![Mitsubishi Electric FX2N-16E series Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/mitsubishi-electric/fx2n-16e-series/fx2n-16e-series_user-manual_238876076.webp)
6 Examination of System Configuration
6.2 Rules of System Configuration
70
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
6.2
Rules of System Configuration
The system configuration must meet the following four requirements.
1
Number of input/output points
The total number of input and output points should be 256 or less in the whole system.
→
For details, refer to 6.3 Number of Input/Output Points and Maximum Number of Input/Output
Points.
2
Number of connected special extension devices
The figure below shows the number of connectable expansion boards, special adapters, extension
power supply units
*1
and special function blocks. The connector conversion adapter (FX
3G
-CNV-
ADP) is required as the expansion board when special adapters are connected.
→
For details, refer to 6.4 Number of Connected Extension Devices (Including Extension Cable).
• FX
3G
Main units (40/60 point type)
• FX
3G
Main units (14/24 point type)
*1.
Available when the main unit is the AC power supply type.
CC-Link/LT
1. Number of input/output points (including input/output occupied points)
Up to 128 points
Main unit
Input/output
extension
unit/block
Special
function
block
· Expansion board
· Special adapter
· CC-Link master
· AnyWireASLINK
master
CC-Link/LT
master
CC-Link and AnyWireASLINK system
2. Number of remote I/O points on CC-Link and AnyWireASLINK
Up to 128 points
Remote I/O station
Remote I/O station
Remote I/O station
Remote I/O station
Remote I/O station
Remote I/O station
Remote I/O station
Remote I/O station
Number of input/output points on whole system
Up to 256 points
Main unit
40/60 point type
Special adapter
(communication)
Up to 2 units
Up to 2 units
Up to 2 units
Only 1 unit
Up to 2 units
Expansion
board
Special
adapter
(analog)
Input/output
powered
extension unit
Extension
power supply
unit
*1
Special
function block
Up to 8 units
Main unit
14/24 point type
Only 1 unit
Only 1 unit
Only 1 unit
Only 1 unit
Up to 2 units
Expansion
board
Special
adapter
(analog)
Input/output
powered
extension unit
Extension
power supply
unit
*1
Special
function block
Up to 8 units
Special adapter
(communication)