61
List of alarm display
5 TROUBLESHOOTING
When an alarm (major failures) occurs in the inverter, the protective function is activated bringing the inverter to an
alarm stop and the PU display automatically changes to any of the following error (alarm) indications.
If your fault does not correspond to any of the following errors or if you have any other problem, please contact your
sales representative.
•
Retention of alarm output signal .................. When the magnetic contactor (MC) provided on the input side of the inverter is
opened at the activation of the protective function, the inverter's control power
will be lost and the alarm output will not be held.
•
Alarm display ........................................... When the protective function is activated, the operation panel display
automatically switches to the above indication.
•
Resetting method............................................When the protective function is activated, the inverter output is kept stopped.
Unless reset, therefore, the inverter cannot restart.
(Refer to page 73.)
•
When the protective function is activated, take the corresponding corrective action, then reset the inverter, and
resume operation.
Not doing so may lead to the inverter fault and damage.
5.1 List of alarm display
* If an error occurs when using the FR-PU04, "Fault 14" is displayed on
the FR-PU04.
Operation Panel
Indication
Name
Refer
to
E
rro
r me
s
s
a
g
e
HOLD
Operation panel lock
Er1 to 4 Parameter write error
rE1 to 4 Copy operation error
Err.
Error
Wa
rn
in
g
s
OL
Stall prevention (overcurrent)
oL
Stall prevention (overvoltage)
RB
Regenerative brake prealarm
TH
Electronic thermal relay
function prealarm
PS
PU stop
MT
Maintenance signal output
CP
Parameter copy
Min
o
r faul
t
FN
Fan fault
Ma
jo
r fa
u
lt
E.OC1
Overcurrent shut-off during
acceleration
E.OC2
Overcurrent shut-off during
constant speed
E.OC3
Overcurrent shut-off during
deceleration or stop
E.OV1
Regenerative overvoltage
shut-off during acceleration
E.OV2
Regenerative overvoltage
shut-off during constant speed
E.OV3
Regenerative overvoltage shut-
off during deceleration or stop
E.THT
Inverter overload shut-off
(electronic thermal relay function)
E.THM
Motor overload shut-off
(electronic thermal relay function)
E.FIN
Fin overheat
E.IPF
Instantaneous power failure
E.BE
Brake transistor alarm
detection/internal circuit error
E.UVT
Undervoltage
E.ILF*
Input phase failure
E.OLT
Stall prevention
to
to
E.GF
Output side earth fault
overcurrent
E.LF
Output phase failure
E.OHT
External thermal relay
operation
*2
E.PTC* PTC thermistor operation
E.OPT
Option alarm
E.OP1
Communication option alarm
E. 1
Option alarm
E.PE
Parameter storage devide
alarm
E.PUE
PU disconnection
E.RET
Retry count excess
E.PE2*
Parameter storage devide
alarm
/
/
E. 6 /
E. 7 /
E.CPU
CPU error
E.CTE
Operation panel power
supply short circuit, RS-485
terminal power supply short
circuit
E.P24
24VDC power output short
circuit
E.CDO*
Output current detection
value exceeded
E.IOH*
Inrush current limit circuit
alarm
E.SER*
Communication error
(inverter)
E.AIE*
Analog input error
E.13
Internal circuit error
Operation Panel
Indication
Name
Refer
to