10-7. Test point diagram
FTC3 (Controller board)
48
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
LED2
Power supply
(Main controller)
LED1
Power supply
(FTC3)
LED3
Transmission
(Indoor/outdoor)
CNP/OUT1 (TBO.1 1-2)
Water circulation pump1
(230V AC)
F3
6.3A/250V
F4
6.3A/250V
F2
6.3A/250V
CN01
Power supply
(230V AC)
F1
6.3A/250V
VDD 5V
(DC5V ± 0.25V)
VDD 13V
(DC13V ± 0.6V)
IN4
(TBI.2 13-14)
Heat source
OFF input
OUT2 (TBO.1 3-4)
Water circulation pump2
(field supply) (230V AC)
CNV1/OUT4 (TBO.1 7-9)
3-way valve (field supply) (7-8:230V AC)
OUT4 (TBO.1 7-8)
2-way valve (field supply) (7-8:230V AC)
CNBHT/BHT (TBO.2 1-2)
Thermostat input for
booster heater
CNBC/BC (TBO.2 3-4)
Signal output for booster
heater protection (230V AC)
CNBH(1-3)/OUT6 (TBO.2 5-6)
Signal output for booster
heater1 (230V AC)
CNBH(5-7)/OUT7 (TBO.2 7-8)
Signal output for booster
heater2 (230V AC)
OUT8 (TBO.2 9-10)
Signal output for booster
(230V AC)
OUT11 (TBO.2 11-12)
Signal output (Error)
(230V AC)
OUT12 (TBO.2 13-14)
Signal output (Defrost)
(230V AC)
CNIHT/IHT (TBO.3 1-2)
Thermostat input for
immersion heater (field supply)
CNIH/OUT9 (TBO.3 5-6)
Signal output for immersion
heater (field supply) (230V AC)
TH1/TH1 (TBI.1 1-2)
Thermistor
(Room temperature)
TH2/TH2 (TBI.1 3-4)
Thermistor
(Ref. liquid temperature)
THW12(1-2)/
THW1(TBI.1 5-6)
Thermistor
(Flow water temperature)
THW12(3-4)/
THW2(TBI.1 7-8)
Thermistor
(Return water
temperature)
THW5(3-4)/
THW5B(TBI.1 11-12)
Thermistor
(Tank water temperature)
THW3/
THW3(TBI.2 3-4)
Thermistor (Booster
heater temperature)
IN1(TBI.2 5-6)
Room thermostat
input
CN2F/IN2(TBI.2 7-8)
Flow switch input
CN22/RC(TBI.2 11-12)
Main controller
(10.4 - 13.7 V DC)
IN5
(TBI.3 7-8)
Outdoor
thermostat input
OUT13 (TBO.3 7-8)
2-way valve2 (field supply)