Part Name
Check Points
Booster heater
Measure the resistance between the terminals with a tester.
Thermostat (90 °C) and thermal cut out (121 °C)
90 °C
Manual reset
water
thermostat
121 °C
Thermal
cut-out
AWG18
AWG18
9
10
Terminal
Normal
Abnormal
9-10
110(±35)m
Ω
Open or Short
2kW heater (230V, 1 phase)
1
2
2kW
AWG15 FEP
WHITE
AWG15 FEP
WHITE
Terminal
Normal
Abnormal
1-2
26.5(+3/-1.3)
Ω
Open or Short
2 + 4kW heater (230V, 1 phase)
1
2
2kW
AWG15 FEP
WHITE
AWG15 FEP
WHITE
3
4
2kW
AWG13 FEP
BLUE
AWG13 FEP
BLUE
2kW
Terminal
Normal
Abnormal
1-2
26.5(+3/-1.3)
Ω
Open or Short
3-4
13.3(+1.5/-0.6)
Ω
Open or Short
3 + 6kW heater (400V, 3 phase)
5
6
AWG15 FEP
WHITE
AWG15 FEP
WHITE
AWG13 FEP
BLUE
2kW
4
AWG15 FEP
WHITE
2kW
2kW
2
3
1kW
1
1kW
1kW
AWG13 FEP
BLUE
AWG13 FEP
BLUE
Terminal
Normal
Abnormal
1-2=2-3=1-3
105.8(+11.8/-5)
Ω
Open or Short
4-5=5-6=4-6
52.9(+5.8/-2.5)
Ω
Open or Short
Flow switch
Measure the resistance between the terminals with a tester.
State of moving part
Normal
Abnormal
Paddle vertical (Flow < 5.5 l/min)
Open
Other than open
Paddle inclined (Flow > 5.5 l/min)
Short
Other than short
Thermistors
Disconnect the connector then measure the resistance with a tester.
(At ambient temperatures of 10 - 30°C.)
Thermistor Normal Abnormal
TH1
4.3 - 9.5 k
Ω
Open or short
TH2
THW1
THW2
THW5B
THW3
160 - 410 k
Ω
Flow
1
2
3
46