IX
Troubleshooting ]
- 118 -
HWE1312A
GB
Maintenance item (1) list
Item
code
Incre-
ments
Lower
limit
Upper
limit
Default
Switch
setting
timing
Unit type
Notes
Main unit
Sub unit
MAIN circuit SUB circuit MAIN circuit SUB circuit
Forcing the units in a specific system to stop
1004
1
0
3
0
○
-
○
-
(Note1)
Outlet water temperature sensor correction (hot water)TH12
1009
-
-
-
-
-
○
-
○
-
(Note2)
Outlet water temperature sensor correction (hot water)TH18
1010
-
-
-
-
-
-
○
-
○
Inlet water temperature sensor correction (hot water)TH11
1011
-
-
-
-
-
○
-
○
-
Start/End time setting 1 Water temp setting
1
1
3
1
○
-
-
-
Start/End time setting 2 Water temp setting
1218
1219
1220
1
1
3
1
○
-
-
-
Start/End time setting 3 Water temp setting
1
1
3
1
When unit is stopped
When unit is stopped
When unit is stopped
When unit is stopped
When unit is stopped
When unit is stopped
When unit is stopped
When unit is stopped
When unit is stopped
○
-
-
-
Inlet water temperature sensor correction (hot water)TH17
1012
-
-
-
-
-
-
○
-
○
Representative water temperature sensor correction
(hot water)TH15
1013
-
-
-
-
-
○
-
-
-
Representative water temperature sensor correction
(hot water)TH16
1014
-
-
-
-
-
○
-
-
-
Built-in thermistor differential DIFF1
1015
-
-
-
-
-
○
○
○
○
(Note3)
Built-in thermistor differential DIFF2
1016
-
-
-
-
-
○
○
○
○
Cumulative operation time of the compressor
1017
-
-
-
-
Can be reset
only when unit
is stopped
○
○
○
○
(Note4)
(Note5)
(Note6)
Cumulative operation time of the compressor
(Unit: 10,000 hours)
1018
-
-
-
-
Can be reset
only when unit
is stopped
○
○
○
○
(Note4)
(Note5)
(Note6)
(Note7)
Temperature data collection interval (S seconds)
1019
1 second
1
9999
60
○
○
○
○
(Note8)
Multiple system Thermo-ON/OFF status check interval
1020
1 minute
1
5
1
○
-
-
-
(Note9)
1215
1
14
15
14
○
-
-
-
Representative water temperature thermistor while the
"Temperature shift (Setting temperature B)" function is enabled.
Representative water temperature thermistor while the
"Temperature shift (Setting temperature A)" function is enabled.
1216
1
14
15
14
○
-
-
-
(Note10)
Representative water temperature thermistor while the
"Temperature shift (Setting temperature C)" function is enabled.
1217
1
14
15
14
○
-
-
-
(Note11)
(Note1) Do not use this item. (Stop the units in a given system by setting the slide switch SWS1 to OFF.)
(Note2) Consult your nearest Mitsubishi representative if the sensors go off below the preset values.
(Note3) Consult your nearest Mitsubishi representative.
(Note4) These items can only be displayed. (Their settings cannot be changed.)
(Note5) The cumulative time between 1 and 9999 hours will be displayed in four digits. (unit: hour)
(Note6) Pressing the push switches SW01 and SW02 simultaneously while the time is displayed will reset (initialize) the data to 0.
(Note7) The cumulative time between 10,000 and 99,990,000 hours will be displayed in four digits (unit: 10000 hours)
(Note8) Set the data collection interval by referring to section “3. Operation status before error”. (Page 115)
(Note9) The Thermo-ON/OFF status check interval can be adjusted to optimize the ON/OFF operation when the piping length to the load side is long and the
detection of changes in water temperature tends to lag behind.
(Note10) Set these settings when using both external thermistors TH15 and TH16 and switching between the two according to the preset water temperature.
(Heating temperature = A°C, Hot water temperature = B °C, Heating ECO temperature = C °C)
(Note11) Set these settings when changing the temperature settings for the units by using the schedule function of the control board.
(Heating temperature: 1
Hot water temperature: 2, Heating ECO temperature: 3)
Содержание CRHV-P600YA-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE1312A GB ...
Страница 9: ... 2 HWE1312A GB ...
Страница 19: ... 12 HWE1312A GB ...
Страница 41: ... II Restrictions 34 HWE1312A GB ...
Страница 43: ... 36 HWE1312A GB ...
Страница 51: ... III Unit Components 44 HWE1312A GB ...
Страница 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Страница 53: ... 46 HWE1312A GB ...
Страница 61: ... IV Remote Controller 54 HWE1312A GB ...
Страница 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Страница 63: ... 56 HWE1312A GB ...
Страница 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Страница 68: ... 61 HWE1312A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 63 2 Principal Parts and Functions 64 ...
Страница 69: ... 62 HWE1312A GB ...
Страница 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Страница 75: ... 68 HWE1312A GB ...
Страница 107: ... VII Control 100 HWE1312A GB ...
Страница 109: ... 102 HWE1312A GB ...
Страница 117: ... 110 HWE1312A GB ...
Страница 165: ... IX Troubleshooting 158 HWE1312A GB ...
Страница 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Страница 167: ... 160 HWE1312A GB ...
Страница 170: ......