VII
Control ]
- 84 -
HWE1312A
GB
(9) Setting the capacity control ratio using analog signal input
• When dip switch SW2-7 is set to ON (Enable external input) and item code 1051 is set to "1", the capacity control
ratio varies with the type of analog input signal.
• When the water temperature setting input signal type is set to 0 (4-20 mA)
• External analog input signal of 4-6 mA: 0%
• External analog input signal of 18-20 mA: 100%
• External analog input signal of between 6 and 18 mA: the percent will be linearly interpolated.
• When the water temperature setting input signal type is set to 1 (0-10 V)
• External analog input signal of 0-1 V: 0%
• External analog input signal of 9-10 V: 100%
• External analog input signal of between 1 and 9 V: the percent will be linearly interpolated.
• When the water temperature setting input signal type is set to 2 (1-5 V)
• External analog input signal of 1-1.5 V: 0%
• External analog input signal of 4.5-5 V: 100%
• External analog input signal of between 1.5 and 4.5 V: the percent will be linearly interpolated.
• When the water temperature setting input signal type is set to 3 (2-10 V)
• External analog input signal of 2-3 V: 0%
• External analog input signal of 9-10 V: 100%
• External analog input signal of between 3 and 9 V: the percent will be linearly interpolated.
100%
0%
6 mA
Input current
18 mA
Load ratio
*%
4 mA
20 mA
100%
0%
0 V
Input voltage
9 V
Load ratio
*%
1 V
10 V
100%
0%
1.5 V
Input voltage
4.5 V
Load ratio
*%
5 V
1 V
100%
0%
3 V
Input voltage
9 V
Load ratio
*%
2 V
10 V
*%: When the compressor frequency drops below 30 Hz, the compressor stops.
The frequency value that causes the compressor to stop varies depending on the outside temperature and water temperature.
Содержание CRHV-P600YA-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE1312A GB ...
Страница 9: ... 2 HWE1312A GB ...
Страница 19: ... 12 HWE1312A GB ...
Страница 41: ... II Restrictions 34 HWE1312A GB ...
Страница 43: ... 36 HWE1312A GB ...
Страница 51: ... III Unit Components 44 HWE1312A GB ...
Страница 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Страница 53: ... 46 HWE1312A GB ...
Страница 61: ... IV Remote Controller 54 HWE1312A GB ...
Страница 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Страница 63: ... 56 HWE1312A GB ...
Страница 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Страница 68: ... 61 HWE1312A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 63 2 Principal Parts and Functions 64 ...
Страница 69: ... 62 HWE1312A GB ...
Страница 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Страница 75: ... 68 HWE1312A GB ...
Страница 107: ... VII Control 100 HWE1312A GB ...
Страница 109: ... 102 HWE1312A GB ...
Страница 117: ... 110 HWE1312A GB ...
Страница 165: ... IX Troubleshooting 158 HWE1312A GB ...
Страница 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Страница 167: ... 160 HWE1312A GB ...
Страница 170: ......