S1
S2
S3
L
N
L
N
BLACK
BLACK
YELLOW
YELLOW
YELLOW
YELLOW
BLACK
BLACK
CNO1
CNO1
CNO1
Black
CNO1
Black
Hydrobox
control board
Hydrobox
control board
S1
S2
S3
Initial settings
(Power supplied
by outdoor unit)
Modified settings
(Separate power
supply to
the hydrobox)
Power
supply
~/N
230V
50Hz
Earth
leakage
breaker
Wiring
circuit
breaker
or
Isolating
switch
L
N
S1
S2
S3
Outdoor unit
S1
S2
S3
TB1
L
N
ECB1
Wiring
circuit
breaker
or
Isolating
switch
To control
board
ELB for
booster
heater
(Primary circuit)
L
N
Power
supply
~/N
230V
50Hz
Earth
leakage
breaker
Wiring
circuit
breaker
or
Isolating
switch
Power
supply
~/N
230V
50Hz
Hydrobox
18
Option2: Hydrobox powered by independent source.
If the hydrobox and outdoor units have separate power supplies, the following
requirements MUST be carried out:
• Hydrobox electrical box connector connections changed (see Figure
4.5.6)
• Outdoor unit DIP switch settings changed to SW8-3 ON.
• Turn on the outdoor unit BEFORE the hydrobox.
<1 phase>
<Figure 7-4>
Electrical connections 1 phase
<Figure 7-3>
Description
Power supply
Capacity (Indoor unit Ref.) Breaker
Wiring
Booster heater (Primary circuit)
~/N 230 V 50 Hz
2 kW (EHPX-VM2A)
16 A *1
2.5 mm²
6 kW (EHSC-VM6A)
32 A *1
6.0 mm²
Hydrobox power supply
~/N 230 V 50 Hz
Hydrobox input capacity
Main switch (Breaker)
*1
16 A
Wiring
Wiring No.
× size (mm²)
Hydrobox power supply
2 × Min. 1.5
Hydrobox power supply earth
1 × Min. 1.5
Hydrobox - Outdoor unit
*2
2 × Min. 0.3
Hydrobox - Outdoor unit earth
—
Circuit
rating
Hydrobox L - N
*3
AC230V
Hydrobox - Outdoor unit S1 - S2
*3
—
Hydrobox - Outdoor unit S2 - S3
*3
DC24V
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*2. Max. 120 m
*3. The values given in the table above are not always measured against the ground value.
Notes: 1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed
fl
exible cord. (Design 60245 IEC 57)
Indoor unit power supply cords shall not be lighter than polychloroprene sheathed
fl
exible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
4. The power supply MUST have suf
fi
cient capacity for each heater and ALL electrical loads. Insuf
fi
cient power supply may result in
chattering of load contactor(s).
* Installer MUST af
fi
x label B that is included with the manuals near each wiring diagram for hydrobox and outdoor units.
Содержание EHSC-VM6A