![Mitsubishi Electric FR-A720-55K Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/mitsubishi-electric/fr-a720-55k/fr-a720-55k_instruction-manual_239754036.webp)
31
MOTOR THERMISTOR INTERFACE
6
6.2
Terminals
6.3
Motor thermistor parameter
6.3.1 Parameter list
Parameters below are used for motor thermistor interface.
Following parameters are available only when used with FR-A7AZ.
* The parameter number in parentheses is the one for use with the parameter unit (FR-PU07/FR-PU04).
Terminal
Symbol
Terminal Name
Description
TH1
Thermistor input 1
Input the motor side thermistor output signal.
TH2
Thermistor input 2
SW2
Thermistor calibration
status switch
When calibrating at installation, change the
switch to place the inverter in calibration status.
Parameter
Number
Name
Setting Range
Minimum
Increments
Initial
Value
407
Motor temperature detection filter
0 to 100s, 9999
1
9999
408
Motor thermistor selection
0, 1
1
0
750
Motor temperature detection level
0 to 200°C
1°C
75°C
751
Reference motor temperature
1 to 200°C
1°C
150°C
C29 (925) *
Motor temperature detection calibration (analog input)
0 to 200%
0.1%
100%
5
TST
5
5
5
TH2
6
TST
DA1
5
5
TH1
SW2