VII
Control ]
- 79 -
HWE1312A
GB
(4) Peak-demand control operation
Peak-demand control is a function used to control the power consumptions of the units during peak-demand hours.
The number of units in operation and the compressor's maximum operating frequency will be controlled
according to the peak-demand control signal.
Individual system control
Multiple system control
Individual unit control
Maximum frequency = Maximum capacity under peak-
demand control
Depending on the peak-demand control setting that is
made on the main unit, the number of units in operation
and the maximum operating frequency of the units in
operation will be adjusted.
Setting procedures
Set the maximum capacity setting on the circuit board.
Step 0
Set the ON/OFF
switch (SWS1) to
OFF.
Set SWS1 to OFF from the remote controller or with the local switch.
Settings cannot be changed unless the ON/OFF setting is set to OFF.
Step 1
Set the dip switches
SW2 and SW3.
Set the dip switches on the circuit board as follows before making the settings for the items
described in this section.
Step 2
Select the desired
item with the push
switch SWP3.
Press the push switch SWP3 to select item code 2.
Press the push switches SWP1 or SWP2 to change the value of the selected item.
The value will keep blinking while it is being changed.
Step 3
Press the push
switches SWP1 (↑)
or SWP2 (↓) to
increase or
decrease the value.
Step 4
Press the push
switch SWP3 to
save the change.
Press SWP3 once within one minute of changing the setting with SWP1 or SWP2 to save the
setting.
Once the new setting is saved, the display will stop blinking and stay lit. The display will, then,
return to the item code display mode.
If SWP3 is not pressed within one minute, the change will not be saved and the display will
return to the item code display mode.
(*) If the peak-demand control contact is ON, units will operate at the maximum capacity that
was set in the steps above.
SW2
SW3
-10
5
6
7
8
9
10
OFF
OFF
OFF
OFF
OFF
ON
OFF
Settings table
Items that can be set
Item
code
Initial
value
Unit
Setting
Setting change
from an optional
remote controller
Increments
Lower
limit
Upper
limit
Maximum capacity setting
2
100
%
5%
0
100
Not possible
Peak-demand control start time
3
1300
Hour: minute
1
0000
2359
Not possible
Peak-demand control end time
4
1300
Hour: minute
1
0000
2359
Not possible
Содержание CRHV-P600YA-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE1312A GB ...
Страница 9: ... 2 HWE1312A GB ...
Страница 19: ... 12 HWE1312A GB ...
Страница 41: ... II Restrictions 34 HWE1312A GB ...
Страница 43: ... 36 HWE1312A GB ...
Страница 51: ... III Unit Components 44 HWE1312A GB ...
Страница 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Страница 53: ... 46 HWE1312A GB ...
Страница 61: ... IV Remote Controller 54 HWE1312A GB ...
Страница 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Страница 63: ... 56 HWE1312A GB ...
Страница 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Страница 68: ... 61 HWE1312A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 63 2 Principal Parts and Functions 64 ...
Страница 69: ... 62 HWE1312A GB ...
Страница 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Страница 75: ... 68 HWE1312A GB ...
Страница 107: ... VII Control 100 HWE1312A GB ...
Страница 109: ... 102 HWE1312A GB ...
Страница 117: ... 110 HWE1312A GB ...
Страница 165: ... IX Troubleshooting 158 HWE1312A GB ...
Страница 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Страница 167: ... 160 HWE1312A GB ...
Страница 170: ......