HIGH RESOLUTION ANALOG INPUT
(2) Calibration of speed command/speed limit (
Pr. 406
= "0, 5")
When
Pr. 406
= "0, 5", terminal 6 acts as speed command or speed limit input and
C30 to C33
are used
for calibration parameter.
(3) Calibration of torque command/torque limit (
Pr. 406
= "2, 3, 4")
When
Pr. 406
= "2, 3, 4" under Real sensorless vector control or vector control, terminal 6 acts as
torque command or torque limit input and
C34 to C 37
are used for calibration parameters.
Gain
C32 (Pr. 927)
Bias
C30 (Pr. 926)
Input voltage
60Hz
60Hz
Frequency
Initial value
0
10V
-10V
C33 (Pr. 927)
C31
(Pr. 926)
Output torque
Gain
C36 (Pr. 929)
Input voltage
150%
150%
0
10V
Bias
C34 (Pr. 928)
Initial value
-10V
Output torque
Gain
C36 (Pr. 929)
Input voltage
150%
0
10V
-10V
Bias
C34 (Pr. 928)
Initial value
<Torque limit, regenerative torque limit>
<Torque command>
Torque limit value
is clamped at 0%.
C37
(Pr. 929)
C35
(Pr. 928)
C37
(Pr. 929)
C35
(Pr. 928)