111
Selection of contr
ol meth
od
80
Motor capacity
0.01kW
9999
0.4 to 55kW Set the applied motor capacity.
{
{
{
9999
V/F control is performed
81
Number of motor
poles
1
9999
2, 4, 6, 8, 10 Set the number of motor poles.
{
{
{
12, 14, 16,
18, 20
X18 signal-ON:V/F
control
Set 10 + number of
motor poles.
9999
V/F control is performed
89
Speed control gain
(magnetic flux
vector)
0.1%
9999
0 to 200%
Motor speed fluctuation due to load
fluctuation is adjusted during advanced
magnetic flux vector control.
100% is a referenced value.
{
×
{
9999
Gain matching with the motor set in
Pr.71
.
451
Second motor
control method
selection
1
9999
10, 11, 12
Select the method of controlling the
second motor. (same as
Pr.800
)
{
{
{
20, 9999
V/F Control (advanced magnetic flux
vector control)
453
Second motor
capacity
0.01kW
9999
0.4 to 55kW Set the capacity of the second motor.
{
{
{
9999
V/F control is performed
454
Number of second
motor poles
1
9999
2, 4, 6, 8, 10
Set the number of poles of the second
motor.
{
{
{
9999
V/F control is performed
569
Second motor
speed control gain
0.1%
9999
0 to 200%
Second motor speed fluctuation due to
load fluctuation is adjusted during
advanced magnetic flux vector control.
100% is a referenced value.
{
×
{
9999
Gain matching with the motor set in
Pr.450
.
800
Control method
selection
1
20
0
Speed control
Vector control
(FR-A7AP)
{
{
{
1
Torque control
2
MC signal-ON:torque
MC signal-OFF:speed
3
Position control
4
MC signal-ON:position
MC signal-OFF:speed
5
MC signal-ON:torque
MC signal-OFF:position
9
Vector control test operation
Test operation of vector control (speed control)
can be performed without connecting a motor.
10
Speed control
Real sensorless
vector control
11
Torque control
12
MC signal-ON :
Torque
MC signal-OFF :
Speed
20
V/F Control (advanced magnetic flux
vector control)
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Para
meter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
mete
rs
{
: enabled
×
: disabled
Magnetic fluxM
a
g
n
e
ti
c
f
lu
x
Magnetic flux
SensorlessS
e
n
s
o
rl
e
s
s
Sensorless
VectorV
e
c
to
r
Vector