124
Extended p
a
ramete
r
li
s
t
Display of
t
he
lif
e of
t
h
e
invert
er p
a
rt
s
255
Life alarm status
display
1
0
(0 to 15)
Display whether the control circuit
capacitor, main circuit capacitor, cooling
fan, and each parts of the inrush current
limit circuit has reached the life alarm
output level or not.
×
×
×
256
Inrush current limit
circuit life display
1%
100%
(0 to 100%)
Display the deterioration degree of the
inrush current limit circuit. Reading only
×
×
×
257
Control circuit
capacitor life
display
1%
100%
(0 to 100%)
Display the deterioration degree of the
control circuit capacitor. Reading only
×
×
×
258
Main circuit
capacitor life
display
1%
100%
(0 to 100%)
Display the deterioration degree of the
main circuit capacitor. Reading only
The value measured by
Pr. 259
is
displayed.
×
×
×
259
Main circuit
capacitor life
measuring
1
0
0, 1
Start measuring the main circuit capacitor life.
Switch the power supply on again and
check the Pr. 259 setting. Measurement is
complete if the setting is "3". Set the
deterioration degree in
Pr.258
.
—
260
Refer to
Pr.72
.
Dec
e
le
rat
e
t
he m
o
to
r t
o
a st
op at
inst
ant
aneous power f
a
ilure
261
Power failure stop
selection
1
0
0
Coasting to stop
When undervoltage or power failure
occurs, the inverter output is shut off.
1
When undervoltage or a power failure
occurs, the inverter can be decelerated to
a stop.
2
When undervoltage or a power failure occurs,
the inverter can be decelerated to a stop.
If power is restored during a power failure, the
inverter accelerates again.
262
Subtracted
frequency at
deceleration start
0.01Hz
3Hz
0 to 20Hz
Normally operation can be performed with
the initial value unchanged. But adjust the
frequency according to the magnitude of
the load specifications (moment of inertia,
torque).
263
Subtraction starting
frequency
0.01Hz
50Hz
0 to 120Hz
When output frequency
≥
Pr.263
Decelerate from the speed obtained
from output frequency minus
Pr.262
.
When output frequency <
Pr.263
Decelerate from output frequency
9999
Decelerate from the speed obtained from
output frequency minus
Pr.262
.
264
Power-failure
deceleration time 1
0.1/
0.01s
5s
0 to 3600/
360s
Set a deceleration slope down to the
frequency set in
Pr.266
.
265
Power-failure
deceleration time 2
0.1/
0.01s
9999
0 to 3600/
360s
Set a deceleration slope below the
frequency set in
Pr.266
.
9999
Same slope as in
Pr.264
266
Power failure
deceleration time
switchover
frequency
0.01Hz
50Hz
0 to 400Hz
Set the frequency at which the
deceleration slope is switched from the
Pr.264
setting to the
Pr.265
setting.
—
267
Refer to
Pr.73
.
268
Refer to
Pr.52
.
269
Parameter for manufacturer setting. Do not set.
331 to 337
Refer to
Pr.117 to Pr.124
.
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled