VII
Control ]
- 76 -
HWE1312A
GB
[When the operation Start/End times do not overlap]
If "Start time1 - End time 1", "Start time 2 - End time 2", "Start time 3 - End time 3" overlap, the settings for the period with a larger
number will be ineffective.
[When operation period 1 and 2 overlap]
If two or more operation periods overlap, the settings for the period with a larger number will be ineffective.
If Start time 1 and start time 3 are set to the same value, the setting for Start time 3 will be ineffective.
Set the setting for Start time 3 to a time at least one minute after End time 1.
(Once the compressor stops when End time 1 comes, the 3-minute restart delay function will keep the compressor from restarting for
three minutes. Because of this, even if Start 3 time is set to a time within three minutes after End time 1, the compressor will not start
right away.)
[When operation periods 1 and 3 overlap]
[When operation periods 2 and 3 overlap]
[When operation periods 2 and 3 overlap]
(*) Refer to the section on how to select the preset water temperatures on the next page.
Operation Period 1
Operation Period 2
Operation Period 3
Target water temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 2
Item code 1219 setting
ON
Operation Period 3
Item code 1220 setting
ON
Operation Period 1
Item code 1218 setting
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
Item code 1220 setting
ON
Operation Period 1
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
Item code 1220 setting
ON
Operation Period 1
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
Item code 1219 setting
ON
Operation Period 1
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
ON
Operation Period 1
Содержание CRHV-P600YA-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE1312A GB ...
Страница 9: ... 2 HWE1312A GB ...
Страница 19: ... 12 HWE1312A GB ...
Страница 41: ... II Restrictions 34 HWE1312A GB ...
Страница 43: ... 36 HWE1312A GB ...
Страница 51: ... III Unit Components 44 HWE1312A GB ...
Страница 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Страница 53: ... 46 HWE1312A GB ...
Страница 61: ... IV Remote Controller 54 HWE1312A GB ...
Страница 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Страница 63: ... 56 HWE1312A GB ...
Страница 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Страница 68: ... 61 HWE1312A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 63 2 Principal Parts and Functions 64 ...
Страница 69: ... 62 HWE1312A GB ...
Страница 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Страница 75: ... 68 HWE1312A GB ...
Страница 107: ... VII Control 100 HWE1312A GB ...
Страница 109: ... 102 HWE1312A GB ...
Страница 117: ... 110 HWE1312A GB ...
Страница 165: ... IX Troubleshooting 158 HWE1312A GB ...
Страница 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Страница 167: ... 160 HWE1312A GB ...
Страница 170: ......