENCO Encode 43 SUM Sum of Active Bits 44 BON Check Specified Bit Status 45 MEAN ...

Страница 421: ...ositioning Control 150 DSZR DOG Search Zero Return 151 152 TBL Batch Data Positioning Mode 153 154 155 ABS Absolute Current Value Read 156 ZRN Zero Return 157 PLSV Variable Speed Pulse Output 158 DRVI Drive to Increment 159 DRVA Drive to Absolute Real Time Clock Control 160 TCMP RTC Data Compare 161 TZCP RTC Data Zone Compare 162 TADD RTC Data Addition 163 TSUB RTC Data Subtraction 164 165 166 TRD...

Страница 422: ...n Ver 1 40 or later 3 Supported in Ver 1 30 or later FNC No Mnemonic Function External Device Communication 270 IVCK Inverter Status Check 1 271 IVDR Inverter Drive 1 272 IVRD Inverter Parameter Read 1 273 IVWR Inverter Parameter Write 1 274 275 IVMC Inverter Multi Command 2 276 ADPRW MODBUS Read Write 3 Extension File Register Control 290 LOADR Load From ER 291 292 293 294 RWER Rewrite to ER 295 ...

Страница 423: ...ntinued model Production stop date Repair acceptance period FX2N 2LC March 31 2018 Until March 31 2025 FX 10DM SET0 September 30 2017 Until September 30 2024 FX2N 20PSU December 31 2015 Until December 31 2022 FX2N 4AD FX2N 4DA FX2N 4AD PT FX2N 4AD TC FX3U 232ADP September 30 2013 Until September 30 2020 FX3U 485ADP FX PCS WIN E March 31 2013 FX 20P E December 31 2012 Until December 31 2019 FX 10DU...

Страница 424: ...ulated FX3G Series products 1 Included modules and batteries None FX3G Series CPU units do not include batteries when shipped from the factory 2 Batteries to be built in modules spare parts and optional parts 1 The value indicates the mass with packaging Appendix D 2 Transport guidelines Comply with IATA Dangerous Goods Regulations IMDG code and the local transport regulations when transporting pr...

Страница 425: ... guidelines 419 FX3G Series Programmable Controllers User s Manual Hardware Edition 21 Memory Cassette 22 Battery A Special Devices M8000 D8000 B Instruction List C Discontinued models D Precautions for battery transportation E Handling of batteries in EU member states MEMO ...

Страница 426: ...e 2006 66 EC requires the following when marketing or exporting batteries and or devices with built in batteries to EU member states To print the symbol on batteries devices or their packaging To explain the symbol in the manuals of the products 1 Labelling To market or export batteries and or devices with built in batteries which have no symbol to EU member states on September 26 2008 or later pr...

Страница 427: ...8000 D8000 B Instruction List C Discontinued models D Precautions for battery transportation E Handling of batteries in EU member states FX3G Series Programmable Controllers User s Manual Hardware Edition Appendix E Handling of Batteries and Devices with Built in Batteries in EU Member States MEMO ...

Страница 428: ...e responsibility of Mitsubishi 1 Loss in opportunity lost profits incurred to the user by Failures of Mitsubishi products 2 Special damages and secondary damages whether foreseeable or not compensation for accidents and compensation for damages to products other than Mitsubishi products 3 Replacement by the user maintenance of on site equipment start up test run and other tasks 4 The Mitsubishi pr...

Страница 429: ...48ET DSS FX2N 48ER D FX2N 48ET D Analog special adapter FX3U 3A ADP Ver 1 20 is supported Supports FX3U 3A ADP Supports the hardware error function of FX3U 4DA ADP Precautions for Battery Transportation are added Appendix D Handling of Batteries and Devices with Built in Batteries in EU Member States are added Appendix E 3 2010 E Explanation corrections for manufacturer s serial number and lot num...

Страница 430: ...ed Supports the IP address change function of FX3U ENET ADP Ver 2 20 is supported Special auxiliary relay of FX3G 4EX BD FX3G 2EYT BD is added Appendix A Description of the programming tool is changed accompanied by change of the programming tool from GX Developer to GX Works2 Errors are corrected 4 2015 K A part of the cover design is changed 11 2015 L The following products is added Special func...

Страница 431: ......

Страница 432: ...ARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JY997D31301N MEE Effective January 2020 Specifications are subject to change without notice MODEL FX3G HW E MODEL CODE 09R521 FX3G SERIES PROGRAMMABLE CONTROLLERS USER S MANUAL Hardware Edition ...

Отзывы: