Startup sequence rotation
-2- Initial control
When the power is turned on, the initial processing of the microcomputer is given top priority.
During the initial processing, processing of the operation signal is suspended and is resumed after the initial processing is
completed.
(Initial processing involves data processing by the microcomputer and initial setup of the LEV opening. This process takes up
to two minutes.)
During the initial processing ”
” will appear on the LED monitor on the MAIN board.
Initial Control
-3- Compressor frequency
The upper limit of frequency during the first 30 seconds of operation is 48 Hz.
The upper limit of frequency during the first 90 seconds of operation is 60 Hz.
If the water temperature is controlled based on the outlet water temperature (SW3-3 is set to OFF.), for 90 seconds after the
startup, the compressor will be controlled every 30 seconds so that the frequency fluctuation will be kept within ± 5 Hz.
If the water temperature is controlled based on the external water temperature sensor reading or the inlet water temperature
(SW3-3 is set to ON.), for 90 seconds after the startup, the compressor will be controlled every 30 seconds so that the fre-
quency fluctuation will be kept within ± 10 Hz.
(The above does not apply when the high-pressure is suppressed to protect the system or when the defrost operation is in
progress.)
The amount of frequency change is controlled to approximate the target value that are determined based on the temperature
difference between the current and the preset water temperatures.
The minimum operating frequency is 30 Hz.
The maximum frequency will be determined based on the relationship between the hot water temperature and the heat source
inlet temperature as well as the ON/OFF status of the Energy-save/Maximum capacity contact.
(The values not on listed in the table are interpolated.)
"Energy-save/Maximum capacity" contact is ON.
(
Maximum frequency of the compressor
Hz
)
°C
-
3
2
4
5
7
9
12
15
17
22
27
32
37 or above
°C
35
100
100
100
45
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
60
76
77
80
80
80
80
80
80
80
80
80
80
80
65
75
-
8
100
100
75
75
78
78
78
78
78
78
78
78
78
78
78
78
Hot water
temperature
Heat source inlet temp.
°C
-
3
2
4
5
7
9
12
15
17
22
27
32
37 or above
°C
35
69
62
60
58
56
53
50
47
46
43
43
42
42
-
8
79
71
66
63
61
59
57
53
51
49
46
46
45
45
80
70
67
69
67
65
63
61
59
57
55
53
54
54
77
70
70
68
68
68
66
62
61
60
57
54
53
54
76
Hot water
temperature
Heat source inlet temp.
"Energy-save/Maximum capacity" contact is OFF.
(
Maximum frequency of the compressor
Hz
)
45
60
65
Содержание CRHV-P600YA-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE1312A GB ...
Страница 9: ... 2 HWE1312A GB ...
Страница 19: ... 12 HWE1312A GB ...
Страница 41: ... II Restrictions 34 HWE1312A GB ...
Страница 43: ... 36 HWE1312A GB ...
Страница 51: ... III Unit Components 44 HWE1312A GB ...
Страница 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Страница 53: ... 46 HWE1312A GB ...
Страница 61: ... IV Remote Controller 54 HWE1312A GB ...
Страница 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Страница 63: ... 56 HWE1312A GB ...
Страница 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Страница 68: ... 61 HWE1312A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 63 2 Principal Parts and Functions 64 ...
Страница 69: ... 62 HWE1312A GB ...
Страница 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Страница 75: ... 68 HWE1312A GB ...
Страница 107: ... VII Control 100 HWE1312A GB ...
Страница 109: ... 102 HWE1312A GB ...
Страница 117: ... 110 HWE1312A GB ...
Страница 165: ... IX Troubleshooting 158 HWE1312A GB ...
Страница 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Страница 167: ... 160 HWE1312A GB ...
Страница 170: ......