113
Extended p
a
ramete
r
li
s
t
Ret
ry f
unct
ion at
alarm
o
ccurr
ence
65
Retry selection
1
0
0 to 5
An alarm for retry can be selected.
67
Number of retries at
alarm occurrence
1
0
0
No retry function
1 to 10
Set the number of retries at alarm
occurrence. An alarm output is not
provided during retry operation.
101 to 110
Set the number of retries at alarm
occurrence. (The setting value minus 100
is the number of retries.) An alarm output is
provided during retry operation.
68
Retry waiting time
0.1s
1s
0 to 10s
Set the waiting time from when an inverter
alarm occurs until a retry is made.
69
Retry count display
erase
1
0
0
Clear the number of restarts succeeded
by retry.
—
66
Refer to
Pr.22 and Pr.23
.
67 to 69
Refer to
Pr.65
.
—
70
Refer to
Pr.30
.
Us
e t
he c
onst
ant
to
rque m
o
to
r
(applied m
o
to
r)
71
Applied motor
1
0
0
Thermal characteristics of a standard
motor
1
Thermal characteristics of the Mitsubishi
constant-torque motor
2
Thermal characteristic of standard motor
Adjustable 5 points V/F
20
Mitsubishi standard motor (SF-JR 4P
1.5kW or less)
Carrier f
requency
and Sof
tP
W
M
sel
e
ct
io
n
72
PWM frequency
selection
1
2
0 to 15/
0 to 6, 25
PWM carrier frequency can be changed.
The setting displayed is in [kHz].
Note that 0 indicates 0.7kHz, 15 indicates
14.5kHz and 25 indicates 2.5kHz.
*12 The setting depends on the inverter
capacity (01160 or less/01800 or more)
240
Soft-PWM
operation selection
1
1
0
Soft-PWM invalid
1
When
Pr. 72
="0 to 5" ("0 to 4" for the 01800 or
more), Soft-PWM is valid.
260
PWM frequency
automatic switchover
1
1
0
PWM carrier frequency is constant
independently of load.
When the carrier frequency is set to 3kHz
or more (Pr. 72
≥
3), perform continuous
operation at less than 85% of the rated
inverter current.
1
Decreases PWM carrier frequency
automatically when load increases.
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled
Содержание FR-F 700 EC