When the rated motor frequency is 50Hz (Pr. 3)
First, check the motor rating plate. If a frequency given on the rating plate is "50Hz" only, always set
Pr. 3 Base frequency
to "50Hz". Leaving the base frequency unchanged from "60Hz" may make the voltage low and the torque insufficient. It
may result in an inverter trip (E.OC
) due to overload.